HomeMy WebLinkAboutREVIEW REPORT - BUILDING - 2-27-2018 - 18-00092 - 155 W 2nd S Suite 190 & 290 - Righteous Slice PizzaReview
Report
Current Building Review Status: REVISIONS
Application Number: 18-00092Permit Details
Application Received Date: 02/15/2018
Commercial Tenant Finish
Application Approved Date:
Application Approved Status: ACPTW/COND
02/15/2018
155 W 2nd S
Righteous Slice Pizza
Status of Plan Reviews Completed
02/16/2018Electrical Review COMPLETED
02/22/2018HVAC Review COMPLETED
02/22/2018Plumbing Review COMPLETED
02/27/2018Building Review REVISIONS
03/14/2018Fire Alarm Review COMPLETED
Permit Review Status
Plan Reviews Still in Progress
Building Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Exit Access meets the requirements of IBC
Section 1016
REVISIONS* Add exit sign on main floor near area under
top of stairs with directional arrow pointing to
north exit.
* Have "EXIT" display on both sides of sign at
top of stairs.
* Directional exit sign may be required closer to
upper dining area from south exit if sign is not
readily visible at door.
*Revisions Response :
Occupant load is identified on plans as per IBC
Section 1004
REVISIONS147 noted under code summary (allowed?). 98
is total under "occupant load schedule". 87 in
seating alone. TOTAL OCCUPANT LOAD?
* Occupant load of the assembly space must be
posted per 1004.3
*Revisions Response :
Doors meet the requirements of IBC Section
1010
REVISIONSEgress doors shall be of the swinging type -
Only door from kitchen is a sliding door.
*Revisions Response :
Panic Hardware shall be installed as per IBC
Section 1010.1.10
Exit doors are part of building shell. Due to the
A-2 occupancy, panic hardware is required on
egress doors serving assembly areas.
COMPLETED
Reviewed By: Quinton Owens
Review Date: 02/27/2018
Plan Review Details
quinton.owens@rexburg.org
Building Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Building Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Penetrations comply with IBC Section 714 for
rated assemblies
Maintain fire rating of all membrane and
through penetrations at fire rated assemblies.
Approval based on inspections.
COMPLETED
Concealed spaces are fireblocked/draftstopped
per Section 718
Fire blocking shall comply with 718 and will be
approved based on inspections.
COMPLETED
Service Facilities comply with IBC 1109.12 Service/Point of sales counters shall have at
least 36" of counter length no more than 36"
above the floor.
COMPLETED
Glass and Glazing meets the requirements of IBC
Chapter 24
Glazing on exterior wall (part of building shell
permit) in hazardous locations shall be safety
glazing.
COMPLETED
I-1, R-1, R-2, & R-3 units have separation as per
IBC Section 420
Maintain 1 hour separation to dwelling units
above.
COMPLETED
Additional Inspector Comments:
Review for tenant space remodel only. Building shell reviewed under permit 16-00038.
Page 2 of 2
Approval of plans does not constitue approval of variance from code