Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
PLANS - 18-00164 - 772 Nina Dr - Solar Panels
CONTRACTOR INFORMATIONDESIGNED BYSOLAR PHOTOVOLTAIC SYSTEMDATEISSUED FOR: PERMIT PROJECT INFORMATION, VICINITY MAP P V - 1 MSPSUBACDCSLCMINVRDCBFMC M A I N S E R V I C E P A N E L S U B S E R V I C E P A N E L A C D I S C O N N E C T D C D I S C O N N E C T S O L A R L O A D C E N T E R M O N I T O R I N G M E T E R I N V E R T E R R A P I D D I S C O N N E C T C O M B I N E R B O X F L E X I B L E M E T A L L I C C O N D U I T ( E ) ( N ) E X T I N T E M T R M T V O C V M P I S C N T S E X I S T I N G N E W E X T E R I O R I N T E R I O R E L E C T R I C A L M E T A L L I C T U B I N G R I G I D M E T A L L I C T U B I N G V O L T A G E O P E N C I R C U I T V O L T A G E A T M A X . P O W E R S H O R T C I R C U I T C U R R E N T N O T T O S C A L E I M P C U R R E N T A T M A X . P O W E R P V - 1 P R O J E C T I N F O R M A T I O N , V I C I N I T Y M A P P V - 1 A S I T E P L A N P V - 2 A R R A Y L A Y O U T P V - 3 E L E C T R I C A L L I N E D I A G R A M A N D N O T E S P V - 4 E L E C T R I C A L C A L C U L A T I O N , M A T E R I A L L I S T P V - 4 A R E Q U I R E D S I G N A G E ADDITIONAL NOTES P L A N S E T L E G E N D A B B R E V I A T I O N S P R O J E C T I N F O R M A T I O N V I C I N I T Y M A P A P P L I C A B L E C O D E S S H E E T I N D E X 3 6 X 2 9 0 W R E C P H O T O V O L T A I C M O D U L E S 1 X 1 0 0 0 0 W S O L A R E D G E 1 0 K W S Y S T E M S I Z E : 1 0 . 4 4 k W D C S T C A R R A Y A R E A : 6 1 0 S F T I M S T O W E L L 7 7 2 N I N A D R R E X B U R G , I D 8 3 4 4 0 2 0 8 - 2 0 1 - 5 5 9 1 JB J U N C T I O N B O X P R O J E C T S I T E ALL CONDUIT TO RUN ON EXTERIOROF HOUSE UNLESS OTHERWISE NOTEDOCCUPANCY: R-3CONSTRUCTION TYPE: VBUNSPRINKLEREDALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH THECODE AND THE MANUFACTURES INSTALLATION INSTRUCTIONS.ALL PLACARDS REQUIRED BY NEC 2017 CODE MACHINEPRINTED LETTERS IN A CONTRASTING COLOR TO THE PLACARD.LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE SUNLIGHTRESISTANT. ELECTRICAL INSTALLATION WILL COMPLY WITH NEC2017 CODE. ALL SOLAR MODULES EQUIPMENT AND METALLICCOMPONENTS ARE TO BE BONDED. ALL PLUMBING ANDMECHANICAL ROOF VENTS TO CLEAR FROM PHOTOVOLTAICARRAY, OR EXTEND ABOVE SOLAR PANELS. SOLARPHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIALSTRUCTURE. DESIGN COMPLYING WITH THE IBC 2015 CODEAND ALL LOCAL ORDINANCES AND POLICIES. THE PROJECT HASBEEN DESIGNED TO WITHSTAND A MINIMUM 110 MPH WINDLOAD. THE SYSTEM WILL NOT BE INTERCONNECTED UNTILAPPROVAL FROM THE LOCAL JURISDICTION AND A UTILITY ISOBTAINED. IF THE MAIN SERVICE PANEL DOES NOT HAVEVERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTORSRESPONSIBILITY TO INSTALL SUPPLEMENTAL GROUNDINGELECTRODE. EACH MODULE WILL BE GROUNDED USING THESUPPLIED CONNECTION POINTS IDENTIFIED ON THE MODULEAND THE MANUFACTURERS INSTALLATION INSTRUCTIONS. ALADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCEWITH OSHA REGULATIONS. PROPER ACCESS AND WORKINGCLEARANCE WILL BE PROVIDED "WARNING: PV POWERSOURCE" TO BE PLACED EVERY 10 FT.RAPID SHUTDOWN NOT REQUIRED. DC IS LESS THAN 5' INSIDEBUILDING.GFCI PROTECTION IN INVERTER. A L L W O R K T O C O M P L Y W I T H T H E F O L L O W I N G C O D E : N E C 2 0 1 7 C O D E I B C 2 0 1 5 C O D E Big Dog Renewable EnergyContractor Lic # 17916620 Pheasant Ridge DrChubbuck, ID 83202208-242-3352 T208-232-5935 F X____________________ 3/27/2018 TIM STOWELL 772 NINA DR REXBURG, ID 83440 208-201-5591 www.bigdogenergy.com N M T R M S P A C I N V CONTRACTOR INFORMATIONDESIGNED BYSOLAR PHOTOVOLTAIC SYSTEMDATEISSUED FOR: PERMIT SITE PLAN, AERIAL VIEW www.bigdogenergy.com P V - 1 A SITE PLAN A E R I A L V I E W S C A L E : N T S S C A L E : 1 " = 3 0 ' - 0 " TOTAL # OF PANELS36 A B B R E V I A T I O N S I N V M S P A C I N V E R T E R M A I N S E R V I C E P A N E L A C D I S C O N N E C T M T R M E T E R Big Dog Renewable EnergyContractor Lic # 017916620 Pheasant Ridge DrChubbuck, ID 83202208-242-3352 T208-232-5935 F X____________________ 2018-3-27 TIM STOWELL 772 NINA DR REXBURG, ID 83440 208-201-5591 L - F O O T 10'-11" 1 9 ' - 1 1 " 3 ' - 4 " 4 ' R A I L G E C ROOF PEAK T Y P I C A L P A N E L A S S E M B L Y 5'-6" CONTRACTOR INFORMATIONDESIGNED BYSOLAR PHOTOVOLTAIC SYSTEMDATEISSUED FOR: PERMIT ARRAY LAYOUT P V - 2 ARRAY LAYOUT S C A L E : 3 / 1 6 " = 1 ' - 0 " RACKING SUPPORTS NOT TO EXCEED 4'SPACING STAGGERED ON TRUSSES www.bigdogenergy.com Big Dog Renewable EnergyContractor Lic # 017916620 Pheasant Ridge DrChubbuck, ID 83202208-242-3352 T208-232-5935 F X____________________ 3/27/2018 TIM STOWELL 772 NINA DR REXBURG, ID 83440 208-201-5591 1 8 M O D U L E S I N S E R I E S MPP T 1 MPP T 3 _~B3 1 S T R I N G 1 T I L T : 2 8 ° A Z I M U T H : 1 7 8 ° M O D U L E : R E C R 2 9 0 C Z C 2 9 0 W V o c = 3 8 . 8 V I s c = 9 . 5 8 A V m p = 3 2 . 1 V I m p = 9 . 0 5 A 1 0 k W I N V E R T E R U N G R O U N D E D S O L A R E D G E S E 1 0 A U S ( 2 0 8 V ) I N V E R T E R 2 4 0 V A C , 4 2 A , N E M A 3 R , U L L I S T E D , ( W / I N T E G R A T E D D C D I S C O N N E C T ) W I T H I N T E G R A T E D G F P , W / I N T E G R A T E D A F P A L L M O D U L E S W I L L B E G R O U N D E D I N A C C O R D A N C E W I T H C O D E A N D T H E M A N U F A C T U R E R ' S I N S T A L L A T I O N I N S T R U C T I O N S . T E R M I N A L S O F T H E D I S C O N N E C T I N G M E A N S M A Y B E E N E R G I Z E D I N T H E O P E N P O S I T I O N . C E C A R T I C L E 6 9 0 . 1 7 WIRE AND CONDUIT CALLOUTS(2) #10 AWG PV/RHW-2(1) #6 AWG BARE COPPER GND IN 34" EMT(3) #6 AWG THWN-2(1) #10 AWG THWN-2 GND IN 3/4" EMT ELECTRICA L E Q U I P M E N T C A L L O U T S 10kW INVE R T E R U N G R O U N D E D SOLARED G E S E 1 0 A U S I N V E R T E R 240VAC, 4 2 A , N E M A 3 R , U L L I S T E D , (W/ INTEG R A T E D D C D I S C O N N E C T ) WITH INTE G R A T E D G F P , W / I N T E G R A T E D A F P AC DISCO N N E C T 240VAC, 6 0 A F U S E D N E M A 3 R , U L L I S T E D W / 6 0 A FUSES200A MAIN S E R V I C E P A N E L , (W/ BIDIRE C T I O N A L U T I L I T Y M E T E R ) P300 SOLA R E D G E O P T I M I Z E R NNGGROUNDING CLAMP<- 6' MIN. ->NEW 58" Ø 8'LGROUNDINGELECTRODE 13 D 10,440W TOTAL SOLAR ARRAY36 REC 290W MODULESARRAY 12 STRINGS OF 18 MODULES @ INVERTER SOLAREDGE10KWEEL1L2MPP T 2 B200A 1 8 M O D U L E S I N S E R I E S 1 S T R I N G 2 T I L T : 2 8 ° A Z I M U T H : 1 7 8 ° H O N E P E R P A N E L H O N E P E R P A N E L HDNGNNGL1L2L1L23TAP ELECTRICAL SINGLE LINE DIAGRAM CONTRACTOR INFORMATIONDESIGNED BYSOLAR PHOTOVOLTAIC SYSTEMDATEISSUED FOR: PERMIT SINGLE LINE DIAGRAM P V - 3 S C A L E : N T S E L E C T R I C A L N O T E S 1 . P V A R R A Y S A R E P E R S I N G L E L I N E . 2 . P V A R R A Y W I R I N G T O J U N C T I O N I S # 1 0 A W G U S E 2 W / F I E L D I N S T A L L E D M C C O N N E C T O R S T O I N T E R F A C E W / M O D U L E S . 3 . P V A R R A Y C O M B I N E R / J U N C T I O N B O X P R O V I D E S T R A N S I T I O N F R O M A R R A Y W I R I N G T O C O N D U I T W I R I N G . 4 . U S E U F E R G R O U N D E L E C T R O D E S Y S T E M F R O M I N V E R T E R T O E X I S T I N G M A I N S E R V I C E G R O U N D E L E C T R O D E P E R N . E . C . 2 5 0 . 5 8 . 5 . G R O U N D E L E C T R O D E C O N D U C T O R F R O M I N V E R T E R T O G R O U N D E L E C T R O D E T O B E M I N I M U M P R O T E C T I O N O F B A R E A R M O R S H E A T H E D C A B L E F O R A L L C O N D U C T O R S I Z E S . 6 . A L L G R O U N D C O N N E C T E D T O M A I N S E R V I C E G R O U N D I N M A I N S E R V I C E P A N E L . 7 . C O N N E C T O R S S H A L L B E P O L A R I S O R E U R O S T R I P I T C O N N E C T O R S . 8 . I N V E R T E R S H A L L B E P E R S I N G L E L I N E , S E E A T T A C H E D C U T S H E E T . 9 . I N V E R T E R I S P E R S I N G L E L I N E . 1 0 . A C D I S C O N N E C T S H A L L B E P E R S I N G L E L I N E . 1 1 . E Q U I P M E N T G R O U N D I N G C O N D U C T O R S O N A C A N D D C S I D E S I Z E D A C C O R D I N G T O N . E . C . 6 9 0 . 1 2 . P O L E O F P V A R R A Y R E F E R E N C E D T O G R O U N D A T T H E I N V E R T E R I N S I N G L E L I N E . 1 3 . A L L C O N D U C T O R S S H A L L B E 6 0 0 V , 9 0 C S T A N D A R D C O P P E R . A L L C O N D U C T O R S I N C O N D U I T S H A L L B E T H W N - 2 . 1 4 . M A X I M U M D C V O L T A G E D R O P S H A L L B E 2 . 5 % 1 5 . A L L C O N D U C T O R S S H A L L B E I N C O N D U I T U N L E S S O T H E R W I S E N O T E D . 1 6 . A L L W O R K T O C O M P L Y W I T H N E C 2 0 1 4 C O D E . 1 7 . D C A R R A Y C O N D U C T O R S A R E T O R E M A I N O U T S I D E O F B U I L D I N G P R I O R T O F U S I B L E C O M B I N E R B O X O R F U S I B L E D C D I S C O N N E C T M E A N S . 1 8 . E X A C T C O N D U I T R U N L O C A T I O N S S U B J E C T T O C H A N G E . 1 9 . 3 . 0 P S F M A X ( . 5 P S F F R O M R A C K I N G , 2 . 5 P S F F R O M M O D U L E S ) D E A D L O A D C O N T R I B U T E D F R O M S O L A R A R R A Y . 2 0 . A R C F A U L T I N S T A L L E D A T I N V E R T E R O R I N C O M B I N E R B O X . 2 1 . D C G R O U N D F A U L T P R O T E C T I O N I N T E G R A T E D I N I N V E R T E R . R A C K I N G & M O D U L E S A R E G R O U N D E D V I A A C O N T I N U O U S # 6 A W G C O P P E R C O N D U C T O R C O N N E C T E D W / W E E B S - M O D U L E S A R E F A C T O R Y P R O V I D E D W / 2 T H R E A D E D H O L E S T O F A C I L I T A T E L A N D I N G O F T H E L U G S A L L E Q U I P M E N T S H A L L B E P R O P E R L Y G R O U N D E D A N D B O N D E D I N A C C O R D A N C E W I T H A R T I C L E 2 5 0 . A L L C I R C U I T S C O N N E C T E D T O M O R E T H A N O N E S O U R C E S H A L L H A V E O V E R C U R R E N T D E V I C E S L O C A T E D S O A S T O P R O V I D E O V E R C U R R E N T P R O T E C T I O N F R O M A L L S O U R C E S 6 9 0 . 9 ( A ) www.bigdogenergy.com Big Dog Renewable Energy Contractor Lic # 017916 620 Pheasant Ridge Dr Chubbuck, ID 83202 208-242-3352 T 208-232-5935 F X____________________ 3/27/2018 TIM STOWELL 772 NINA DR REXBURG, ID 83440 208-201-5591 CONTRACTOR INFORMATIONDESIGNED BYSOLAR PHOTOVOLTAIC SYSTEMDATEISSUED FOR: PERMIT ELECTRICAL CALCULATIONS, MATERIAL LIST P V - 4 ELECTRICAL CALCULATIONS M A T E R I A L L I S T R E C 2 9 0 T P M O D U L E 3 6 S N A P N R A C K , S T A N D A R D R A I L S E T , 1 2 2 I N , B L A C K , 6 P C 5 S N A P N R A C K , S T A N D A R D R A I L S E T , 1 2 2 I N , B L A C K , 2 P C 2 S N A P N R A C K , S T A N D A R D R A I L S P L I C E A S S E M B L Y , B L A C K 1 4 S N A P N R A C K , M I D C L A M P A S S E M B L Y , 1 . 3 1 - 1 . 7 7 I N , B L A C K 8 4 S N A P N R A C K , U N I V E R S A L E N D C L A M P A S S E M B L Y , R E V 2 2 4 S N A P N R A C K , S T A N D A R D R A I L E N D C A P , B L A C K 2 4 S N A P N R A C K , L - F O O T K I T W / F L A S H I N G , B L A C K 7 8 W I L E Y W E E B , P M C , G R O U N D I N G L U G / C O N N E C T O R , W A S H E R F O R S N A P N R A C K R A I L S 3 2 W I L E Y W E E B , 6 . 7 A S , G R O U N D I N G L U G / C O N N E C T O R , A S S E M B L E D B O N D I N G J U M P E R 8 G R O U N D I N G , W I L E Y W E E B , L - 6 . 7 A S , A S S E M B L E D W E E B L U G W / W A S H E R 8 H E L L E R M A N T Y T O N , 1 8 8 - 0 9 1 0 1 , P R E P R I N T E D L A B E L K I T , R E S I D E N T I A L , 7 K W T O 1 5 K W 1 C A B L E T I E , F I T S . 2 " T O . 3 " D I A C A B L E S , S S T , 2 5 P A C K 2 P V O U T P U T , M U L T I - C O N T A C T M C 4 , M A L E / F E M A L E , 1 0 / 1 , 5 0 F T , 6 0 0 V , P V W I R E 2 S T R A I N R E L I E F , 1 / 2 I N , N Y L O N , 0 . 2 5 - 0 . 2 7 I N C A B L E D I A , T W O H O L E , M A L E P I P E T H R E A D , 6 M M 2 S O L A R E D G E 9 3 0 0 - 5 S E R I E S - N X X D C O P T I M I Z E D 3 0 0 W 3 6 TOTAL A R R A Y AC CON D U C T O R A M P A C I T Y C A L C U L A T I O N S ( F R O M A R R A Y T O M S P ) : # OF INV E R T E R S : 1 CIRCUIT C O N D U C T O R S I Z E : # 6 A W G # OF CU R R E N T C A R R Y I N G C O N D U C T O R S : 3 CONDUI T F I L L C O R R E C T I O N P E R N E C 3 1 0 . 1 5 ( B ) ( 2 ) ( a ) : 1 CIRCUIT C O N D U C T O R A M P A C I T Y : 6 5 A REQUIRE D C I R C U I T C O N D U C T O R A M P A C I T Y P E R N E C 6 9 0 . 8 ( B ) : 1.25 X M A X I N V E R T E R O U T P U T C U R R E N T X # O F I N V E R T E R S 1.25* 4 2 * 1 = 5 2 . 5 A MAIN DI S C O N N E C T : 2 0 0 A NEW SO L A R S Y S T E M : 6 0 A LINE SID E T A P S O L A R E D G E S E 1 0 0 0 0 A - U S 1 0 K W I N V E R T E R 1 www.bigdogenergy.com Big Dog Renewable Energy Contractor Lic # 017916 620 Pheasant Ridge Dr Chubbuck, ID 83202 208-242-3352 T 208-232-5935 F X____________________ 3/27/2018 TIM STOWELL 772 NINA DR REXBURG, ID 83440 208-201-5591 ARRAY 1OPERATING VOLTAGE =17*38.8=350V OPTIMIZERTOTALOPERATING CURRENT =2*9.05=18.1ADC CONDUCTOR AMPACITY CALCULATIONS:MAX # OF STRINGS PER SET OF DC CONDUCTORS:1EXPECTED WIRE TEMP (°C):+17oC Correction, 3.5"53TEMP CORRECTION PER TABLE 310.16:0.84# OF CURRENT CARRYING CONDUCTORS:4CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a):1CIRCUIT CONDUCTOR SIZE:#10AWGCIRCUIT CONDUCTOR AMPACITY:30AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B):1.25 X 1.25 X Isc X # OF STRINGS1.25*1.25*9.58*1=14.96ADERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16:TEMP CORR. PER NEC TABLE 310.16 X CONDUIT FILL CORR. PERNEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY =0.84*.70*30=17.64A>14.6AAC CONDUCTOR AMPACITY CALCULATIONS:# OF INVERTERS:1EXPECTED WIRE TEMP (°C):26TEMP CORRECTION PER TABLE 310.16:1CIRCUIT CONDUCTOR SIZE:#6AWG# OF CURRENT CARRYING CONDUCTORS:3CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a):1CIRCUIT CONDUCTOR AMPACITY:65AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B):1.25 X MAX INVERTER OUTPUT CURRENT X # OF INVERTERS1.25*42*1=52.5ADERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16:TEMP CORR. PER NEC TABLE 310.16 X CONDUIT FILL CORR. PERNEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY =1*1*65=65A>52.5A60AOCPD CONTRACTOR INFORMATIONDESIGNED BYSOLAR PHOTOVOLTAIC SYSTEMDATEISSUED FOR: PERMIT REQUIRED SIGNAGE P V - 4 A REQUIRED SIGNAGE1. PROVIDE A PLACARD WITH THE FOLLOWING WORKING IN 14"HIGH LETTERING PER NEC 690-17.2. LABEL FOR SOLAR DC DISCONNECT:3. LABEL YELLOW W/BLACK LETTERING FOR PV AC DISCONNECT:4. LABEL FOR INVERTER:5. AT THE MAIN SERVICE DISCONNECT PROVIDE A SIGN WITH THEFOLLOWING WORKING:THE SIGN SHOULD BE PLACED ON THE OUTSIDE COVER IF THEMAIN SERVICE DISCONNECT IS OPERABLE WITH THE SERVICEPANEL CLOSED.6. PHOTOVOLTAIC DC CONDUCTORS ENTERING THE BUILDINGSHALL BE INSTALLED IN A METALLIC RACEWAY AND SHALL BEIDENTIFIED EVERY FIVE FEET FOR THE ENTIRE LENGTH ASFOLLOWS:7. AT AL L S O U R C E S O F P O W E R ( U T I L I T Y , S O L A R , E T C . ) 8. AT RA P I D S H U T D O W N : WARNING:ELECTRICAL SHOCK HAZARD.DO NOT TOUCH TERMINALS. TERMINALS ONBOTH THE LINE AND LOAD SIDES MAY BEENERGIZED IN THE OPEN POSITION."SOLAR DC DISCONNECT""SOLAR AC DISCONNECT"CAUTION:PANEL FED BY MULTIPLE POWER SOURCESCAUTION:PV POWER SOURCE U T I L I T Y : 2 4 0 V 2 0 0 A S O L A R : 2 4 0 V 6 0 A SOLA R P V S Y S T E M E Q U I P P E D WI T H R A P I D S H U T D O W N 9. AT SE R V I C E D I S C O N N E C T I F R E Q U I R E D 10. AT MA I N B I L L I N G M E T E R Y E L L O W W / B L A C K L E T T E R I N G : RAPID S H U T D O W N D I S C O N N E C T PH O T O V O L T A I C S Y S T E M C O N N E C T E D "GRID-TIED PHOTOVOLTAIC POWER SOURCE"OPERATING CURRENT: 35 ADCOPERATING VOLTAGE: 350 VDC www.bigdogenergy.com Big Dog Renewable EnergyContractor Lic # 017916620 Pheasant Ridge DrChubbuck, ID 83202208-242-3352 T208-232-5935 F X____________________ 3/27/2018 TIM STOWELL 772 NINA DR REXBURG, ID 83440 208-201-5591 PIDFree 100%PIDFree 100%PIDFree 100% MORE POWER OUTPUT PER M² IMPROVED PERFORMANCE IN SHADED CONDITIONS 100% PID FREE REDUCES BALANCE OF SYSTEM COSTS REC TwinPeak 2 Series solar panels feature an innovative design with high panel efficiency and power output, enabling customers to get the most out of the space used for the installation. Combined with industry-leading product quality and the reliability of a strong and established European brand, REC TwinPeak 2 panels are ideal for residential and commercial rooftops worldwide. PREMIUM SOLAR PANELSWITH SUPERIOR PERFORMANCE rec TwinPeak 2 Series www.recgroup.com GR GR GR GR 28 [1.1] 1675±2.5 [65.94 ±0.1] 910 [35.8]382.5 [5.05] 95 6 [ 3 7 . 6 4 ] 99 7 ± 2 . 5 [ 3 9 . 2 5 ± 0 . 1 ] 17 [ 0 . 7 ] 45 [1.5] 900 [35] 1200 [47] Scale: 1:1.57 11±0.2[0.43 ±0.8] 6.6 ± 0 . 2 [ 0 . 2 6 ± 0 . 0 8 ] 20.5±0.5[0.78 ±0.08] 38 [1.5] Re f : N E - 0 5 - 0 7 - 0 7 R e v - D 0 2 . 1 7 take-e-way WEEE Compliant Recycling scheme REC TWINPEAK 2 SERIES GENERAL DATA TEMPERATURE RATINGS Note! Specifications subject to change without notice. ELECTRICAL DATA @ STC Product Code*: RECxxxTP2 Nominal Power - PMPP (Wp) 275 280 285 290 295 Watt Class Sorting - (W)0/+5 0/+5 0/+5 0/+5 0/+5 Nominal Power Voltage - VMPP (V) 31.5 31.7 31.9 32.1 32.3 Nominal Power Current - IMPP (A) 8.74 8.84 8.95 9.05 9.14 Open Circuit Voltage - VOC (V) 38.2 38.4 38.6 38.8 39.0 Short Circuit Current - ISC (A) 9.30 9.39 9.49 9.58 9.65 Panel Efficiency (%) 16.5 16.8 17.1 17.4 17.7 MAXIMUM RATINGS CERTIFICATIONS MECHANICAL DATAWARRANTY Dimensions: 1675 x 997 x 38 mm Area: 1.67 m² Weight: 18.5 kg Nominal operating cell temperature (NOCT) 44.6°C (±2°C) Temperature coefficient of PMPP -0.39 %/°C Temperature coefficient of VOC -0.31 %/°C Temperature coefficient of ISC 0.045 %/°C Values at standard test conditions STC (airmass AM 1.5, irradiance 1000 W/m², cell temperature 25°C). At low irradiance of 200 W/m² (AM 1.5 and cell temperature 25°C) at least 94% of the STC module efficiency will be achieved.*Where xxx indicates the nominal power class (PMPP) at STC indicated above, and can be followed by the suffix BLK for black framed modules. Nominal operating cell temperature NOCT (800 W/m², AM 1.5, windspeed 1 m/s, ambient temperature 20°C).*Where xxx indicates the nominal power class (PMPP) at STC indicated above, and can be followed by the suffix BLK for black framed modules. 17.7% 10 25 EFFICIENCY YEAR PRODUCT WARRANTY YEAR LINEAR POWER OUTPUT WARRANTY IEC 61215, IEC 61730 & UL 1703. IEC 62804 (PID Free),IEC 61701 (Salt Mist Level 6),IEC 62716 (Ammonia Resistance),ISO 11925-2 (Ignitability Class E), UNI 8457/9174 (Class 1),ISO 9001:2015, ISO 14001, OHSAS 18001 Operational temperature: -40 ... +85°C Maximum system voltage: 1000 V Maximum snow load: 550 kg/m² (5400 Pa) Maximum wind load: 244 kg/m² (2400 Pa) Max series fuse rating: 25 A Max reverse current: 25 A Cell type: 120 REC HC multicrystalline 6 strings of 20 cells Glass: 3.2 mm solar glass with anti-reflective surface treatment Back sheet: Highly resistant polyester polyolefin construction Frame: Anodized aluminum (available in silver or black) Junction box: IP67 rated, 3-part with 3 bypass diodes 4 mm² solar cable, 0.9 m + 1.2 m Connectors*: Stäubli MC4 PV-KBT4/PV-KST4 (4 mm²) Tonglin TL-Cable01SFR (4 mm²) *Dependent on product type ELECTRICAL DATA @ NOCT*Product Code*: RECxxxTP2 Nominal Power - PMPP (Wp) 206 210 214 218 223 Nominal Power Voltage - VMPP (V) 29.2 29.4 29.6 29.8 30.0 Nominal Power Current - IMPP (A) 7.07 7.15 7.24 7.32 7.43 Open Circuit Voltage - VOC (V) 35.4 35.6 35.8 36.0 36.2 Short Circuit Current - ISC (A) 7.52 7.59 7.68 7.75 7.85 Measurements in mm [in] 10 year product warranty 25 year linear power output warranty (max. degression in performance of 0.7% p.a. from 97% after the first year) See warranty conditions for further details. Founded in Norway in 1996, REC is a leading vertically integrated solar energy company. Through integrated manufacturing from silicon to wafers, cells, high-quality panels and extending to solar solutions, REC provides the world with a reliable source of clean energy. REC’s renowned product quality is supported by the lowest warranty claims rate in the industry. REC is a Bluestar Elkem company with headquarters in Norway and operational headquarters in Singapore. REC employs more than 2,000 people worldwide, producing 1.4 GW of solar panels annually. IN V E R T E R S www.solaredge.us SolarEdge Single Phase Inverters For North America SE3000A-US / SE3800A-US / SE5000A-US / SE6000A-US / SE7600A-US / SE10000A-US / SE11400A-US USA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - AUSTRALIA - THE NETHERLANDS - UK - ISRAEL 12-25 The best choice for SolarEdge enabled systems Integrated arc fault protection for NEC 2011 690.11 compliance Rapid shutdown for NEC 2014 690.12 Superior efficiency (98%) Small, lightweight and easy to install on provided bracket Built-in module-level monitoring Internet connection through Ethernet or Wireless Outdoor and indoor installation Fixed voltage inverter, DC/AC conversion only Pre-assembled Safety Switch for faster installation Optional – revenue grade data, ANSI C12.1 © SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners. Date: 01/2016. V.02. Subject to change without notice. Single Phase Inverters for North America SE3000A-US / SE3800A-US / SE5000A-US / SE6000A-US / SE7600A-US / SE10000A-US / SE11400A-US SE3000A-US SE3800A-US SE5000A-US SE6000A-US SE7600A-US SE10000A- US SE11400A-US OUTPUT Nominal AC Power Output 3000 3800 5000 6000 7600 9980 @ 208V 10000 @240V 11400 VA Max. AC Power Output 3300 4150 5400 @ 208V 5450 @240V 6000 8350 10800 @ 208V 10950 @240V 12000 VA AC Output Voltage Min.-Nom.-Max.(1) 183 - 208 - 229 Vac --3 --3 - AC Output Voltage Min.-Nom.-Max.(1) 211 - 240 - 264 Vac 3 3 3 3 3 3 3 AC Frequency Min.-Nom.-Max.(1) 59.3 - 60 - 60.5 Hz Max. Continuous Output Current 12.5 16 24 @ 208V 21 @ 240V 25 32 48 @ 208V 42 @ 240V 47.5 A GFDI Threshold 1 A Utility Monitoring, Islanding Protection, Country Configurable Thresholds Yes Yes INPUT Maximum DC Power (STC)4050 5100 6750 8100 10250 13500 15350 W Transformer-less, Ungrounded Yes Max. Input Voltage 500 Vdc Nom. DC Input Voltage 325 @ 208V / 350 @ 240V Vdc Max. Input Current(2) 9.5 13 16.5 @ 208V 15.5 @ 240V 18 23 33 @ 208V 30.5 @ 240V 34.5 Adc Max. Input Short Circuit Current 45 Adc Reverse-Polarity Protection Yes Ground-Fault Isolation Detection 600k Sensitivity Maximum Inverter Efficiency 97.7 98.2 98.3 98.3 98 98 98 % CEC Weighted Efficiency 97.5 98 97 @ 208V 98 @ 240V 97.5 97.5 97 @ 208V 97.5 @ 240V 97.5 % Nighttime Power Consumption < 2.5 < 4 W ADDITIONAL FEATURES Supported Communication Interfaces RS485, RS232, Ethernet, ZigBee (optional) Revenue Grade Data, ANSI C12.1 Optional(3) Rapid Shutdown – NEC 2014 690.12 Yes STANDARD COMPLIANCE Safety UL1741, UL1699B, UL1998 , CSA 22.2 Grid Connection Standards IEEE1547 Emissions FCC part15 class B INSTALLATION SPECIFICATIONS AC output conduit size / AWG range 3/4” minimum / 16-6 AWG 3/4” minimum / 8-3 AWG DC input conduit size / # of strings / AWG range 3/4” minimum / 1-2 strings / 16-6 AWG 3/4” minimum / 1-3 strings / 14-6 AWGDimensions with Safety Switch (HxWxD) 30.5 x 12.5 x 7.2 / 775 x 315 x 184 30.5 x 12.5 x 10.5 / 775 x 315 x 260 in / mm Weight with Safety Switch 51.2 / 23.2 54.7 / 24.7 88 .4 / 40.1 lb / kg Cooling Natural Convection Natural convection and internal fan (user replaceable) Fans (user replaceable) Noise < 25 < 50 dBA Min.-Max. Operating Temperature Range -13 to +140 / -25 to +60 (-40 to +60 version available(4)) ˚F / ˚C Protection Rating NEMA 3R (1) For other regional settings please contact SolarEdge support. (2) A higher current source may be used; the inverter will limit its input current to the values stated.(3) Revenue grade inverter P/N: SExxxxA-US000NNR2 (for 7600W inverter:SE7600A-US002NNR2).(4) -40 version P/N: SExxxxA-US000NNU4 (for 7600W inverter:SE7600A-US002NNU4). SolarEdge Power Optimizer Frame-Mounted Module Add-On P300 / P350 / P404 / P500 Fast mount power optimizers with module-level optimization Quicker installation - Power optimizers can be mounted in advance saving installation time Up to 25% more energy Superior efficiency (99.5%) Mitigates all types of modules mismatch-loss, from manufacturing tolerance to partial shading Flexible system design for maximum space utilization Next generation maintenance with module level monitoring Module-level voltage shutdown for installer and firefighter safety PO W E R O P T I M I Z E R www.solaredge.comUSA - CANADA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - AUSTRALIA - THE NETHERLANDS - UK - ISRAEL - TURKEY - SOUTH AFRICA © SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGEare trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners. Date: 02/2016. V.01. Subject to change without notice. P300 (for 60-cell modules) P350 (for high-power 60-cell and for 72-cell modules) P500 (for 96-cell modules) P404 (for 60-cell and 72-cell, short strings) INPUT Rated Input DC Power(1)300 350 500 405 W Absolute Maximum Input Voltage (Voc at lowest temperature)48 60 80 80 Vdc MPPT Operating Range 8 - 48 8 - 60 8 - 80 12.5 - 80 Vdc Maximum Continuous Input Current (Isc)10 11 10.1 Adc Maximum Efficiency 99.5 % Weighted Efficiency 98.8 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc Maximum Output Voltage 60 85 Vdc OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power Optimizer 1 Vdc STANDARD COMPLIANCE EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3 Safety IEC62109-1 (class II safety), UL1741 RoHS Yes Fire Safety VDE-AR-E 2100-712:2013-05 INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Dimensions (W x L x H) 139 x 165 x 41 / 5.47 x 6.5 x 1.61 139 x 165 x 49 / 5.47 x 6.5 x 1.93 139 x 165 x 56 / 5.47 x 6.5 x 2.2 mm / in Weight (including cables) 880 / 1.94 950 / 2.1 1065 / 2.34 gr / lb Input Connector MC4(2) Output Connector MC4 Output Wire Length 0.95 / 3.0 1.2 / 3.9 m / ft Operating Temperature Range -40 - +85 / -40 - +185 ˚C / ˚F Protection Rating IP68 / NEMA6P Relative Humidity 0 - 100 % SolarEdge Power Optimizer Frame-mounted Module Add-On P300 / P350 / P404 / P500 (1) Rated STC power of the module. Module of up to +5% power tolerance allowed.(2) For other connector types please contact SolarEdge.Supported frame cross-section PV SYSTEM DESIGN USING A SOLAREDGE INVERTER SINGLE PHASE THREE PHASE Minimum String Length (Power Optimizers)8 16 Maximum String Length (Power Optimizers)25 50 Maximum Power per String 5250 11250 W Parallel Strings of Different Lengths or Orientations Yes 1.1-2.2mm / 0.04-0.09in > 12mm / 0.48in 3-1© 2007 Schneider Electric All Rights Reserved 3 SA F E T Y S W I T C H E S Table of Contents Section 3 Safety Switches General Duty, p. 3-2 Light Duty, p. 3-2 Heavy Duty, p. 3-4 Double Throw, p. 3-14 General Duty Fusible & Non-Fusible 3-2 Application Data and Dimensions 3-3 Standards: •UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875. •NEMA Standards Publication KS1. Enclosed Switches. Light Duty Fusible 3-2 Application Data and Dimensions 3-3 Standards: •UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875. •NEMA Standards Publication KS1. Enclosed Switches. Heavy Duty Fusible 3-4 Non-Fusible 3-6 Special Application Enclosures 3-7 Accessories 3-9 Application Data and Dimensions 3-12 Standards: •UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875 and E154828. •NEMA Standards Publication KS1. Enclosed Switches. Double Throw Fusible and Non-Fusible 3-14 Application Data 3-17 Dimensions 3-18 Accessories 3-20 Standards: •UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875 (unless otherwise noted). •NEMA Standards Publication KS1 Enclosed Switches (applies to Type DT and DTU series F only). New! 3-2 © 2007 Schneider Electric All Rights Reserved www.schneider-electric.us 3 S A F E T Y S W I T C H E S General Duty Safety Switches Light Duty Class 3130 General Duty—Up To 100 kA Short Circuit Current Rating With Proper Current Limiting Fusing General duty safety switches are designed for residential and commercial applications where economy is a prime consideration. Typical loads are lighting, air conditioning, and appliances. They are suitable for use as service equipment when equipped with a factory-installed neutral assembly or a field-installed service grounding kit. General duty safety switches are UL Listed, File E2875, and meet or exceed the NEMA Standard KS1. 400 and 600 A general duty switches (NEMA 1 only) will accept Class J fuses and are UL Listed for use on systems with up to 100 kA available fault current. 600 A requires Class J fuse kit—GDJK600 (page 3-3). 400 A requires moving load base. Class T 400–800 A general duty safety switches use 300 Vac Class T fuses and are UL Listed for use on systems with up to 100 kA available fault current. a Bolt-on hubs—Refer to page 3-9. b When installed, this kit rejects all but Class R fuses. When installed with this kit and Class R fuses, the switch is UL Listed for use on systems with up to 100 kA available fault current. c For corner grounded delta systems only. Use switching poles for ungrounded conductors. d If corner grounded delta, use outer switching poles for ungrounded conductors. e For 200% neutral, order (1) additional neutral kit SN20A at $133. and (1) neutral jumper kit SN20NI at $18.40. f Bolt-on hubs—Refer to page 3-9. g Enclosed molded case switch—Refer to 1-22. h Includes factory-installed grounding kit. i Not service entrance rated—Refer to page 1-19 for more information. j Includes factory-installed neutral.For service equipment use or when neutral is required, order part number SN0610 at $71.00. k Suitable for use as service equipment, requires field installation of neutral assembly SN20A at $133.00. l If corner grounded delta, install neutral and use outer switching poles for ungrounded conductors. Light Duty—Visible Blades 10 kA Short Circuit Current Rating The Square D light duty enclosed switch is ideal for home applications in disconnecting power to workshops, hobby rooms, furnaces and garages. m For single phase hp rating, use two switching poles. n DE1A Discount Schedule. UL Listed Short Circuit Withstand Rating Switch Type Fuse Class Short Circuit Rating Fusible Plug 10 kA H10 kA K10 kA J100 kA R100 kA T100 kA Non-Fusiblea H10 kA K10 kA J100 kA R100 kAb T100 kA a The UL Listed short-circuit current rating for Square D general duty, not fusible switches is based on the switch being used in conjunction with fuses. Evaluation of non-fusible switches in conjunction with molded case circuit breakers has not been performed. If a UL Listed short-circuit current rating is required, this non-fusible switch must be replaced with a Square D general duty fusible safety switch equipped with the appropriate class and size fusing. The UL Listed short-circuit current rating of the fusible switch is typically as follows: when used with Class H & K fuses—10,000 A, Class R and J fuses—100,000 A. Consult the wiring diagram of the switch to verify the UL Listed short-circuit current rating. b 50 kA for 60 A non-fusible switch. Table 3.1: Fusible System A Fuse NEMA 1 Indoor NEMA 3Ra Rainproof Class R Fuse Kits Field-Installableb Horsepower Ratings Std. (Fast Acting One-Time Fuses) Max. (Dual Element Time-Delay Fuses)Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 1Ø 3Ø 1Ø 3Ø 2 Wire (1 Blade and Fuseholder, 1 Neutral)—120 Vac 30 Plug Use Light Duty Device for This Application (see below) — — — — 30 Cart. Use 3 Wire Devices for this application. — — — — 3 Wire (2 Blades and Fuseholders, 1 Neutral)—120/240 Vac (Plug), 240 Vac (Cart.) Maximum 30 Plug D211N 60.00 D211NRB 118.00 — — 1-1/2 — 3 — 30 Cart.D221N 81.00 D221NRB 125.00 DRK30 17.10 1-1/2 3c 37-1/2c 60 Cart.D222N 137.00 D222NRB 217.00 RFK03H 17.00 37-1/2c 10 15c 100 Cart.D223N 284.00 D223NRB 320.00 RFK10 31.80 7-1/2 15c 15 30c 200 Cart.D224Ne 589.00 D224NRBe 800.00 HRK1020 31.80 15 25c —60c 400 Cart.D225N 1703.00 D225NR 2306.00 DRK40 74.00 ———— 600 Cart.D226N 3406.00 D226NR 4379.00 DRK600 74.00 ———— 4 Wire (3 Blades and Fuseholders, 1 Neutral)—240 Vac Maximum 30 Cart.D321N 125.00 D321NRB 195.00 DRK30 17.10 1-1/2 3 3 7-1/2 60 Cart.D322N 217.00 D322NRB 294.00 RFK03H 17.00 37-1/2d10 15d 100 Cart.D323N 376.00 D323NRB 544.00 RFK10 31.80 7-1/2 15d 15 30d 200 Cart.D324Ne 801.00 D324NRBe 974.00 HRK1020 31.80 15 25d —60d 400 Cart.D325N 2075.00 D325NR 2595.00 DRK40 74.00 —50 — 125 400 Class T D325NT 1996.00 D325NTR 2494.00 —— — 50 — — 600 Cart.D326N 3882.00 D326NR 5251.00 DRK600 74.00 —75 — 150 600 Class T D326NT 3732.00 D326NTR 5046.00 —— — 75 — — 800 Class T T327N 6481.00 T327NR 8292.00 — — —100 —— Table 3.2: Non-Fusible System A NEMA 1 Indoor NEMA 3R Rainproof f Horsepower Ratings (Max.) Cat. No.$ Price Cat. No.$ Price 1Ø 3Ø 2 Wire (2 Blades)—240 Vac Maximum 30 ——DU221RBk 118.00 3— 60 ——DU222RBk 235.00 10 — 60 QO260NATSgh 107.00 QO200TRghi 107.00 10 — 100 QO2000NSgh 184.00 QO2000NRBgi 225.00 20 — 200 Use 3P Switch —Use 3P Switch ——— 400 Use 3P Switch —Use 3P Switch ——— 600 Use 3P Switch —Use 3P Switch ——— 3 Wire (3 Blades)—240 Vac Maximum 30 DU321k 103.00 DU321RBk 195.00 37-1/2 60 DU322k 137.00 DU322RBk 295.00 10 15 100 DU323j 318.00 DU323RBj 544.00 15 30 200 DU324k 589.00 DU324RBk 974.00 15 60l 400 DU325k 1465.00 ———125 600 DU326l 2794.00 ———150 Table 3.3: Fusible System Rating (A)Fuse NEMA 1 Indoor Horsepower Ratings System A Fuse NEMA 1 Indoor Horsepower Ratings Cat. No. n $ Price Std. Max. Cat. No. n $ Price Std. Max. 2 Wire (1 Blade and Fuseholder, 1 Neutral)—120 Vac 3 Wire (2 Blades and Fuseholders, 1 Neutral)—120/240 Vac 30 Plug L111N $35.90 1/2 2 30 Plug L211N 47.80 1-1/2 m 3 m 30 Cart.L221N 65.00 1-1/2 m 3 mL211N DE1A DE2A Discount Schedule Modified4/16/09 www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-3 General Duty Safety Switches Accessories, Lug Data and Dimension Class 3130 Field-Installable Electrical Interlock Kits Electrical interlocks for Series F 100–200 A general duty safety switches and Series F 60 A fusible general duty safety switches are available in kit form for field installation. Each kit contains instructions for proper field mounting. A pivot arm operates from switch mechanism, breaking the control circuit before the main switch blades break. Switches with electrical interlocks installed are UL Listed. a Electrical interlock kit catalog numbers with -1 suffix indicates one normally open and one normally closed contact; -2 indicates two normally open and two normally closed contacts. Kits are UL Listed. Field-Installable Fuse Puller Kits Kit consists of three fuse pullers as required for a 3P, fusible, 60 and 100 A general duty switch. Kits can be installed in 60 and 100 A Series F switches. b 30–100 A switches suitable for 60oC or 75oC conductors. 200–800 A switches suitable for 75oC conductors. c 30–100 A switches suitable for 60oC or 75oC conductors. 200–800 A switches suitable for 75oC conductors. Table 3.4: Electrical Interlock Kit Switch Rating(A)Electrical Interlock KitCat. No.a $ Price Fusible Series F 60 EIK031 orEIK032 145.00 Series F 100–200 EIK1 orEIK2 207.00 Table 3.5: Field-Installable Class J Fuse Kit The kit consists of three Class J fuse adapters as required for a 3P, fusible 600 A general duty switch. Kit can be installed in 600 A series E3 switches only (NEMA 1). Switch Rating(A)Class J KitCat. No.$ Price 600 A Series E3 GDJK600 195.00 H DW/H W Description Cat. No.$ Price Series F 60 A Fuse Puller Kit FPK03 20.00 Series F 100 A Fuse Puller Kit FPK0610 28.40 Table 3.6: Field-Installable Service Grounding Kits Switch Rating (A)Cat. No.$ Price Wire Size (AWG) 30 PK3GTA1 7.60 (2) 12 Cu or (2) 10 Al or (1) 4 Al/Cu Max. Series E 60 PK3GTA1 7.60 (2) 12 Cu or (2) 10 Al or (1) 4 Al/Cu Max. Series F 60 GTK03 7.60 (2) 12 Cu or (2) 10 Al or (1) 4 Al/Cu Max. 100 GTK0610 12.60 (2) 1/0 Al/Cu Max. 200 PKOGTA2 36.80 (2) 2/0 Al/Cu Max. 400 PKOGTA2 36.80 (2) 2/0 Al/Cu Max. 600 (Two Required)Per Lug 800 PKOGTA3 82.00 (6) 3/0 Al/Cu Max. Table 3.7: Terminal Lug Datab Rating(A)ConductorsPer Phase Wire RangeWire Bending Space Per NEC Table 312.6AWG/kcmil Lug Wire RangeAWG/kcmil 30 1 12–6 (Al) or 14–6 (Cu) 12–6 (Al) or 14–6 (Cu) 60 1 10–3 (Al) or 14–3 (Cu) 10–2 (Al) or 14–2 (Cu) 100 1 12–1 (Al) or 14–1 (Cu) 12–1/0 (Al) or 14–1/0 (Cu) 200 1 6 –250 (Al/Cu) 6 –300 (Al/Cu) 400NEMA 1 1or2 1/0 –600 (Al/Cu)or 1/0 –300 (Al/Cu) (1) 1/0 –750 (Al/Cu)or(2) 1/0 –300 (Al/Cu) 400NEMA 3R 2 1/0–250 (Al/Cu) (1) 1 –600 (Al/Cu)or(2) 1/0 –250 (Al/Cu) 600 2 4 –500 (Al/Cu) 4 –600 (Al/Cu) 800 3 3/0 –500 (Al/Cu) 3/0 –500 (Al/Cu) Table 3.8: Field-Installable Lug Kit Kit consists of three line, three load, and two neutral lugs as required for a 3P 400 A or 600 A general duty switch. Kit can be installed on 400 or 600 A Series E3 switches. This kit applicable to NEMA 1 enclosures only. Switch Rating(A)Lug Kit Cat. No.Wire Range/NEC 312.6AWG/kcmil Lug Wire Range per LugAWG/kcmil $ Price 400 or 600 A Series E3 GD4060LK (1) 1/0–600 or(2) 1/0–500 or(4) 1/0–250 (2) 1/0–600 or(4) 1/0–250 269.00 Table 3.9: Approximate Dimensions Cat. No. Series HWW/HDStd.Pack Cat. No. Series HWW/HDStd.Packin. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm L111N E2 7.63 194 5.00 127 6.13 156 4.00 102 1 D325NTRc E1 30.63 778 21.38 543 22.25 565 10.13 257 1 L211N E2 7.63 194 5.00 127 6.13 156 4.00 102 1 D326Nc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1 L221N E2 7.63 194 5.00 127 6.13 156 4.00 102 1 D326NTc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1 D211Nc E3 9.25 235 6.75 171 7.25 184 3.63 92 5 D326NRc E1 49.13 1248 24.75 629 25.13 638 8.88 226 1 D211NRBc E2 9.63 245 7.25 184 7.75 197 3.75 95 5 D326NTRc E1 49.13 1246 24.75 629 25.13 638 8.88 226 1 D221Nc E3 9.25 235 6.75 171 7.25 184 3.63 92 5 DU221RBc E2 9.63 245 7.25 184 7.75 197 3.75 95 5 D221NRBc E3 9.63 245 7.25 184 7.75 197 3.75 95 5 DU222RBc E1 9.63 245 7.25 184 7.75 197 3.75 95 5 D222N F1 14.63 372 6.50 165 7.45 189 4.88 124 1 DU321c E2 9.25 235 6.75 171 7.25 184 3.63 92 5 D222NRB F1 14.88 378 6.63 168 7.45 189 4.88 124 1 DU321RBc E2 9.63 245 7.25 184 7.75 197 3.75 95 5 D223N F3 17.50 445 8.50 216 10.50 267 6.50 165 1 DU322c E1 9.25 235 6.75 171 7.25 184 3.63 92 5 D223NRB F3 17.50 445 8.50 216 10.50 267 6.50 165 1 DU322RBc E1 9.63 245 7.25 184 7.75 197 3.75 95 5 D224N F1 29.00 737 17.25 438 19.00 483 8.25 210 1 DU323 F3 17.50 445 8.50 216 10.50 267 6.50 165 1 D224NRB F1 29.25 743 17.25 438 19.00 483 8.25 210 1 DU323RB F3 17.50 445 8.50 216 10.50 267 6.50 165 1 D225N E3 45.12 1146 24.00 610 24.88 632 8.88 226 1 DU324 F1 29.00 737 17.25 438 19.00 483 8.25 210 1 D225NR E1 30.63 778 21.38 543 22.25 565 10.13 257 1 DU324RB F1 29.25 743 17.25 438 19.00 483 8.25 210 1 D226Nc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1 DU325c E3 45.12 1146 24.00 610 24.88 632 8.88 226 1 D226NRc E1 49.13 1248 24.75 629 25.13 638 8.88 226 1 DU326c E3 49.13 1248 24.00 610 24.88 632 8.88 226 1 D321Nc E3 9.25 235 6.75 171 7.25 184 3.63 92 5 QO200TRc G3 6.50 165 4.63 118 — — 3.88 99 5 D321NRBc E3 9.63 245 7.25 184 7.75 197 3.75 95 5 QO260NATSc E2 9.25 235 4.88 124 — — 3.25 83 1 D322N F1 14.63 372 6.50 165 7.45 189 4.88 124 1 QO2000NRBc E1 14.00 356 7.75 197 — — 4.50 114 1 D322NRB F1 14.88 378 6.63 168 7.45 189 4.88 124 1 QO2000NSc E1 13.38 340 6.13 156 — — 3.50 89 1 D323N F3 17.50 445 8.50 216 10.50 267 6.50 165 1 T327Nc E1 49.13 1248 24.00 610 24.88 632 8.88 226 1 D323NRB F3 17.50 445 8.50 216 10.50 267 6.50 165 1 T327NRc E1 49.13 1248 24.75 629 25.13 638 8.88 226 1 D324N F1 29.00 737 17.25 438 19.00 483 8.25 210 1 D325NTRc E1 30.63 778 21.38 543 22.25 565 10.13 257 1 D324NRB F1 29.25 743 17.25 438 19.00 483 8.25 210 1 D326Nc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1 D325Nc E3 45.12 1146 24.00 610 24.88 632 8.88 226 1 D326NTc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1 D325NTc E3 45.12 1146 24.00 610 24.88 632 8.88 226 1 D326NRc E1 49.13 1248 24.75 629 25.13 638 8.88 226 1 D325NRc E1 30.63 778 21.38 543 22.25 565 10.13 257 1 DE1 DE3A Discount Schedule www.schneider-electric.us 3 S A F E T Y S W I T C H E S 3-4 © 2007 Schneider Electric All Rights Reserved Heavy Duty Safety Switches 240 Volt Class 3110 Visible blade heavy duty safety switches are designed for application where maximum performance and continuity of service are required. All heavy duty safety switches feature quick-make, quick-break operating mechanism, a dual cover interlock and a color coded indicator handle. They are suitable for use as service equipment when equipped with a field- or factory-installed neutral assembly or equipment grounding kit, unless a 600Y/347 V or 480 Y/277 V, 1000 A or greater, solidly grounded WYE system is used, per NEC 215-10. Heavy duty safety switches are UL Listed (except as noted), File E2875 & 154828 and meet or exceed the NEMA Standard KS1. For UL Listed short circuit current ratings, see page 3-6. Dimensions: NEMA 1 and 3R . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-12 Dimensions: NEMA 4, 4X and 5 Stainless and NEMA 12 . . . . . . .page 3-13 Accessories: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3-9 through 3-11 NEMA 1 NEMA 3R NEMA 4, 4X and 5 Stainless Steel NEMA 12 Table 3.10: 240 Volt—Single Throw Fusible System Amperes NEMA 1Indoor NEMA 3RRainproof(Bolt-on Hubs,page 3-9) NEMA 4, 4X, 5, a304 Stainless Steel (for 316 stainless, seepage 3-7) Dust tight, Watertight, Corrosion Resistant (Watertight Hubs, page 3-9) NEMA 12KWithKnockouts(Watertight Hubs,page 3-9) NEMA12, 3R bWithoutKnockouts (Watertight Hubs, page 3-9) Horsepower Ratings c 240 Vac 250 Vdcd Std.(Using Fast Acting, One Time Fuses) Max.(Using Dual Element, Time Delay Fuses) Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 1Ø 3Ø 1Ø 3Ø 2 Wire (2 Blades and Fuseholders)—240 Vac, 250 Vdc 30 Use 3 Wire DevicesFor 2 Wire Applications H221DS 1298.00 H221A 336.00 H221AWK 315.00 1-1/2 3 e 37-1/2e 5 30 ————H2212AWKf 392.00 1-1/2 —3 —5 60 H222DS 1558.00 — —H222AWK 431.00 37-1/2e10 15 e 10 100 H223DS 3396.00 H223A 672.00 H223AWK 632.00 7-1/2 15 e 15 30 e 20 200 H224DS 4640.00 H224A 1158.00 H224AWK 1095.00 15 25 e —60 e 40 400 H225 1819.00 H225R 2589.00 H225DS 9654.00 — —H225AWK 2775.00 — — — —50 600 H226 3616.00 H226R 4854.00 H226DS 13848.00 — —H226AWK 4362.00 —75 e —200 e 50 800 H227 5639.00 H227Rg 7655.00 — — — —H227AWK 6883.00 50 —50 —50 1200 H228 7788.00 H228Rg 10324.00 — — — —H228AWK 10543.00 50 —50 —50 3 Wire (2 Blades and Fuseholders, 1 Neutral)—240 Vac, 250 Vdc 30 H221N 157.00 H221NRB 298.00 Use 2 Wire Devices,Field-Installable Solid Neutral AssembliesOrder Separately See page 3-10. 1-1/2 3 e 37-1/2 e 5 60 H222N 314.00 H222NRB 561.00 37-1/2e10 15 e 10 100 H223N 477.00 H223NRB 724.00 7-1/2 15 e 15 30 e 20 200 H224N 859.00 H224NRB 1041.00 15 25 e —60 e 40 400 H225N 2061.00 H225NR 2830.00 H225NDS 9858.00 — —H225NAWK 2869.00 —50 e —125 e 50 600 H226N 3879.00 H226NR 5118.00 H226NDS 14054.00 — —H226NAWK 4624.00 —75 e —200 e 50 800 H227N 6711.00 H227NRg 8144.00 — — — —H227NAWK 8225.00 50 —50 —50 1200 H228N 8281.00 H228NRg 11110.00 — — — —H228NAWK 11456.00 50 —50 —50 3 Wire (3 Blades and Fuseholders)—240 Vac, 250 Vdc 30 Use 4 Wire DevicesFor 3 Wire Applications H321DS 1366.00 H321A 426.00 H321AWK 403.00 1-1/2 3 3 7-1/2 5 60 H322DS 1688.00 H322A 609.00 H322AWK 576.00 3 7-1/2 10 15 10 100 H323DS 3564.00 H323A 941.00 H323AWK 887.00 7-1/2 15 15 30 20 200 H324DS 4997.00 H324A 1360.00 H324AWK 1284.00 15 25 —60 40 400 H325 2283.00 H325R 2650.00 H325DS 9974.00 — —H325AWK 2835.00 —50 —125 50 600 H326 4113.00 H326R 5524.00 H326DS 14266.00 — —H326AWK 4910.00 —75 —200 50 800 H327 7637.00 H327Rg 9899.00 — — — —H327AWK 9685.00 50 100 50 250 50 1200 H328 9678.00 H328Rg 12485.00 — — — —H328AWK 11633.00 50 100 50 250 50 4 Wire (3 Blades and Fuseholders, 1 Neutral)—240 Vac, 250 Vdc 30 H321N 209.00 H321NRB 370.00 Use 3 Wire Devices,Field-Installable Solid Neutral AssembliesOrder Separately. See page 3-10 1-1/2 3 3 7-1/2 5 60 H322N 352.00 H322NRB 594.00 3 7-1/2 10 15 10 100 H323N 561.00 H323NRB 852.00 7-1/2 15 15 30 20 200 H324N 967.00 H324NRB 1165.00 15 25 —60 40 400 H325N 2525.00 H325NR 2881.00 H325NDS 10214.00 — —H325NAWK 3090.00 —50 —125 50 600 H326N 4346.00 H326NR 5748.00 H326NDS 14506.00 — —H326NAWK 5171.00 —75 —200 50 800 H327N 8126.00 H327NRg 10375.00 — — — —H327NAWK 10586.00 50 100 50 250 50 1200 H328N 10209.00 H328NRg 13139.00 — — — —H328NAWK 13343.00 50 100 50 250 50 4 Wire (4 Blades and Fuseholders) 30 Use 600 Vac Devices. See page 3-5. 60 100 200 400 600 a Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12. For NEMA 3R applications, remove drain screw from bottom endwall. b Also suitable for NEMA 3R application by removing drain screw from bottom endwall. c Refer to page 7-31 for additional motor application data. The starting current of motors of more than standard horsepower may require the use of fuses with appropriate time delay characteristics. d For switching dc, use two switching poles. e For corner grounded delta systems only and with neutral assembly installed. Use switching poles for ungrounded conductors. f 60 ampere switch with 30 ampere fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks. g Suitable for NEMA 5 applications with drain screw installed. DE1 Discount Schedule www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-5 Heavy Duty Safety Switches 600 Volt Class 3110 Class H Fuse Provisions: Fusible Square D 30 through 600 A heavy duty safety switches accept Class H fuses as standard. With Class H fuses installed, the switch is UL Listed for use on systems with up to 10 kA available fault current. Class R Fuse Provisions: Fusible Square D 30–600 A heavy duty safety switches will accept Class R fuses as standard. A field-installable rejection kit is available which, when installed, rejects all but Class R fuses. With the installation of the rejection kit and Class R fuses, the switch is UL Listed for use on systems with up to 200 kA available fault current. See Class R fuse kits on page 3-9. Class J Fuse Provisions: Provisions for installing Class J fuses are included in 30 through 400 A 600 Volt, and 100 through 400 A 240 Volt, fusible heavy duty safety switches. Conversion to Class J fuse spacing requires relocating the load side fuse base assembly from the standard Class H fuse location to an alternate position as marked in the enclosure. With Class J fuses installed, the switch is UL Listed for use on systems with up to 200 kA available fault current. Switches rated 600 A, 240 or 600 Volt, require the addition of an adapter kit, H600J at $304. One kit per 3P switch. Class L Fuse Provisions: Fusible 800 A and 1200 A safety switches use Class L bolt-in fuses and are rated for use on systems with up to 200 kA at 600 Vac maximum. 1200 A switches accept class L fuses from 601–1200 A, 800 A switches accept class L fuses from 601–800 A. Dimensions: NEMA 1 and 3R . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-12 Dimensions: NEMA 4, 4X and 5 . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-13 Accessories: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages 3-9 through 3-11 Table 3.11: 600 Volts—Single Throw Fusible System Amperes NEMA 1Indoor NEMA 3RRainproof(Bolt-on Hubs,page 3-9) NEMA 4, 4X, 5a304 Stainless Steel(for 316 stainless, see page 3-7) Dust tight, Watertight, Corrosion Resistant(Watertight Hubs, page 3-9) NEMA 12KWith Knockouts(Watertight Hubs,page 3-9) NEMA 12, 3RbWithout Knockouts(Watertight Hubs,page 3-9) Horsepower Ratingsc 480 Vac 600 Vac dce Std.(Using Fast Acting, One Time Fuses) Max.(Using Dual Element, Time Delay Fuses) Std.(Using Fast Acting, One Time Fuses) Max.(Using Dual Element, Time Delay Fuses) Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 3Ø 3Ø 3Ø 3Ø 250 600 2 Wire (2 Blades and Fuseholders)—600 Vac, 600 Vdc 30 Use 3 Wire DevicesFor 2 Wire Applications — ————— 60 — ————— 100 — ————— 200 — ————— 400 H265 2804.00 H265R 3616.00 H265DS 9974.00 — —H265AWK 3350.00 100d 250d ——50 50 600 H266 4435.00 H266R 7124.00 H266DS 14266.00 — —H266AWK 4894.00 150d 400d ——50 50 800 H267 6910.00 H267Rg 10923.00 — — — —H267AWK 10184.00 — — — —50 50 1200 H268 9713.00 H268Rg 11994.00 — — — —H268AWK 12029.00 — — — —50 50 3 Wire (3 Blades and Fuseholders)—600 Vac, 600 Vdce 30 H361 352.00 H361RB 599.00 H361DS 1680.00 H361A 676.00 H361AWK 637.00 5157-1/220515 30 H3612f 411.00 H3612RBf 699.00 — —H3612Af 690.00 H3612AWKf 651.00 5157-1/220—1560H362425.00 H362RB 703.00 H362DS 1847.00 H362A 698.00 H362AWK 656.00 15 30 15 50 —30 100 H363 792.00 H363RB 1096.00 H363DS 3662.00 H363A 1084.00 H363AWK 1026.00 25 60 30 75 —50 200 H364 1138.00 H364RB 1506.00 H364DS 5123.00 H364A 1696.00 H364AWK 1600.00 50 125 60 150 40 50 400 H365 3034.00 H365R 3688.00 H365DS 10214.00 — —H365AWK 3641.00 100 250 125 350 50 50 600 H366 5099.00 H366R 7266.00 H366DS 14056.00 — —H366AWK 6135.00 150 400 200 500 50 50 800 H367 8879.00 H367R g 11000.00 — — — —H367AWK 10901.00 200 500 250 500 50 50 1200 H368 11671.00 H368Rg 13339.00 —— — —H368AWK 13137.00 200 500 250 500 50 50 4 Wire (3 Blades and Fuseholders, 1 Neutral)—600 Vac, 600 Vdce 30 H361N 411.00 H361NRB 657.00 Use 3 Wire Devices Field-Installable Solid NeutralAssemblies. Order Separately. See page 3-10 5157-1/220—1560H362N473.0 H362NRB 756.00 15 30 15 50 —30100H363N852.00 H363NRB 1158.00 25 60 30 75 —50200H364N1246.00 H364NRB 1605.00 H364NDS 5247.00 H364NA 1810.00 H364NAWK 1705.00 50 125 60 150 40 50400H365N3265.00 H365NR 3843.00 H365NDS 10445.00 — —H365NAWK 3882.00 100 250 125 350 50 50600H366N5346.00 H366NR 7369.00 H366NDS 14748.00 — —H366NAWK 6400.00 150 400 200 500 50 50800H367N9362.00 H367NRg 11470.00 — — — —H367NAWK 11502.00 200 500 250 500 50 501200H368N12076.00 H368NRg 13995.00 — — — —H368NAWK 13880.00 200 500 250 500 50 50 4 Wire (4 Blades and Fuseholders)—600 Vac, 600 Vdch 2Ø 2Ø 2Ø 2Ø 30 H461 609.00 — —H461DS 1958.00 — —H461AWK 743.00 7-1/2 20 10 25 5 15 60 H462 710.00 — —H462DS 2046.00 — —H462AWK 838.00 15 40 20 50 10 30 100 H463 1185.00 — —H463DS 5563.00 — —H463AWK 1288.00 25 50 30 75 20 30 200 H464 1971.00 — —H464DS 8397.00 — —H464AWK 2148.00 50 —50 —40 50 400 H465 4140.00 — — — — — —H465AWK 4538.00 100 250 125 350 50 50 600 H466 6736.00 — — — — — — — — 150 400 200 500 50 50 6 Wire (6 Blades and Fuseholders)—600 Vac h 3Ø 3Ø 3Ø 3Ø 100 —— — —H663DS 17309.00 — —H663AWK 3408.00 25 60 30 75 —— 200 —— — —H664DS 23595.00 — —H664AWK 8148.00 For applications requiring motor disconnect capability, use electrical interlock. Refer to page 3-9. a Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12. b Also suitable for NEMA 3R application by removing drain screw from bottom endwall. c Refer to page 7-35 for additional motor application data. The starting current of motors of more than standard horsepower may require the use of fuses with appropriate time delay characteristics. d For corner grounded delta systems only and with neutral assembly installed. Use switching poles for ungrounded conductors. e On 3P devices, use two outside poles for switching dc. f 60 A switch with 30 A fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks. g Suitable for NEMA 5 applications with drain screw installed. h Not suitable for use as service equipment. Class R Fuse DE1 Discount Schedule www.schneider-electric.us 3 S A F E T Y S W I T C H E S 3-6 © 2007 Schneider Electric All Rights Reserved Heavy Duty Safety Switches UL Listed Maximum Short Circuit Current Ratings—AC only NOTE:Consult the wiring diagram of the switch to verify the UL Listed short circuit current rating. m On 600 V, 200 A switches, 100,000 A max. on corner grounded delta when protected by Class J or R fuses. Any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used in conjunction with an non-fused safety switch when there is up to 10 kA short circuit current available. (See table below.) Above 10, kA—When applied on systems with greater than 10 kA short circuit current available, the UL Listed short circuit current rating for Square D non-fused switches is based upon the switch being used in conjunction with fuses or Square D circuit breakers or Mag-Gard motor circuit protectors. Table 3.12: 600 Volt—Single Throw Non-Fusible System Rating(A) NEMA 1Indoor NEMA 3RRainproof(Bolt-on Hubs, page 3-9) NEMA 4, 4X, 5 a304 Stainless Steel(for 316 stainless, see page 3-7)Dust tight, WatertightCorrosion Resistant(Watertight Hubs, page 3-9) NEMA 12KWithKnockouts(Watertight Hubs, page 3-9) NEMA 12, 3RbWithoutKnockouts(Watertight Hubs, page 3-9) Horsepower Ratings(Max.) c Volts ac dcd240 480 600 Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 1Ø 3Ø 1Ø 3Ø 1Ø 3Ø 250 600 2 Wire (2 Blades)—600 Vac, 600 Vdc 30 Use 3 Wire DevicesFor 2 Wire Applications —— — ——— — — 60 —— — ——— — — 100 —— — ——— — — 200 —— — ——— — — 400 HU265 1833.00 HU265R 2509.00 HU265DS 8541.00 — —HU265AWK 2141.00 — — — — — —50 50 600 HU266 3264.00 HU266R 5022.00 HU266DS 12303.00 — —HU266AWK 3605.00 — — — — — —50 50 800 HU267 4978.00 HU267Re 8589.00 — — — —HU267AWK 8638.00 50 —50 —50 ——50 1200 HU268 6817.00 HU268Re 11595.00 — — — —HU268AWK 11681.00 50 —50 ———50 50 3 Wire (3 Blades)—600 Vac, 600 Vdc 30 HU361 186.00 HU361RB 325.00 HU361DS 1413.00 HU361A 459.00 HU361AWK 431.00 5 10 7-1/2 20 10 30 5 15 30 HU361EIf 425.00 HU361RBEIf 564.00 HU361DSEIf 1653.00 HU361AEIf 698.00 HU361AWKEIf 671.00 5 10 7-1/2 20 10 30 5 15 30 HU3612g 246.00 HU3612RBg 425.00 ——HU3612Ag 473.00 HU3612AWKg 444.00 5 10 7-1/2 20 10 30 5 15 60 HU362 325.00 HU362RB 584.00 HU362DS 1680.00 HU362A 583.00 HU362AWK 555.00 10 20 25 50 30 60 10 30 60 —— — —HU362DSEIf 1981.00 — ———10 20 25 50 30 60 10 30 100 HU363 522.00 HU363RB 817.00 HU363DS 3401.00 HU363A 843.00 HU363AWK 796.00 20 40 40 75 40 100 20 50 200 HU364 806.00 HU364RB 990.00 HU364DS 4640.00 HU364A 1131.00 HU364AWK 1069.00 15 60 50 125 50 150 40 50 400 HU365 1869.00 HU365R 2560.00 HU365DS 9529.00 — —HU365AWK 2682.00 —125 —250 —350 50 50 600 HU366 3328.00 HU366R 5122.00 HU366DS 12708.00 — —HU366AWK 4474.00 —200 —400 —500 50 50 800 HU367 6652.00 HU367Re 8700.00 ——— —HU367AWK 8731.00 50 250 50 500 50 500 50 50 1200 HU368 8947.00 HU368Re 11911.00 ——— —HU368AWK 11960.00 50 250 50 500 50 500 50 50 4 Wire (4 Blades)—600 Vac, 600 Vdck 2Ø 3Ø 2Ø 3Ø 2Ø 3Ø 30 HU461h 551.00 — —HU461DS 1724.00 — —HU461AWKi 610.00 10 10 20 20 25 30 10j 15j 60 HU462h 609.00 — —HU462DS 2018.00 — —HU462AWK 672.00 20 20 40 50 50 60 10 30 100 HU463h 1098.00 — —HU463DS 4934.00 — —HU463AWK 1194.00 30 40 50 75 50 75 20 30 200 HU464h 1599.00 — —HU464DS 7496.00 — —HU464AWK 1888.00 50 60 50 125 50 150 40 50 400 HU465 3467.00 — ———— —HU465AWK 3781.00 — 125 — 250 —350 50 50 600 HU466 6048.00 — ———— ——— — 200 — 400 — 500 50 50 6 Wire (6 Blades)—600 Vack 3Ø 3Ø 3Ø 30 —— — —HU661DS 7935.00 — —HU661AWKl 2238.00 —10 —20 —30 —— 60 —— — —HU662DS 8836.00 — —HU662AWKl 2589.00 —20 —50 —60 —— 100 —— — —HU663DS 13762.00 — —HU663AWKl 3195.00 —40 —75 —75 —— 200 —— — —HU664DS 18877.00 — —HU664AWKl 7025.00 —60 —125 —150 —— a Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12. b Also suitable for NEMA 3R application by removing drain screw from bottom endwall. c Refer to page 7-32 for additional motor application data. d For switching dc, use two switching poles. e Suitable for NEMA 5 applications with drain screw installed. f Switches with EI suffix are stocked with factory-installed electrical interlocks with one normally open and one normally closed contact. g Use 60 A enclosure accessories, including electrical interlocks. h No knockouts are provided. i Check series number on switch for correct accessory. See page 3-13. j HU461AWK (Series E1) is rated 5 hp@250 Vdc, 10 hp@600 Vdc. k Not suitable for use as service equipment. l One enclosure for NEMA 1, 3, 3R or 12 applications. UL Listed. Table 3.13: Fusible Safety Switches For the short circuit current rating, refer to the table below. Heavy DutySafety Switch Type UL ListedFuse Class UL Listed Short CircuitCurrent Ratings Fusible H, K 10 kA R, J, L 200 kAm Table 3.14: Maximum I 2t and Ip Ratings of Heavy Duty Switchesn Switch Rating(A)Max. I2t Rating(Amp2 sec.)Max Ip Rating(A) 30 50,000 14,000 60 200,000 26,000 100 500,000 32,000 200 2,000,000 50,000 400 6,000,000 75,000 600 12,000,000 100,000 800 10,000,000 80,000 1200 15,000,000 120,000 n Per UL 489, Table 7.12, page 7-11. Table 3.15: Non-Fusible Safety Switches Heavy Duty Safety Switch Type Switch Rating(A) o Fuse or Circuit Breaker Typep UL Listed Short Circuit Current Rating Non-FusedSwitches All Any Brand Circuit Breaker Up to 10 kAH, K R,T,J.L 200 kA 30–100 FA 14 kA 30–100 FH 18 kA 200 KA 22 kA400 LA 600 MA 200 KH 25 kA400 LH 600 MH o Applies to NEMA 1, 3R, 4X stainless, 12 switches. p Ampere rating of fuse or circuit breaker not to exceed switch ampere rating. DE1 Discount Schedule Modified4/17/09 www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-7 Heavy Duty Safety Switches–Special Applications Class 3110 316 Grade Stainless Steel—NEMA 3, 3R, 4, 4X, 5, 12 Type 316 stainless steel enclosure safety switches offer superior corrosion resistance to a wider range of chemicals than Type 304 stainless switches. Type 316 better resists chloride and is often used in marine, waste treatment and transportation applications. Use watertight hubs from page 3-9. Equipment grounding lugs are supplied as standard. (For Type 304 stainless switches see pages 3-4–3-6.) Fiberglass Reinforced Polyester Enclosures—NEMA 4X Fiberglass reinforced polyester enclosures are watertight, corrosion resistant, and impervious to windblown dust, rain, and splashing liquid. The molded fiberglass is extremely stable in a wide range of operating temperatures and can withstand heavy impact. Switches are furnished with hubs (page 3-13) and equipment grounding lugs. UL Listed. Krydon® Enclosures—NEMA 4X Krydon enclosures are compression molded of fiberglass reinforced polyester, specially formulated to withstand attack from almost any corrosive atmosphere found in the toughest industrial application. Switches are furnished with hubs (page 3-13) and equipment grounding lugs. UL Listed. NEMA 7 and 9 An enclosed automatic molded case switch for use in Divisions 1 and 2 of the following: Class I, Groups C and D; Class II, Groups E, F and G; or Class III, Hazardous Locations as defined in NEC® Article 500. Furnished with threaded conduit openings in both top and bottom endwall (page 3-13). Suitable for use as service equipment and listed as “Raintight’’ for outdoor applications. UL Listed, and CSA Certified. Equipment grounding lugs supplied as standard. a Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses. b For switching dc use two switching poles. c For EI Kit information and pricing refer to page 3-9. d Not suitable for use as service equipment. e Electrical interlock not available. For auxiliary switches, refer to page 7-4 for catalog number suffix and price adder (e.g. H60XFA1212). f Includes PKDB1, breather and drain kit, required for rainproof application—NEMA 7 only. g Not UL Listed or CSA Certified due to wire bending space requirements. Table 3.16: 3P 600 Vac, 600 Vdc Amperes Cat. No $ Price Horsepower Ratings– 3Øa 480 Vac 600 Vac 600 Vdcb Std. Max.Std.Max. Max. Fusible 30 H361SS 2296.00 5157-1/22015 60 H362SS 2528.00 15 30 15 50 30 100 H363SS 5041.00 25 60 30 75 50 200 H364SS 7061.00 50 125 60 150 50 Non-Fusible 30 HU361SS 1932.00 —20 —30 15 60 HU362SS 2296.00 —50 —60 30 100 HU363SS 4686.00 —75 —100 50 200 HU364SS 6415.00 —125 —150 50 Table 3.17: 3P 600 Vac, 600 Vdc Amperes Cat. No. $ Price Class R Fuse Kits Electrical Interlock Kits Field-Installable Cat. No. c Horsepower Ratings– 3Øa 480 Vac 600 Vac 600 Vdcb Cat. No. $ Price 1 NO/1 NC Contact 2 NO/2 NC Contacts Std. Max. Std. Max. Max. Fusible 30 H361DF 2380.00 RFK06 17.00 9999TC10 9999TC20 5 15 7-1/2 20 15 60 H362DF 2645.00 RFK06H 17.00 9999TC10 9999TC20 15 30 15 50 30 100 H363DF 5075.00 RFK10 31.80 9999TC10 9999TC20 25 60 30 75 50 200 H364DFd 6486.00 HRK1020 31.80 9999R8 9999R9 50 125 60 150 50 Non-Fusible 30 HU361DF 2268.00 — —9999TC10 9999TC20 —20 —30 15 60 HU362DF 2521.00 — —9999TC10 9999TC20 —50 —60 30 100 HU363DF 4827.00 — —9999TC10 9999TC20 —75 —100 50 200 HU364DFd 6463.00 — —9999R8 9999R9 —125 ——50 Table 3.18: 3P, 600 Vac, 600 Vdc Amperes Cat. No. $ Price Class R Fuse Kits Electrical Interlock KitsField-Installable Cat. No. c Horsepower Ratings– 3Øa 480 Vac 600 Vac 600 Vdcb Cat. No. $ Price 1 NO/1 NC Contact 2 NO/2 NC Contacts Std. Max. Std. Max. Max. Fusible 30 H361DX 2774.00 RFK06 17.00 9999TC10 9999TC20 5 15 7 1⁄2 20 15 60 H362DX 3084.00 RFK06H 17.00 9999TC10 9999TC20 15 30 15 50 30 100 H363DX 5905.00 RFK10 31.80 9999TC10 9999TC20 25 60 30 75 50 Non-Fusible 30 HU361DX 2640.00 — —9999TC10 9999TC20 —20 —30 15 60 HU362DX 2937.00 — —9999TC10 9999TC20 —50 —60 30 100 HU363DX 5625.00 — —9999TC10 9999TC20 —75 —100 50 Table 3.19: 3P, Non-Fusible, 600 Vac, 250 Vdc Maximum, Short Circuit Rating 10 kA AIR Amperes Enclosed Molded Case Switchf Solid Neutral Assembly Horsepower Ratings—3Ø Cat. No.g $ Price Cat. No.$ Price 240 Vac 480 Vac 600 Vacb 60 H60XFA 1714.00 100SNA 95.00 15 30 50 60 H60XFA1212 1924.00 100SNA 95.00 15 30 50 100 H100XFA 2030.00 100SNA 95.00 30 60 75 100 H100XFA1212 2191.00 100SNA 95.00 30 60 75 225 H225XKAg 4258.00 225SNA 126.00 60 125 150 H362SS H363DF H361DX H60XFA DE1 Discount Schedule 3-8 © 2007 Schneider Electric All Rights Reserved www.schneider-electric.us 3 S A F E T Y S W I T C H E S Heavy Duty Safety Switches Special Applications—Receptacle Switches Class 3110 Receptacle Switches Interlocked Receptacle Switches are furnished with a factory-installed 3 Phase 4 Wire Appleton Powertite®, Crouse-Hinds Style 2 Arktite®, or Hubbellock® receptacle. The fourth wire is connected to the switch equipment grounding terminal and is not a neutral termination. Interlocking linkage between the receptacle and switch mechanism prevents insertion or removal of the plug while the switch is in the “ON’’ position or insertion of any plug other than specified. Grounding lugs are included. Appleton Powertite Receptacle •Devices are UL Listed and CSA Certified, suitable for use as service equipment. •Receptacles are epoxy powder coated over copper-free cast aluminum and NEMA 3, 3R, 4, 4X and 12 rated. Appleton receptacles are UL Classified for use with the Crouse-Hinds plugs listed below. •Short circuit rating: 10 kA when used in conjunction with Class H or K fuses; 200 kA when used in conjunction with Class R or J fuses. a Receptacle UL Listed for use with “Appleton ACP or CPH” plugs; UL Classified for use with Crouse-Hinds “APJ” Arktite plugs listed on this page. b Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses. c For switching dc, use two switching poles. Crouse-Hinds Arktite Receptacle •UL Listed, suitable for use as service equipment. •Short circuit rating: 10 kA when used in conjunction with Class H or K fuses; 200 kA when used in conjunction with Class R or J fuses. d Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses. Hubbellock Receptacle •UL Listed, suitable for use as service equipment. •Short circuit rating: 10 kA. Note: The Hubbellock receptacle switch utilizes the Square D interlocked plug SD12781 only available from Square D. e Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses. f Hubbell plug is furnished with a Kellems grip for 1-1/2 in. to 1-21/64 in. cable diameter. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3-9 through 3-11. Amperes NEMA 1 NEMA 3, 3R, 4, 4X, 5, 12304 Stainless SteelEnclosure NEMA 12, 3R Use With Plug a Horsepower Ratings–3Øb Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 480 Vac 600 Vac 250 Vdcc Std. Max. Std. Max. Std. Max. Fusible—3P, 600 Vac, 250 Vdc 30 H361WA 1384.00 H361DSWA 2934.00 H361AWA 1526.00 ACP3034BC 823.00 5157-1/220 5— 60 H362WA 1608.00 H362DSWA 3112.00 H362AWA 1672.00 ACP6034BC 863.00 15 30 15 50 10 — 100 H363WA 2459.00 H363DSWA 5645.00 H363AWA 2505.00 ACP1034CD 1285.00 25 60 30 75 20 — Non-Fusible—3P, 600 Vac, 250 Vdc 30 HU361WA 1262.00 HU361DSWA 2667.00 HU361AWA 1384.00 ACP3034BC 823.00 —20 —30 —5 60 HU362WA 1537.00 HU362DSWA 2941.00 HU362AWA 1571.00 ACP6034BC 863.00 —50 —60 —10 100 HU363WA 2102.00 HU363DSWA 5340.00 HU363AWA 2231.00 ACP1034CD 1285.00 —75 —100 —20 Table 3.20: Amperes NEMA 1 NEMA 3, 3R, 4, 4X, 5, 12304 Stainless Steel Enclosure NEMA 12, 3R Use With Plug Horsepower Ratings–3Ød Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 480 Vac 600 Vac Std. Max. Std. Max. Fusible—3P, 600 Vac Maximum 30 H361WC 1426.00 H361DSWC 4251.00 H361AWC 1570.00 APJ3485 823.00 5157-1/220 60 H362WC 1834.00 H362DSWC 5166.00 H362AWC 1897.00 APJ6485 863.00 15 30 15 50 100 H363WC 4003.00 H363DSWC 9884.00 H363AWC 4058.00 APJ10487 1285.00 —60 —75 Non-Fusible—3P, 600 Vac Maximum 30 HU361WC 1301.00 HU361DSWC 3925.00 HU361AWC 1424.00 APJ3485 823.00 —20 —30 60 HU362WC 1756.00 HU362DSWC 4916.00 HU362AWC 1785.00 APJ6485 863.00 —50 —60 100 HU363WC 3499.00 HU363DSWC 9350.00 HU363AWC 3629.00 APJ10487 1285.00 —60 —100 Table 3.21: Amperes NEMA 1 NEMA 12 Use With Plug Horsepower Ratings—3Øe Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 480 Vac 600 Vac Std. Max. Std. Max. Fusible—3P, 600 Vac Maximum 60 H362WH 1567.00 H362AWH 1639.00 SD12781f 406.00 15 30 15 50 Non-Fusible—3P, 600 Vac Maximum 60 HU362WH 1491.00 HU362AWH 1540.00 SD12781f 406.00 —50 —60 H362AWA Interlocked Receptacle Switch with Appleton Powertite Receptacle H362AWC Interlocked Receptacle Switch with Crouse-Hinds H362AWH Interlocked Receptacle Switch with Hubbell Hubbellock Receptacle DE1 Discount Schedule www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-9 Heavy Duty Safety Switches–Special Accessories Electrical Interlock Kits Electrical interlocks for heavy duty 30–1200 A safety switches are available factory-installed or in kit form for field installation. Each kit contains instructions for proper field mounting. A pivot arm operates from switch mechanism, breaking the control circuit before the main switch blades break. Switches with electrical interlocks installed are UL Listed. For factory-installed electrical interlocks add EI (for one contact) or EI2 (for two contacts) suffix to catalog number. a See page 3-7 for electrical interlocks on NEMA 4X fiberglass reinforced polyester and Krydon®. b Electrical interlock kit catalog numbers with 1 suffix indicates one normally open and one normally closed contact; 2 indicates two normally open and two normally closed contacts. Kits are UL Listed. c HU461AWK uses EK3061 or EK3062. d The following series -F5–F7 devices use EIK-1,2: H3612, H3612A, H3612AWK, H3612RB, H461, H461DS, H461AWK, HU461, HU461DS, HU661DS, HU661AWK, H361AWA, H361AWC, HU361AWA and HU361AWC. e H362WA, HU362WA, H362WC, H362AWA, HU362AWA, H362AWC, HU362AWC, and H2212AWK use EIK1 or EIK2 electric interlock. f Single pole single throw interlock kits are rated 1⁄2 hp @ 110 and 220 Vac. Class R Fuse Kits When installed, this kit rejects all but Class R fuses. Kits are available for field installation. For factory installation, add “CLR’’ suffix to catalog number. g H221-2AWK uses RFK06 Class R fuse kit. Internal Barrier Kits Internal Barrier Kits provide an additional barrier that helps prevent accidental contact with live parts. Field-installed transparent barriers do not restrict visual inspection of the switch. Barriers provide IEC529 IP2X “finger safe” protection when door of enclosed disconnect switch is open. Convenient door allows use of test probes without accessing fuses and replacement of fuses without removing barrier. Barrier can also be used with the skirt kit to enclose a panel mounted Type 9422 disconnect. j Requires arc shield on 240 V switches be changed to 600 V arc suppressor. Rainproof Bolt-On Hubs—For Use On NEMA 3R Enclosure Conduit Size 3/4 11-1/41-1/222-1/233-1/24Closing Cap Hub Cat. No.B075 B100 B125 B150 B200 B250 B300 B350 B400 BCAP $ Price Each 22.20 22.20 22.20 22.20 40.90 68.00 124.00 200.00 245.00 2.50(DE1A) Note: NEMA 3R rainproof enclosures with Cat. No. ending in RB have a bolt-on closing cap factory-installed. Order bolt-on hubs separately from table above. For more details see page 1-13. Hubs through size 21⁄2 can be directly installed on RB devices. Devices requiring 3" or larger hubs must have holes cut in the field. Gaskets are provided on 3" and larger hubs. Note: All hubs are UL Listed for indoor and rainproof applications and suitable for use with conduit having ANSI standard taper pipe thread. Watertight Hubs—For Use On NEMA 4, 4X and 5 Stainless Steel and NEMA 12 Enclosures Conduit Trade Size 1/2 3/4 1 1-1/4 1-1/2 2 2-1/22 3 3-1/2 4 Standard-Zinc Hub Cat. No.H050 H075 H100 H125 H150 H200 H250 H300 H350 H400 Zinc $ Price Each 20.70 30.00 31.40 36.00 55.00 80.00 92.00 118.00 188.00 254.00 Chrome PlatedHub Cat. No.H050CP H075CP H100CP H125CP H150CP H200CP ——— — RB Hub Table 3.22: Electrical Interlock Kit a Switch Rating(A)Series Number(See pages 3-12, 3-13)Electrical Interlock KitCat. No.b $ Price Factory-Installed$ Price 30 F1, F5–F7 EIK031c d 145.00 239.00EIK032c d F3 EIK1 207.00 301.00EIK2 60 F1-F3F5–F7 (600 V) EIK1 207.00 301.00EIK2 F4F5–F6 (240 V) EIK031e 145.00 239.00EIK032e 100–200 F2–F7 EIK1 207.00 301.00EIK2 400–1200 E1–E4 EIK40601 355.00 449.00EIK40602 Table 3.23: Electrical Interlock Contact Ratingsf Interlock Type AC - 50 or 60 Hz DC Volts Make Break Cont. Volts Make &Break Cont. Cat. No. ending with a 1 utilize a 9007A01 limit switch. 1 NO/1 NCCONTACT 120 40 A 15 A 15 A 115 0.50 A 15 A 240 20 A 10 A 15 A 230 0.25 A 15 A 480 10 A 6 A 15 A ——— 600 8 A 5 A 15 A 600 0.05 A 15 A Cat. No. ending with a 2 utilize a 9007C03 limit switch. 2 NO/2 NCCONTACTS 120 30 A 3.0 A 10 A 115 1.0 A 10 A 240 15 A 1.5 A 10 A 230 0.30 A 10 A 480 7.5 A 0.75 A 10 A ——— 600 6.0 A 0.60 A 10 A 600 0.10 A 10 A Table 3.24: Class R Fuse Kits—240 V (one kit per 3P switch) Switch Rating(A)Series Number(See pages 3-12, 3-13)Class R Fuse KitCat. No.$ Price Factory-Installed $ Price 30 F5–F7 RFK03Lg 17.00 130.00 60 F1, F2, F3 RFK06 17.00 130.00 60 F4–F7 RFK03H 17.00 130.00 100 F2–F7 RFK10 31.80 154.00 200 F5–F6 HRK1020 31.80 154.00 400–600 E HRK4060 74.00 240.00 Table 3.25: Class R Fuse Kits—600 V (one kit per 3P switch) Switch Rating (A) Series Number (See pages 3-12, 3-13) Class R Fuse Kit Cat. No.$ Price Factory-Installed $ Price 30h F1, F5–F7 RFK03Hi 17.00 130.00 30h F3 RFK06 17.00 130.00 60h F1–F7 RFK06Hi 17.00 130.00 100h F2–F7 RFK10 31.80 154.00 200 F5–F6 HRK1020 31.80 154.00 400–600 E2–E4 HRK4060 74.00 240.00 h See page 3-7 for Class R Fuse Kits in NEMA 4X Fiberglass Reinforced Polyester and Krydon switches. i The following series -F5–F7 devices use RFK06: H3612, H3612A, H3612AWK, H3612RB, H461, H461DS, H461AWK, H361AWA and H361AWC. Cat. No. Description Safety Switch Application (F Series Only) 9422 Type T Disconnect Application$ Price SS03 Interior Barrier for 30 A Safety Switchj 600 Vac – 30 A NA 100.240 Vac – 60 A SS06 Interior Barrier for 60 A Safety Switch, 30 or 60 A 9422 Switch 600 Vac – 60 A 600 Vac – 30 A 110.600 Vac – 60 A SS10 Interior Barrier for 100 A Safety Switch or 100 A 9422 Switch 600 Vac – 100 A 600 Vac – 100 A 130. SS20 Interior Barrier for 200 A Safety Switch 600 Vac – 200 A NA 150. SS0306SK Skirt Kit to Enclose 30 or 60A 9422 Switch (requires SS06) NA 600 Vac – 30 A 150.600 Vac – 60 A SS10SK Skirt Kit to Enclose 100 A 9422 Switch (requires SS10) NA 600 Vac – 100 A 170. New! DE1 DE1A Discount Schedule Modified4/16/09 www.schneider-electric.us 3 S A F E T Y S W I T C H E S 3-10 © 2007 Schneider Electric All Rights Reserved Heavy Duty Safety Switches Accessories Class 3110 Note: Neutrals cannot be installed in 4P, 6P, or NEMA 4X fiberglass reinforced polyester safety switches. a The following series -F5–F6 devices use SN0610(C): H-361-2, H-361-2RB, H-361-2A and H-361-2AWK. b For 200% neutral, order (2) neutral kits and (1) SN20NI neutral jumper kit. Price $18.40. (2) 350 Max. Al/Cu. Equipment Grounding Kits Equipment grounding kits are field-installable and UL Listed in 30–1200 A heavy duty switches. For factory installation of equipment grounding kit, add suffix GL to standard Cat. No. (Example: H361GL). Price = Switch + Kit Price. NOTE:Kits are factory-installed standard in 30–200 A series F NEMA 4-4X-5 (stainless) and 12, and in all NEMA 30–200 A Series F 4–6P switches. Note: Shipped in quantities of 6. Special Paint UL Listed heavy duty switches are available painted with special safety colors. Special colors available include: safety red, safety orange, safety yellow, safety green, safety blue, safety purple, black and white. All colors comply with OSHA Standard 1910.144 and ANSI Specification Z535.1 for marking physical hazards. A minimum quantity of 10 is required. To order, add suffix SP to standard Cat. No. Specify color on order. Phenolic Legend Plate Available engraved and mounted on all heavy duty safety switches, except NEMA 7 and 9. Legend engraved in 1/4 in. high white letters on black background. Customer must provide legend. UL Listed. To order, add suffix NP to standard Cat. No. Example: H363-NP Price adder per legend plate—$111.00 Neutral Assemblies—Field-Installable Neutral Assemblies For Fusible and Non-Fusible 240 and 600 Volt Safety Switches Switch Rating (A) Series Number(Seepages 3-12, 3-13) StandardNeutral KitCat. No. Terminal DataAWG/kcmil .rice Optional Copper OnlyNeutral Kit Cat. No.Terminal DataAWG/kcmil $ Price 30 F1, F5–F6 SN03a (3) 2 Max. Al/Cu 55.00 SN03Ca (3) 6 Max. Cu 68.00 60 F1–F3, F5–F6 (600 V)SN0610 (2) 1/0 Max. Al/Cu 71.00 SN0610C (2) 1/0 Max. Cu 76.00(2) 2 Max. Al/Cu (2) 6 Max. Cu F4, F5–F6 (240 V)SN03a (3) 2 Max. Al/Cu 55.00 SN03Ca (3) 6 Max. Cu 68.00 100 F2–F6 SN0610 (2) 1/0 Max. Al/Cu 71.00 SN0610C (2) 1/0 Max. Cu 76.00(2) 6 Max. Al/Cu (2) 6 Max. Cu 200b F5–F6 SN20A (2) 250 Max. Al/Cu(1) 1/0 Max. Al/Cu 133.00 SN20C (2) 250 Max. Cu(1) 1/0 Max. Cu 164.00 400 & 600 E1–E4 H600SN (4) 750 Max. Al/Cu(1) 300 Max. Al/Cu 218.00 H600SNC (2) 600 Max. Cu 301.00(2) 350 Max. Cu (1) 250 Max. Cu 800 E2–E4 H800SNE4 (6) 750 Max. Al/Cu 502.00 — — —(2) 350 Max. Al/Cu 1200 E2–E4 H1200SNE4 (8) 750 Max. Al/Cu 689.00 — — —(2) 350 Max. Al/Cu Equipment Grounding Kits—Field- or Factory-Installable Equipment Grounding Kits–240 and 600 V Switch Rating (A) Series Number (See pages 3-12, 3-13) Standard Cat. No. Terminal Data AWG/kcmil $ Price Optional Copper Only Cat. No. Terminal Data AWG/kcmil $ Price 30 F1, F5–F7 GTK03c (2) 12 Cu or (2) 10 Al or (1) 4 Max. Al/Cu 7.60 GTK03Cc (1) 6 Max. Cu 8.90 60d F1–F3d, F5–F7 (600 V)GTK0610d (2) 2/0 Max. Al/Cu 12.60 GTK0610Cd (2) 4 Max. Cu 15.10 60 F4, F5–F6 (240 V)GTK03 (2) 12 Cu or (2) 10 Al or (1) 4 Max. Al/Cu 7.60 GTK03C (1) 6 Max. Cu 8.90 100 F2–F7 GTK0610 (2) 2/0 Max. Al/Cu 12.60 GTK0610C (2) 4 Max. Cu 15.10 200 F5–F7 PKOGTA2 (2) 2/0 Max. Al/Cu 36.80 PKOGTC2 (2) 4 Max. Cu 38.90 400 & 600 E2–E4 PKOGTA2e (2) 2/0 Max. Al/Cu 36.80 PKOGTC3 (4) 1/0 Max. Cu 71.00f(2 Required) 800 E2–E4 PKOGTA7 (4) 350 Max. Al/Cu 132.00f ——— 1200 E2–E4 PKOGTA8 (8) 350 Max. Al/Cu 135.00f ——— c The following series -F5–F6 devices use GTK0610(C): H-361-2 and H-361-2RB d 4- and 6-pole 30 A F Series. e Two required if grounding conductors are run in parallel. f PE1A Discount Schedule Table 3.26: Square D Gray Paint Description Cat. No.$ Price 16 oz. Aerosol Paint Can, Square D Gray Paint PK49SP 26.00 ea. Price Adder Each Switch Quantity $ Price 30 A 60 A 100 A 200 A 400 A 600 A 10 161.00 185.00 289.00 319.00 758.00 1867.00 DE1 PE1A Discount Schedule www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-11 Heavy Duty Safety Switches Class 3110 Key Interlock Systems Factory-installed only on heavy duty safety switches and double throw safety switches. Interlocks are used to prevent the authorized operator from making an unauthorized operation. Not available on hazardous location devices (NEMA 7/9) or fiberglass reinforced polyester (NEMA 4X). The key interlock system is a simple and easy method of applying individual key interlock units and assemblies to the above equipment so as to require operation in a predetermined sequence. UL Listed. Quoting: Contact Square D for Cat. No., availability, and pricing prior to quoting a job. Ordering: Order cannot be released for production until the following information has been provided: •End User—Company name, address •Function of each lock (e.g., switch to be locked open with key removed, key held when switch is closed) •Existing Equipment—if switch is to be interlocked with equipment already on site, provide brand of existing lock and key number •Other New Equipment—if switch is to be interlocked with new equipment not yet installed at the site, then provide contact person and phone number so that locks may be coordinated •Additional information may be required upon order entry •Schneider Electric locks supplied unless otherwise specified. Use these suffixes on switch Cat. Nos.: •KI = 1 lock per switch •KI2 = 1 lock with 2 cylinders (2 keys) per switch •KIKI = 2 separate locks per switch a Prices do not apply when more than three devices are interlocked, as these schemes normally require more than one key assembly per device. Lock-On Provisions Lock-off provisions are standard on all heavy duty safety switches. Provision for one 3⁄8 in. hasp padlock is available factory-installed on NEMA 1, 3R, 4-4X-5 stainless steel and 12 switches. This modification will allow the switch to be locked in the “ON’’ position. UL Listed. Cover Viewing Window Optional cover viewing window is positioned over the blades to allow visual verification of “ON-OFF’’ status. Available on 30 through 1200 A heavy duty switches, all NEMA Types. (Not available on NEMA 4X fiberglass reinforced polyester, Krydon® enclosures, or NEMA 7 and 9 devices.) Factory-installed only: add “VW’’ suffix to the Cat. No. See table below for price adder. Copper Only Lug Kits Heavy duty safety switches are supplied standard with Al lugs, which accept both Cu and Al wires. For field installation of copper-only lug kits, order kits below. For factory installation of copper only lugs, add suffix SLC to standard Cat. No. Note: NEMA 12, 12K and stainless steel switches with factory-installed lugs bear the UL Marine Listed manifest for use on vessels over 65 feet long. NEMA 12, 12K and stainless steel switches using field-installed copper only lug kits are UL Marine Listed, but do not bear the marine manifest. b One kit includes all phase line/load lugs for a 3-pole switch. Double Lug Kits 200 A heavy duty F-series switches are supplied standard with lugs listed on page 3-12 (one wire per phase). For lugs that accept two wires per phase and neutral, order the following kit: NOTE:Not UL Listed. c Kit contains 3 lugs. For double lugs for line and load, order 2 kits. Table 3.31: 800 and 1200 A Compression Lug Kits– Field- Installable (See page 3-12 for 100–600 A switches) Series E4 800 and 1200 A safety switches are equipped as standard with mechanical lugs. Alternate compression lug kits are available for field installation and are UL Listed. Each kit consists of VCEL07512H1 Versa-Crimp® Compression Lugs and lug landing connectors capable of converting line and load side of one switch pole or neutral. Order one field-installable kit per pole or neutral per table below. Example: 3-pole, 3 wire requires (3) kits; 3-pole, 4 wire requires (4) kits. Note: For terminal lug data, refer to table below. Table 3.32: Factory-Installed Series E4 800 and 1200 A safety switches are available with factory- installed VCEL-075-12H1 Versa-Crimp compression lug kits (above). For factory installation add suffix LK to standard Cat. No. (Example: H367LK) and use price adder from table below based on system type. Note:For terminal Lug data refer to table below. Table 3.27: Price Adder Per Locka Switch Type $ Price 30–1200 A Heavy Duty 1370.00 30–600 A Double Throw 1325.00 Table 3.28: Price Adder Per Each Switch Safety Switch Rating $ Price To order, add suffix SPLO to standard Cat. No. Example: H364-SPLO 30–1200 A 103.00 Table 3.29: Price Adder Per Switch—UL Listed Amperes 2 and 3-Pole 4 and 6-Pole 30–200 A 25.00 50.00 400–1200 A 1531.00 — Table 3.30: Kits – Wire size (page 3-13) Switch(A)Lug Kit Cat. No.b Kit$ Price Factory-InstalledAdder per Switch 30 CL0306F 46.30 149. 60 CL0306F 46.30 149. 100 CL10F 106.00 287. 200 CL20F 176.00 478. 400 CL40F 366.00 993. 600 CL60F 595.00 1617. 800 — — — 1200 — — — Switch(A)Lug KitCat. No.Kit $ Pricec Lug wire range per phase and neutralAWG/kcmil Switch wire range per phase and neutralAWG/kcmil 200 AL20DTF 106.00 (2) 6 –300 Cu/Al (2) 6 –250 Cu/Al SwitchAmperes Lug KitCat. No.$ Price PerPole or Neutral 800 H8LKE2 595.00 1200 H12LKE2 739.00 SwitchAmperes System Factory-Installed$ Price Adder Per Switch 800 2 Wire 1404.00 3 Wire 1981.00 4 Wire 2559.00 1200 2 Wire 1727.00 3 Wire 2464.00 4 Wire 3204.00 Table 3.33: Terminal Lug Data—800 and 1200 A Compression Lugs SwitchAmperes ConductorsPer Phase Compression Lug (VCEL-075-12H1)Wire Range 800 (3) Line 500–750 kcmil (Al) and or (3) Load 500 kcmil (Cu) 1200 (4) Line 500–750 kcmil (Al) and or (4) Load 500 kcmil (Cu) Al/Cu to Cu Only DE1 Discount Schedule www.schneider-electric.us 3 S A F E T Y S W I T C H E S 3-12 © 2007 Schneider Electric All Rights Reserved Heavy Duty Safety Switches NEMA Type 1 and 3R—Dimensions, Lug Data Class 3110 a 30–100 A switches suitable for 60°C or 75°C conductors. 200–1200 A switches suitable for 75oC conductors. b For NEMA 1 and R3 only. c HU461AWK— 14–6 AWG (Cu). d H60XFA— 14–6 AWG (Cu). e H225XKA— 4 AWG–300 kcmil (Cu). f Max. wire range 600 Al/Cu on NEMA 4-4X Stainless and NEMA 12. g Order two PK516KN mounting kits ($5.80 each. Lexington Order Point) when installing VCEL030516H1 lugs. Only one kit is required on 2-Pole switches. h See page 3-11, 800 and 1200 A compression lug kits for additional information. Table 3.34: Terminal Lug Data (NEMA 1, 3R, 4, 4X, 5, 7, 9, 12)a Rating(A) ConductorsPer Phaseand Neutral Wire Range Wire Bending Space Per NEC Table 312.6AWG/kcmil Lug Wire RangeAWG/kcmil Optional Versa-Crimp® Compression LugField-Installableb 30c 1 12–6 (Al) or 14–6 (Cu) 12–2 (Al) or 14–2 (Cu)—2 14–10 (Cu) solid or 14–10 (Cu) stranded 60d 1 14–3 (Al) or 14–3 (Cu) 12–2 (Al) or 14–2 (Cu)— 100 1 12–1/0 (Al) or 14–1/0 (Cu) 12–1/0 (Al) or 14–1/0 (Cu) VCEL02114S1 200e 1 6–250 (Al/Cu) 6–300 (Al/Cu) VCEL030516H1 400 VCEL07512H1 1 1/0–750 (Al/Cu)f 1/0–750 (Al/Cu) or or or and VCEL030516H1g 2 1/0–300 (Al/Cu) 1/0–300 (Al/Cu) and VCEL05012H1 600 2 3/0–500 (Al/Cu) 3/0–500 (Al/Cu) VCEL05012H1 800 3 3/0–750 (Al/Cu) 3/0–750 (Al/Cu) H8LKE2h 1200 4 3/0–750 (Al/Cu) 3/0–750 (Al/Cu) H12LKE2h H W/H D W H W/H D W Typical NEMA 1 Typical NEMA 3R Cat. No. Approximate Dimensions Cat. No. Approximate Dimensions Series HWDW/H Series HWDW/H in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm H221N F5 14.60 371 6.50 165 4.88 124 7.55 192 H364, N F5 29.00 737 17.13 435 8.25 210 18.50 470 H221NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 H364RB, NRB F5 29.25 743 17.25 438 8.50 216 18.63 473 H222N F5 14.60 371 6.50 165 4.88 124 7.55 192 H365, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H222NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 H365R, NR E4 50.31 1278 27.88 708 10.13 257 27.88 708 H223N F5 21.25 540 8.50 216 6.38 162 10.50 267 H366, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H223NRB F5 21.25 540 8.50 216 6.38 162 10.50 267 H366NR, R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H224N F5 29.00 737 17.13 435 8.25 210 18.50 470 H367, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H224NRB F5 29.25 743 17.25 438 8.50 216 18.63 473 H367NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H225, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H368, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H225NR, R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H368NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H226, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 H461 F5 20.50 521 14.75 375 6.85 174 16.13 410 H226NR, R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H462 F5 20.50 521 14.75 375 6.85 174 16.13 410 H227, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H463 F5 20.50 521 14.75 375 6.85 174 16.13 410 H227NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H464 F5 29.00 737 23.25 591 8.75 222 24.88 632 H228, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 H465 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H228NR, R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H466 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H265 E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU265 E4 50.25 1276 27.63 702 10.13 257 27.63 702 H265R E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU265R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H266 E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU266 E4 50.25 1276 27.63 702 10.13 257 27.63 702 H266R E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU266R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H267 E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU267 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H267R E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU267R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H268 E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU268 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H268R E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU268R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H321N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU361 F5 14.60 371 6.50 165 4.88 124 7.55 192 H321NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU361RB F5 14.88 378 6.63 168 4.88 124 7.55 192 H322N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU361WA F6 18.19 462 9.00 229 6.81 173 10.50 267 H322NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU361WC F6 18.19 462 9.00 229 6.81 173 10.50 267 H323N F5 21.25 540 8.50 216 6.38 162 10.50 267 HU362 F5 17.50 445 9.00 229 6.38 162 10.50 267 H323NRB F5 21.25 540 8.50 216 6.38 162 10.50 267 HU362RB F5 17.50 445 9.00 229 6.38 162 10.50 267 H324N F5 29.00 737 17.13 435 8.25 210 18.50 470 HU362WA F6 18.19 462 9.00 229 6.81 173 10.50 267 H324NRB F5 29.25 743 17.25 438 8.50 216 18.63 473 HU362WC F6 16.75 425 9.00 229 7.00 178 10.50 267 H325, N E4 50.25 1276 27.88 708 10.13 257 27.88 708 HU362WH F5 18.19 462 9.00 229 6.81 173 10.50 267 H325R, NR E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU363 F5 21.25 540 8.50 216 6.38 162 10.50 267 H326, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU363RB F5 21.25 540 8.50 216 6.38 162 10.50 267 H326R, NR E4 50.31 1278 27.88 708 10.13 257 27.88 708 HU363WA F6 21.85 462 9.00 229 6.81 173 10.50 267 H327, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU363WC F6 21.85 555 9.00 229 6.81 173 10.50 267 H327R, NR E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU364 F5 29.00 737 17.13 435 8.25 210 18.50 470 H328, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU364RB F5 29.25 743 17.25 438 8.50 216 18.63 473 H328R, NR E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU365 E4 50.25 1276 27.63 702 10.13 257 27.63 702 H361, N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU365R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H361-2 F5 17.50 445 9.00 229 6.38 162 10.50 267 HU366 E4 50.25 1276 27.63 702 10.13 257 27.63 702 H361NRB, RB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU366R E4 50.31 1278 27.88 708 10.13 257 27.88 708 H361WA F6 18.19 462 9.00 229 6.81 173 10.50 267 HU367 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H361WC F6 18.19 462 9.00 229 6.81 173 10.50 267 HU367R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H362, N F5 17.50 445 9.00 229 6.38 162 10.50 267 HU368 E4 69.13 1756 36.62 930 17.75 451 36.62 930 H362NRB, RB F5 17.50 445 9.00 229 6.38 162 10.50 267 HU368R E4 69.13 1756 36.62 930 17.75 451 36.62 930 H362WA F6 18.19 462 9.00 229 6.81 173 10.50 267 HU461 F5 20.50 521 14.75 375 6.85 174 16.13 410 H362WC F6 16.75 425 9.00 229 7.00 178 10.50 267 HU462 F5 20.50 521 14.75 375 6.85 174 16.13 410 H362WH F5 18.19 462 9.00 229 6.81 173 10.50 267 HU463 F5 20.50 521 14.75 375 6.85 174 16.13 410 H363, N F5 21.25 540 8.50 216 6.38 162 10.50 267 HU464 F5 29.00 737 23.25 591 8.75 222 24.88 632 H363NRB, RB F5 21.25 540 8.50 216 6.38 162 10.50 267 HU465 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H363WA F6 21.85 462 9.00 229 6.81 173 10.50 267 HU466 E4 50.25 1276 33.88 861 10.13 257 33.88 861 H363WC F6 21.85 555 9.00 229 6.81 173 10.50 267 www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-13 Heavy Duty Safety Switches Class 3110 NEMA Type 4, 4X, 5, 7, 9 and 12 Table 3.35: Optional Copper Only Lug Kits — (See page 3-11 for pricing. See page 3-12 for terminal lug data for the series switches listed in the dimension table below.) Rating (A) Optional Lug Kit Cat. No.a Lug Wire Range Per Phase AWG/kcmil 30–60 CL0306F (1) 14–8 Cu solid or 14–4 Cu strand 100 CL10F (1) 14–8 Cu solid or 14–1/0 Cu strand200 CL20F (1) 6–250 Cu 400 CL40F (1) 1–600 Cu plus (1) 6–250 Cu 600 CL60F (2) 4–350 Cu a One kit includes all phase line/load lugs for a 3-pole switch. Table 3.36: Conduit Provisions — NEMA 4X Fiberglass Reinforced Polyester and Krydon, NEMA 7 and 9 Rating (A) Top and Bottom Endwall NEMA 4X Fiberglass Reinforced Polyester and Krydonb NEMA 7 and 9c 30 3/4 in. — 60 1-1/4 in. 3/4 in.100 2 in. 1-1/4 in. 200 2-1/2 in. 2-1/2 in. b Hubs and hub drilling templates are provided for field installation. c Threaded conduit opening. Cat. No. Approximate Dimensions Series HWDW/H in. mm in. mm in. mm in. mm H60XFA E1 15.93 405 9.87 251 6.96 177 9.87 251 H100XFA E1 15.93 405 9.87 251 6.96 177 9.87 251 H221AWK, A F6 14.60 371 6.63 168 4.96 125 7.55 192 H221DS F6 14.93 379 7.22 183 5.11 130 8.67 220 H221-2AWK F6 16.50 419 9.00 229 7.00 178 10.50 267 H222AWK, A F6 14.60 371 6.63 168 4.96 125 7.55 192 H222DS F6 14.93 379 7.22 183 5.11 130 8.67 220 H223AWK, A F6 20.50 521 9.00 229 7.00 178 10.50 267 H223DS F6 20.82 529 9.36 238 6.97 177 11.25 286 H224A,AWK F6 29.00 737 17.25 438 8.75 216 18.63 473 H224DS F6 29.00 737 17.75 451 8.88 226 19.25 489 H225AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H225NAWK, NDS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H225XKA C2 22.56 573 10.88 276 7.75 197 10.88 276 H226AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H226NAWK, NDS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H227AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930 H228AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930 H265AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H266AWK, A, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H267AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930 H268AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930 H321AWK, A F6 14.60 371 6.63 168 4.96 125 7.55 192 H321DS F6 14.93 379 7.22 183 5.11 130 8.67 220 H322AWK, A F6 14.60 371 6.63 168 4.96 125 7.55 192 H322DS F6 14.93 379 7.22 183 5.11 130 8.67 220 H323AWK, A F6 20.50 521 9.00 229 7.00 178 10.50 267 H323DS F6 20.82 529 9.36 238 6.97 177 11.25 286 H324A,AWK F6 29.00 737 17.25 438 8.75 216 18.63 473 H324DS F6 29.00 737 17.75 451 8.88 226 19.25 489 H325AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H325NAWK, NDS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H326AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H326NAWK, NDS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H327AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930 H328AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930 H361AWA F7 16.50 419 9.00 229 7.00 178 10.50 267 H361AWC F7 16.50 419 9.00 229 7.00 178 10.50 267 H361AWK, A F6 14.60 371 6.63 168 4.96 125 7.55 192 H361DS F6 14.93 379 7.22 183 5.11 130 8.67 220 H361DSWA F7 16.87 428 8.92 227 5.11 130 10.81 275 H361DSWC F7 16.87 428 8.92 227 5.11 130 10.79 274 H361DF F1 16.50 419 11.00 279 8.80 224 11.00 279 H361DX F1 19.40 493 11.40 290 8.60 218 11.40 290 H361SS F6 14.93 379 7.22 183 5.11 130 8.67 220 H361-2AWK, A F6 16.50 419 9.00 229 7.00 178 10.50 267 H362AWA F7 16.50 419 9.00 229 7.00 178 10.50 267 H362AWC F7 16.50 419 9.00 229 7.00 178 10.50 267 H362AWH F6 16.50 419 9.00 229 7.00 178 10.50 267 H362AWK, A F6 16.50 419 9.00 229 7.00 178 10.50 267 H362DS F6 16.87 428 8.92 227 6.97 177 10.81 275 H W D Typical NEMA 4X Fiberglass Reinforced Polyester and Krydon® H W/H D W Typical NEMA 4, 4X, 5, 12, 12K (Stainless has flat front) H WD Typical NEMA 7, 9 H362DSWA F7 16.87 428 8.92 227 5.11 130 10.81 275H362DSWC F7 16.87 428 8.92 227 5.11 130 10.79 274H362DF F1 16.50 419 11.00 279 8.80 224 11.00 279H362DX F1 19.40 493 11.40 290 8.60 218 11.40 290 H362SS F6 16.87 428 8.92 227 6.97 177 10.81 275H363AWA F7 20.50 521 9.00 229 7.00 178 10.50 267H363AWC F7 20.50 521 9.00 229 7.00 178 10.50 267H363AWK, A F6 20.50 521 9.00 229 7.00 178 10.50 267 H363DS F6 20.82 529 9.36 238 6.97 177 11.25 286H363DSWA F7 20.82 529 9.36 238 6.97 177 11.25 286H363DSWC F7 20.82 529 9.36 238 6.97 177 11.25 286H363DF F1 24.80 630 13.70 348 12.00 305 13.70 348H363DX F1 25.25 641 11.40 290 8.60 218 11.40 290 H363SS F6 20.82 529 9.36 238 6.97 177 11.25 286H364A,AWK F6 29.00 737 17.25 438 8.75 216 18.63 473H364DS,NDS F6 29.00 737 17.75 451 8.88 226 19.25 489H364NA,NAWK F6 29.00 737 17.25 438 8.75 216 18.63 473H364DF E1 31.30 795 26.30 668 11.80 300 26.30 668 H364SS F6 29.00 737 17.75 451 8.88 226 19.25 489H365AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667H365NAWK, NDS E4 46.25 1175 26.25 667 10.13 259 26.25 667H366AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667H366NAWK, NDS E4 46.25 1175 26.25 667 10.13 259 26.25 667 H367AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930H368AWK, NAWK E4 69.13 1756 36.62 930 17.75 451 36.62 930H461AWK F6 20.50 521 14.75 375 6.80 173 16.13 410H461DS F6 20.82 529 15.08 383 6.97 177 16.85 428H462AWK F6 20.50 521 14.75 375 6.80 173 16.13 410 H462DS F6 20.82 529 15.08 383 6.97 177 16.85 428H463AWK F6 20.50 521 14.75 375 6.80 173 16.13 410H463 DS F6 20.82 529 15.08 383 6.97 177 16.85 428H464AWK F6 29.00 737 23.25 591 8.75 222 24.88 632H464DS F6 29.00 737 23.75 603 8.88 226 25.25 641 H465AWK E4 46.25 1175 32.50 826 10.13 259 32.50 826H663AWK F6 20.50 521 14.75 375 6.80 173 16.13 410H663DS F6 20.82 529 15.08 383 6.97 177 16.85 428H664AWK F6 29.00 737 23.25 591 8.75 222 24.88 632H664DS F6 29.00 737 23.75 603 8.88 226 25.25 641 HU265AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667HU266AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667HU267AWK E4 69.13 1756 36.62 930 17.75 451 36.62 930HU268AWK E4 69.13 1756 36.62 930 17.75 451 36.62 930HU361AWA F7 16.50 419 9.00 229 7.00 178 10.50 267 HU361AWC F7 16.50 419 9.00 229 7.00 178 10.50 267HU361AWK, A F6 14.60 371 6.63 168 4.96 125 7.55 192HU361DS F6 14.93 379 7.22 183 5.11 130 8.67 220HU361DSWA F7 16.87 428 8.92 227 5.11 130 10.81 275HU361DSWC F7 16.87 428 8.92 227 5.11 130 10.79 274 HU361DF F1 16.50 419 11.00 279 8.80 224 11.00 279HU361DX F1 19.40 493 11.40 290 8.60 218 11.40 290HU361SS F6 14.93 379 7.22 183 5.11 130 8.67 220HU362AWA F7 16.50 419 9.00 229 7.00 178 10.50 267HU362AWC F7 16.50 419 9.00 229 7.00 178 10.50 267 HU362AWH F6 16.50 419 9.00 229 7.00 178 10.50 267HU362AWK, A F6 16.50 419 9.00 229 7.00 178 10.50 267HU362DS F6 16.87 428 8.92 227 6.97 177 10.81 275HU362DSWA F7 16.87 428 8.92 227 5.11 130 10.81 275HU362DSWC F7 16.87 428 8.92 227 5.11 130 10.79 274 HU362DF F1 16.50 419 11.00 279 8.80 224 11.00 279HU362DX F1 19.40 493 11.40 290 8.60 218 11.40 290HU362SS F6 16.87 428 8.92 227 6.97 177 10.81 275HU363AWA F7 20.50 521 9.00 229 7.00 178 10.50 267HU363AWC F7 20.50 521 9.00 229 7.00 178 10.50 267 HU363AWK, A F6 20.50 521 9.00 229 7.00 178 10.50 267HU363DS F6 20.82 529 9.36 238 6.97 177 11.25 286HU363DSWA F7 20.82 529 9.36 238 6.97 177 11.25 286HU363DSWC F7 20.82 529 9.36 238 6.97 177 11.25 286HU363DF F1 24.80 630 13.70 348 12.00 305 13.70 348 HU363DX F1 25.25 641 11.40 290 8.60 218 11.40 290HU363SS F6 20.82 529 9.36 238 6.97 177 11.25 286HU364A,AWK F6 29.00 737 17.25 438 8.75 216 18.63 473HU364DF E1 31.30 795 26.30 668 11.80 300 26.30 668HU364DS F6 29.00 737 17.75 451 8.88 226 19.25 489 HU364SS F6 29.00 737 17.75 451 8.88 226 19.25 489HU365AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667HU366AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667HU367AWK E4 69.13 1756 36.62 930 17.75 451 36.62 930HU368AWK E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU461AWK E1 16.63 422 9.88 251 6.13 156 11.00 279HU461DS F6 20.82 529 15.08 383 6.97 177 16.85 428HU462AWK F6 20.50 521 14.75 375 6.80 173 16.13 410HU462DS F6 20.82 529 15.08 383 6.97 177 16.85 428HU463AWK F6 20.50 521 14.75 375 6.80 173 16.13 410 HU463DS F6 20.82 529 15.08 383 6.97 177 16.85 428HU464AWK F6 29.00 737 23.25 591 8.75 222 24.88 632HU464DS F6 29.00 737 23.75 603 8.88 226 25.25 641HU465AWK E4 46.25 1175 32.50 826 10.13 259 32.50 826HU661AWK F6 20.50 521 14.75 375 6.80 173 16.13 410 HU661DS F6 20.82 529 15.08 383 6.97 177 16.85 428HU662AWK F6 20.50 521 14.75 375 6.80 173 16.13 410HU662DS F6 20.82 529 15.08 383 6.97 177 16.85 428HU663AWK F6 20.50 521 14.75 375 6.80 173 16.13 410HU663DS F6 20.82 529 15.08 383 6.97 177 16.85 428 HU664AWK F6 29.00 737 23.25 591 8.75 222 24.88 632HU664DS F6 29.00 737 23.75 603 8.88 226 25.25 641 Cat. No. Approximate Dimensions Series HWDW/H in. mm in. mm in. mm in. mm www.schneider-electric.us 3 S A F E T Y S W I T C H E S 3-14 © 2007 Schneider Electric All Rights Reserved Double Throw Safety Switches—Fusible and Non-Fusible Class 3140 30–100 A Types DT, DTU (Series F) 30 (Series T4), 200–600 A Types 82,000 and 200 A DTU (Series E, A) Field-Installable Accessories: —Neutral —Electrical Interlock —Grounding Terminals •Fusible (DT) and non-fusible (DTU) switches available. •Manually operated switch suitable for use in accordance with article 702 of the NEC, ANSI/NFPA 70 •Standards: U:L 98, NEMA KS1, CSA, and NOM •Modular design—switch handle, lock-plate, switch mechanism; line and load bases are field replaceable •UL Listed short circuit current ratings up to 200 kA (using Class R, J, or T fuses—see table for rating) •Load make/break rated •Meets NEMA hp ratings •Dual cover interlock •May be padlocked ON (I) or OFF (O) •Lock-off accepts up to three padlocks •Side-opening door •Quick make / quick break mechanism •Meets NEMA requirements as heavy duty switch •Field-installable electrical interlock kits •Field-installable neutral assembly kits (2P and 3P switches) •UL Listed as suitable for use as service equipment •Supplied as standard for switching one load between two power sources, and may be field-converted to switch on power source between two loads. •Non-fusible •Designed for manual transfer of loads from one supply to another •UL Listed switches are suitable for use in accordance with Arcticle 702 of the National Electrical Code, ANSI / NFPA 70. •All 82,000 and DTU double throw switches are continuous dute rated for their nameplate ampere rating •The 82,000 and DTU (Series E, A) switches are load make/break rated •UL Listed as suitable for use as service equipment •Horsepower rated only as footnoted. 30–100 A DT, DTU (Series F) NEMA 1 DTU (Series E) 200 A NEMA 3R 82,000 Line NEMA 1 92251 www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-15 Double Throw Safety Switches 240 Volt Class 3140 600 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-16 Application Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-17 Dimensions: 30–100 A (Series F) . . . . . . . . . . . . . . . . . . . . . . . . . page 3-18 Dimensions: 30, 200–600 A (Series E, T4, A) . . . . . . . . . . . . . . . page 3-19 Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-20 System Rating(A)Current Series NEMA 1 NEMA 3R NEMA 4,4X,5304 Stainless Steel NEMA 12Gasketed Horsepower Ratingsab 240 Vac 250 VdccStd. Max. Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 1Ø 3Ø 1Ø 3Ø Table 3.37: Fusible—2P, 240 Vac—250 Vdc 100 F DT223 1586.00 DT223RB 2037.00 ——— —7.515d15 30 d 20 3P, 240 Vac—250 Vdc 30 F DT321 1097.00 DT321RB 1477.00 ————1.5 e 3d 3 e 7.5d 5 60 F DT322 1313.00 DT322RB 1741.00 ————3 e 7.5d 10 e 15 d 10 100 F DT323 2069.00 DT323RB 2483.00 ——— —7.5 e 15d 15 e 30d 20 Table 3.38: Non-Fusible—2P, 240 Vac—250 Vdc 60 F DTU222 641.00 ————————10—10 f 100 F DTU223 914.00 DTU223RB 898.00 ——— ———15—20 f 30 T4 92251 g 390.00 ——————————— 200 E 82254 1210.00 DTU224NRBgh 1451.00 ——H82254 3114.00 15 — — — — —— — — — — — — — —15———— 400 A 82255 g 3900.00 82255R g 5810.00 ——H82255g 6890.00 ———— — 3P, 240 Vac—250 Vdc 30 F DTU321 536.00 ———————3 d 5 e 10 d 5 f 60 F DTU322 746.00 ————————10 e 15 d 10 f 100 F DTU323 1176.00 DTU323RB 1302.00 ——— ———15 e 30 d 20 f 30 T4 92351 g 458.00 ——————————— 200 E 82354 g 1709.00 DTU324NRB gh 2003.00 ——H82354 gi 3605.00 —15—— — 200 E DTU324N gh 1865.00 ———————15——— 400 A 82355 g 5360.00 82355R g 8692.00 ——H82355 g 7810.00 ———— — 600 A DTU326 8370.00 DTU326R 9260.00 — — — — — 125 — — 50 4P, 240 Vac 30 T4 92451 g 635.00 ——————————— 200 E 82454k 3456.00 82454Rk 5011.00 ——H82454j 4519.00 —15j —— — 400 A 82455 7670.00 82455R 10800.00 ——H82455 10650.00 ———— — 600 A DTU426 13570.00 DTU426R 13730.00 — — — — — 125 — — 50 a Refer to page 7-31 for additional motor application data. The starting current of motors or more than standard horsepower may require the use of fuses with appropriate time delay characteristics. b Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses. c For switching dc, use two switching poles. d If used on corner grounded delta systems, install neutral and use outer switching pole for ungrounded conductors. e Use outer switching poles. f Maximum rating. g 240 Vac only h Neutral included with device. i Suitable for use as service equipment. j Hp rating applies only to H82454. k 250 V dc rated. Line Line Load Line Line Load Line Line Load Line Line Load DE1 Discount Schedule www.schneider-electric.us 3 S A F E T Y S W I T C H E S 3-16 © 2007 Schneider Electric All Rights Reserved Double Throw Safety Switches 600 V Class 3140 240 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-15 Application Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-17 Dimensions: 30–100 A (Series F) . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-18 Dimensions: 30, 200–600 A (Series E, T4, A) . . . . . . . . . . . . . . . . page 3-19 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-20 Table 3.39: 600 V Double Throw Safety Switches System Rating(A)Current Series NEMA 1 NEMA 3R NEMA 4,4X,5304 Stainless Steel NEMA 12Gasketed Horsepower Ratingsao 240 Vac 480 Vac 600 Vac Vdcb std max std max std max 250 600Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price 3Ø 3Ø 3Ø b 3Øb 3Ø 3Ø Fusible 3P, 600 Vac—600 Vdc 30 F DT361 1344.00 DT361RB 1785.00 —— — ———5157.520515 60 F DT362 1407.00 DT362RB 2090.00 — — — — — — 15 30 15 50 — 30 100 F DT363 2457.00 DT363RB 2951.00 — — — — — — 25 60 30 75 — 50 Non-Fusible 3P, 600 Vac—600 Vdc 1Ø d 3Ø b 1Ø d 3Ø b 1Ø d 3Ø 30 F DTU361 586.00 DTU361RB 1029.00 — — — — 5 10 7.5 20 10 30 5 15 60 F DTU362 836.00 DTU362RB 1363.00 DTU362DS 4204.00 DTU362AWK p 2423.00 10 20e 25 50 g 30 60 g 10 30 100 F DTU363 1357.00 DTU363RB 2283.00 DTU363DS 6276.00 DTU363AWK p 2596.00 20 40h 40 75 hi 40 75 h 20 50 200 E 82344j 1855.00 82344RBj 3912.00 82344DSjr 7610.00 H82344ljq 5002.00 ———15 k ———— 400 A 82345n 5475.00 82345R m 8760.00 82345DS m 10450.00 H82345n 8070.00 ———————— 600 A DTU366 n 9260.00 DTU366R n 13200.00 ——DTU366AWKn14450.00 —125— 250 —35050— Non-Fusible 4P, 600 Vac—600 Vdc 2Ø 3Ø 2Ø 3Ø 2Ø 3Ø 60 F DTU462 2023.00 Use NEMA 12 —DTU462DS 4455.00 DTU462AWK p 2789.00 20 20 40 50 50 60 10 30 100 F DTU463 2567.00 —DTU463DS 6652.00 DTU463AWK p 4082.00 30 40 50 75 50 75 20 30 200 E 82444 n 4095.00 82444R n 5420.00 82444DS n 10070.00 H82444lj 4762.00 ———————— 400 A 82445 m 8385.00 82445Rm 11200.00 ——H82445m 11230.00 ———————— 600 A DTU466 n 13570.00 DTU466R n 15650.00 — — — — —125— 250 —35050— Non-Fusible 6P, 600 Vac—600 Vdc 1Ø 3Ø 1Ø 3Ø 1Ø 3Ø 60 F — — — — — —DTU662AWK p 5649.00 —20— 50 —601030 100 F — — — — — —DTU663AWK p 8490.00 —40— 75 —752050 a Refer to page 7-31 for additional motor application data. The starting current of motors or more than standard horsepower may require the use of fuses with appropriate time delay characteristics. b If used on corner grounded delta systems, install neutral and use outer switching pole for ungrounded conductors. c For switching dc, use two switching poles. d Use outer switching poles. e Maximum Hp is 15 for corner grounded delta systems. f Maximum Hp is 30 for corner grounded delta systems. g Use 75oC #4 Cu or #2 Al conductors only. h Use 75oC #1 Cu conductors only. i Maximum Hp is 60 for corner grounded delta systems. j 480 Vac maximum only, 250Vdc. k Standard Hp rating. l Not suitable for use as service equipment. m 600 Vac max. n 250 V dc rated. o Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses. (Non-fusible switches have max rating unless noted.) p Complete rating on switch is NEMA 3R or 12. For 3R applications, remove drain screw from bottom endwall. q H82 ... and H92 ... devices are NEMA 12 only, intended for use indoors only. r Not UL Listed. Line Line Load Line Line Load Line Line Load Line Line Load DE1 Discount Schedule Modified4/16/09 www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-17 Double Throw Safety Switches Application Data Class 3140 a Rating applies to AC only. The UL Listed short circuit current rating for non-fusible switches is based on the switch being used in conjunction with the corresponding fuse type. Evaluation of non-fusible switches in conjunction with molded case circuit breakers has not been performed. b The DTU361 and DTU361RB are also suitable for use on a circuit capable of delivering not more than (A) 18 kA, 600 Vac maximum when protected by Type FH circuit breaker rated 30 A maximum or (B) 14 kA, 600 Vac maximum when protected by Type FA circuit breaker rated 30 A maximum. c Any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used ahead of a non-fused safety switch when there is up to 10 kA short circuit current available. d 400 A 82,000 switch is only 10 kA. e Thomas and Betts catalog numbers. f Versa-Crimp® catalog numbers. g 200–600 A switches suitable for 75oC conductors. h 30 A switches suitable for 60oC or 75oC conductors. i Versa-Crimp® catalog numbers. 240 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-15 600 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-16 Dimensions: 30–100 A (Series F) . . . . . . . . . . . . . . . . . . . . . . . . . page 3-18 Dimensions: 30, 200–600 A (Series E, T4, A). . . . . . . . . . . . . . . . .page 3-19 Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-20 Situations Requiring Fuses 30–100 A Type DT (Series F): Select DT switches from pages 3-15, 3-16, which have provisions for accepting fuses. 30, 200–600 A Type 82,000 (Series E, T4, A), all DTU devices: Use the non-fusible double throw switches from pages 3-15, 3-16 in conjunction with standard fused devices, and install them according to the diagram 1 or 2. Non-Fusible D/T Switch Line Line Load Fusible Single Throw Switch or Circuit Breaker Diagram 1 Non-Fusible D/T Switch Line Line Fusible Single Throw Switch or Circuit Breaker FusibleSingleThrow Switch or Circuit Breaker Load Diagram 2 Table 3.40: UL Listed Short Circuit Current Ratings Switch Type Ampere Rating VoltageRating UL ListedFuse Class Short Circuit Current Rating a(A) Type DT(Series F) 30–100 A 240 V or600 V H, K 10,000 R, J 200,000 Type DTU b(Series F)30–100 A 240 V or600 V H or K 10,000 c R, J or T 200,000 DTU224NRB andDTU324NRB(Series E)200 A 240 V H, K 10,000 c DTU324N(Series E)200 A 240 V H, K 10,000 c R, J 100,000 Type 82,000 all 240 V H, K 10,000 c R, J 100,000 d 600 V H, K 10,000 c Type DTU (A series)600 A 240 V or 600 V H, K 10,000 R, J, T 100,000 Table 3.41: Terminal Lug Data for Type DT, DTU (Series F) Double Throw Safety Switches Switch WiresperPhase NEMA 1, 3R, 4, 4X, 12 Optional Copper Only LugWire RangeWire Bending Space Per NEC Table 373-6AWG/kcmil Standard LugWire RangeAWG/kcmil OptionalCompression LugField-Installable 30–60 A Type DT, DTU (Series F)1 12–2 Alor 14–2 Cu 12–2 Alor 14–2 Cu C10-14, D8-14, or E6-14 e See pages 3-11 and 3-13 for appropriate kit.Order 2 kits per switch.100 AType DT, DTU (Series F)1 12–1/0 Alor 14–1/0 Cu 12–1/0 Alor 14–1/0 Cu VCEL02114S1 f Table 3.42: Terminal Lug Data for Types 82,000 and for A and E-Series DTU devices g Switch WiresperPhase Wire RangeWire Bending SpacePer NEC Table 373-6AWG/kcmil Lug Wire RangeAWG/kcmil OptionalCompression LugsField-Installable 30 A (Series T4) h 1 14–8 Al/Cu 12–2 Alor 14–2 Cu — 200 1 6–300 Al/Cu 6–300 Al/Cu VCEL030516H1 i 400 1or2 1/0–600 Al/Cuor 1/0–300 Al/Cu 1/0–600 Al/Cu — 600 2 250–500 Al/Cu 250–500 Al/Cu — DE1 Discount Schedule www.schneider-electric.us 3 S A F E T Y S W I T C H E S 3-18 © 2007 Schneider Electric All Rights Reserved Double Throw Safety Switches Dimensions—Series F Devices Class 3140 240 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-15 600 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-16 Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-17 Dimensions: 30, 200–600 A (Series E, T4, A) . . . . . . . . . . . . . . . . page 3-19 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-20 Table 3.43: 30–100 A Type DT, DTU (Series F)—Approximate Dimensions Cat. No.Series HWW/HD in. mm in. mm in. mm in. mm DT223 F5 38.00 965 9.88 251 11.13 283 6.75 171 DT223RB F5 38.00 965 6.87 174 8.12 206 6.60 168 DT321 F5 38.00 965 10.25 260 11.50 292 6.75 171 DT321RB F5 38.00 965 10.25 260 11.80 300 6.60 168 DT322 F5 38.00 965 10.25 260 11.50 292 6.75 171 DT322RB F5 38.00 965 10.25 260 11.80 300 6.60 168 DT323 F5 38.00 965 9.88 251 11.13 283 6.75 171 DT323RB F5 38.00 965 6.87 174 8.12 206 6.60 168 DT361 F5 38.00 965 10.25 260 11.50 292 6.75 171 DT361RB F5 38.00 965 10.25 260 11.80 300 6.60 168 DT362 F5 38.00 965 10.25 260 11.50 292 6.75 171 DT362RB F5 38.00 965 10.25 260 11.80 300 6.60 168 DT363 F5 38.00 965 9.88 251 11.13 283 6.75 171 DT363RB F5 38.00 965 6.87 174 8.12 206 6.60 168 DTU222 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU223 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU223RB F5 30.50 775 10.25 260 11.96 304 6.93 176 DTU321 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU322 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU323 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU323RB F5 30.50 775 10.25 260 11.96 304 6.93 176 DTU361 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU361RB F5 30.50 775 10.25 260 11.96 304 6.93 176 DTU362 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU362AWK F6 29.94 760 10.25 260 11.96 304 6.93 176 DTU362DS F6 30.26 769 10.25 260 11.50 292 7.12 181 DTU362RB F5 30.50 775 10.25 260 11.96 304 6.93 176 DTU363 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU363AWK F6 29.94 760 10.25 260 11.96 304 6.93 176 DTU363DS F6 30.26 769 10.25 260 11.50 292 7.12 181 DTU363RB F5 30.50 775 10.25 260 11.96 304 6.93 176 DTU462 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU462AWK F6 30.26 769 15.50 394 16.75 425 7.12 181 DTU462DS F6 30.26 769 15.50 394 16.75 425 7.12 181 DTU463 F5 29.94 760 10.25 260 11.96 304 6.93 176 DTU463AWK F6 30.26 769 15.50 394 16.75 425 7.12 181 DTU463DS F6 30.26 769 15.50 394 16.75 425 7.12 181 DTU662AWK F6 30.26 769 15.50 394 16.75 425 7.12 181 DTU663AWK F6 30.26 769 15.50 394 16.75 425 7.12 181 W W/H D H NEMA 1 W W/H D H NEMA 4, 4X, 5 and 12 W W/H D H NEMA 3R www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-19 Double Throw Safety Switches Dimensions—Series E, T4 Devices Class 3140 240 V Double Throw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-15 600 V Double Throw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-16 Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-17 Dimensions: 30–100 A (Series F) . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-18 Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-20 Table 3.44: 30, 200–600 A Types 82,000 and E-Series DTU devices, NEMA 1 and 3R—Approximate Dimensions Cat. No. Series HWW/HD in. mm in. mm in. mm in. mm DTU224NRB E1 32.50 826 20.63 524 24.00 610 10.63 270 82254 E1 30.88 784 15.75 400 19.63 499 9.75 248 82254NW E1 30.88 784 20.00 508 23.88 607 11.75 298 82344 E2 30.88 784 20.00 508 23.88 607 11.75 298 82344RB E1 32.50 826 20.63 524 24.00 610 10.63 270 82354 E1 30.88 784 20.00 508 23.88 607 11.75 298 92251 T4 10.00 254 8.00 203 9.75 248 4.75 121 82344DS E1 30.88 784 20.00 508 23.88 607 11.75 298 DTU324N E1 32.50 826 24.50 622 26.25 667 10.63 270 DTU324NRB E1 32.50 826 24.50 622 26.25 667 10.63 270 H82344 E2 32.50 826 24.50 622 26.25 667 10.63 270 H82444 E2 32.50 826 30.21 767 33.61 854 10.63 270 H82454 E3 32.50 826 30.21 767 33.61 854 10.63 270 82454 E3 38.00 965 29.62 753 33.02 839 10.63 270 82444 E3 38.00 965 29.62 753 33.02 839 10.63 270 82454R E3 38.00 965 29.62 753 33.02 839 10.63 270 82444R E3 38.00 965 29.62 753 33.02 839 10.63 270 H82254 E3 32.50 826 24.50 622 26.25 667 10.63 270 H82354 E3 32.50 826 24.50 622 26.25 667 10.63 270 82444DS E3 38.00 965 29.62 753 33.02 839 10.63 270 82255 A1 38.50 978 26.10 663 29.51 750 10.63 270 82255R A1 39.00 991 26.62 676 30.02 763 10.63 270 82345 A1 38.50 978 26.10 663 29.51 750 10.63 270 82345DS A1 39.00 991 26.62 676 30.02 763 10.63 270 82345R A1 39.00 991 26.62 676 30.02 763 10.63 270 82355 A1 38.50 978 26.10 663 29.51 750 10.63 270 82355R A1 39.00 991 26.62 676 30.02 763 10.63 270 82445 A1 38.50 978 30.10 765 33.50 851 10.63 270 82445R A1 39.00 991 30.21 767 33.61 854 10.63 270 82455 A1 38.50 978 30.10 765 33.50 851 10.63 270 82455R A1 39.00 991 30.21 767 33.61 854 10.63 270 H82255 A1 39.00 991 26.62 676 30.02 763 10.63 270 H82345 A1 39.00 991 26.62 676 30.02 763 10.63 270 H82355 A1 39.00 991 26.62 676 30.02 763 10.63 270 H82445 A1 39.00 991 30.21 767 33.61 854 10.63 270 H82455 A1 39.00 991 30.21 767 33.61 854 10.63 270 DTU326 A1 63.31 1608 23.66 601 24.46 621 8.88 226 DTU426 A1 63.31 1608 27.00 686 27.80 706 8.88 226 DTU366 A1 63.31 1608 23.66 601 24.46 621 8.88 226 DTU466 A1 63.31 1608 27.00 686 27.80 706 8.88 226 DTU326R A1 63.76 1619 23.66 601 24.46 621 8.88 226 DTU426R A1 63.76 1619 27.00 686 27.80 706 8.88 226 DTU366R A1 63.76 1619 23.66 601 24.46 621 8.88 226 DTU466R A1 63.76 1619 27.00 686 27.80 706 8.88 226 DTU366AWK A1 63.76 1619 23.66 601 24.46 621 8.88 226 W W/H D H NEMA 1 W H D W/H DTU—200 A NEMA 3R 3-20 © 2007 Schneider Electric All Rights Reserved www.schneider-electric.us 3 S A F E T Y S W I T C H E S Double Throw Safety Switch Accessories Class 3140 a For Type 82,000 switches, neutral is available factory-installed on 2P and 3P double throw switches. Not UL Listed. To order, add suffix N to the standard catalog number and add the above price to the list price of the switch. For DTU switches, neutral is factory-installed in standard device and is UL Listed. b Neutral assembly catalog number DT200N can be added to 4P Type 82000 switches in the field. c Electrical interlock kit catalog numbers with “1” suffix indicate one normally open and normally closed contact; “2” indicates two normally open and two normally closed contacts. See page 3-9 for electrical interlock ratings. d 30–100 A Type DT, DTU (Series F) switches contain (2) separate switching mechanisms. Each mechanism will accept an electrical interlock. Some applications may therefore require (2) electrical interlocks. e 30–100A Type DT, DTU (Series F) switches with factory-installed electrical interlocks installed are UL Listed and interlocks are furnished with 2 N.O. /2 N.C. contacts installed in both “ON” positions. To order, add suffix EI to standard catalog number. f Electrical interlock EK400DTU2 can be added to 4-pole Type 82000 switches in the field. g Type 82000 and DTU switches are available with electrical interlock factory-installed only. Not UL listed. Electrical interlocks are furnished with 2 N.O./N.C. contacts and are installed in both “ON” positions. To order, add suffix EI to standard switch catalog number. Key Interlock Systems For factory-installed key interlocks, refer to page 3-11. Phenolic Legend Plate For factory-installed phenolic legend plates, refer to page 3-10. Lock-On Provisions—UL Listed 30–100 A type DT, DTU (Series F) and type 92,000 included on standard device. Type 82,000 and 200 A DTU (Series E) available factory-installed. Add SPLO to catalog number and add $273. to list price. 240 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-15 600 V Double Throw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-16 Application Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-17 Dimensions: 30–100 A (Series F) . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-18 Dimensions: 30, 200–600 A (Series E, T4, A) . . . . . . . . . . . . . . . . page 3-19 Table 3.45: Neutral Assembly Switch Field-InstalledStandard Neutral KitCat. No. TerminalDataAWG/kcmil $ Price Field-InstalledCopper onlyNeutral Kit Cat. No. TerminalDataAWG/kcmil $ Price 30–100 A Type DT, DTU (Series F) (2- and 3-pole switches only)SN0310 14–1/0 Al/Cu 76.00 SN0310C 14–1/0 Cu 80.00 30 A (Series T4) (2- and 3-pole switches only)aa605.00 ——— 200 A Type 82000 and DTU (Series E) baa740.00 ——— 400 A Type 82000 DT400N (1) 4–600kcmil or(2) 1/0–250kcmil 70.00 ——— 600 A Type DTU (Series A)DT600NKD 250–500kcmil 301.00 ——— Table 3.46: Electrical Interlocks Switch Field-Installed Electrical Interlock Kit Cat. No. c $ Price Factory-Installed$ Price Adder Per Switch 30–100 A Type DT, DTU (Series F) EIK1, EIK2 d 207.00 603.00e 200 A Type 82000 and DTU (Series E) fg—742.00e 400 A Type 82000 EK400DTU2 173.00 — 600 A Type DTU (Series A)DS200EK2D 292.00 — Table 3.47: Service Grounding Kit (Required for service equipment use.) Switch Field-Installed Service Grounding Lug Kit Cat. No.Terminal DataAWG/kcmil $ Price 30–100 A Type DT, DTU (Series F) Included Included std. 30 A Type 92,000 DT30SG (4) 14–4 Cu/Al 19.60 200 A Type 82000 and DTU (Series E)DT100SG (3) 14–1/0 Cu/Al 20.00 400 A Type 82000 PKOGTA2(2 required)(4) 10–2/0 Cu or(4) 6–2/0 Al 36.80 600 A Type 82000 (Series A)DS468GKD 6–250kcmil 206.00 Table 3.48: Class R Fuse Kits When installed, this kit rejects all but Class R fuses. Kits are available for field installation. For factory installation, add “CLR” suffix to catalog number. Switch Series Number Class R Fuse Kit Cat. No. $ Price Factory-Installed $ Price Class R Fuse Kits—240 V (two kits per 3P switch) 30 A F5 RFK03 16.30 260.00 60 A F5 RFK06 17.00 260.00 100 A F5 RFK10 31.80 260.00 Class R Fuse Kits—600 V (two kits per 3P switch) 30 A F5 RFK06 17.00 260.00 60 A F5 RFK06H 17.00 260.00 100 A F5 RFK10 31.80 260.00 Table 3.49: Rainproof Bolt-On Hubs—For Use On NEMA 3R Enclosures Conduit Size 3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4 Closing Cap Hub Cat. No.B075 B100 B125 B150 B200 B250 B300 B350 B400 BCAP $ Price Eachh 22.20 22.20 22.20 22.20 40.90 68.00 124.00 200.00 245.00 2.50 Note: NEMA 3R rainproof enclosures with catalog number ending in RB have a bolt-on closing cap factory-installed. Order bolt-on hubs separately from table above. For more details see page 1-13. Hubs through size 2-1/2 in. can be directly installed on RB devices. Devices requiring 3 in. or larger hubs must have holes cut in the field. Gaskets are provided on 3 in. and larger hubs. Note: All hubs are UL Listed for indoor and rainproof applications and suitable for use with conduit having ANSI standard taper pipe thread. h See Discount Schedule. Table 3.50: Watertight Hubs—For Use On NEMA 4, 4X and 5 Stainless Steel and NEMA 12 Enclosures Conduit Trade Size 1/23/4 11-1/41-1/222-1/233-1/24 Standard-Zinc Hub Cat. No.H050 H075 H100 H125 H150 H200 H250 H300 H350 H400 Zinc $ Price Each 20.70 30.00 31.40 36.00 55.00 80.00 92.00 118.00 188.00 254.00 Chrome Plated Hub Cat. No.H050CP H075CP H100CP H125CP H150CP H200CP ———— Chrome Plated $ Price Each 27.10 37.60 42.90 44.60 64.00 91.00 ———— “RB Hub” DE1 DE1A Discount Schedule Modified4/16/09 www.schneider-electric.us 3 SA F E T Y S W I T C H E S © 2007 Schneider Electric All Rights Reserved 3-21 Heavy Duty Safety Switches MD50 Motor Disconnect Switches Class 3110 The MD50 Motor Disconnect Switch’s IEC309-2 pin and sleeve technology merged with a durable mechanical interlock features provide safe, quick and reliable mating of mobile and fixed motors to power connections. The mechanical interlock prevents the making or breaking under load of plug connected equipment. The plug must be inserted before the power can be turned “ON”. The plug can not be removed until the power is turned “OFF”. Grounding and conduit Hub included. NOTE:Auxiliary Contact’s ordering information; 20 and 30 Amps non-fused, ME2030AUX 60 A and 100 Amps non-fused, ME80AUX, ME20 a UL98 Listed. NOTE:Auxiliary Contact’s ordering information; 30 Amps fused, ME30FDAUX 60 Amps fused, ME60FDAUX Type J Fuses Table 3.51: Non-Fusible System Amperes Voltage NEMA 4X and 12 Use With Plug Horse PowerRating Phase Wire SizeCat No. $ Price Cat. No. $ Price 2-Pole 3-Wires 30 125 MD330MI4 823.86 ME330P4W 142.79 2 1 12–8 250 MD330MI6 832.86 ME330P6W 142.79 5 1 12–8 60 250 MD360MI6 1091.69 ME360P6W 234.71 10 1 6–2 3-Pole 4-Wires 20 250 MD420MI9 787.50 ME420P9W 108.17 7.5 3 12–8 480 MD420MI7 787.50 ME420P7W 108.17 15 3 12–8 30 250 MD430MI9 762.14 ME430P9W 157.21 10 3 12–8 480 MD430MI7 762.14 ME430P7W 157.21 20 3 12–8 600 MD430MI5 889.97 ME430P5W 157.21 20 3 12–8 60 250 MD460MI9 1040.45 ME460P9W 229.33 20 3 6–2 480 MD460MI7 1040.45 ME460P7W 229.33 40 3 6–2 600 MD460MI5 1307.06 ME460P5W 229.33 50 3 6–2 100 125/250 MD4100MI12 1181.88 ME4100P12 310.10 125 V 5, 250 V 15 1 6–1/0 240 MD4100MI9 1415.05 ME4100P9 310.10 25 3 6–1/0 480 MD4100MI7 1273.79 ME4100P7 310.10 50 3 6–1/0 600 MD4100MI5 1415.05 ME4100P5 310.10 50 3 6–1/0 4-Pole 5-Wires 30 Y120/208 MD530MI9 821.85 ME530P9W 194.71 7.5 3 12–8 Y277/480 MD530MI7 887.59 ME530P7W 194.71 20 3 12–8 Y347/600 MD530MI5 887.59 ME530P5W 194.71 20 3 12–8 60 Y120/208 MD560MI9 1084.91 ME560P9W 272.60 20 3 6–2 Y277/480 MD560MI7 1139.16 ME560P7W 272.60 40 3 6–2 Y347/600 MD560MI5 1301.90 ME560P5W 272.60 50 3 6–2 100 Y120/208 MD5100MI9 1415.05 ME5100P9 373.56 25 3 6–1/0 Y277/480 MD5100MI7 1415.05 ME5100P7 373.56 50 3 6–1/0 Y347/600 MD5100MI5 1415.05 ME5100P5 373.56 50 3 6–1/0 Table 3.52: Fusiblea System Amperes Voltage NEMA 4X and 12 Use With Plug Horse Power Rating Horse Power Rating Max. Phase Wire SizeCat. No. $ Price Cat. No. $ Price 3-Pole 4-Wires 30 250 MD430MIF9 1087.54 ME430P9W 157.21 37.5318–8 480 MD430MIF7 1368.77 ME430P7W 157.21 5 15 3 18–8 600 MD430MIF5 1196.12 ME430P5W 157.21 7.5 20 3 18–8 60 250 MD460MIF9 1342.07 ME460P9W 229.33 7.5 15 3 14–4 480 MD460MIF7 1419.09 ME460P7W 229.33 15 30 3 14–4 600 MD460MIF5 1415.05 ME460P5W 229.33 15 30 3 14–4 DE1 Discount Schedule Modified4/16/09 3-22 © 2007 Schneider Electric All Rights Reserved www.schneider-electric.us 3 S A F E T Y S W I T C H E S MANUFACTURER SPEC SHEET - RAIL MANUFACTURER SPEC SHEET - RAIL MANUFACTURER SPEC SHEET - RAIL MANUFACTURER SPEC SHEET - RAIL