HomeMy WebLinkAboutINSPECTION SUMMARY - 13-00526 - Season's II Medical OfficePermit
Inspection
Summary
Permit Status of (Expired) as of Report Date: 02/20/2018 12:38 pm
Permit Details Permit Number: 13-00526
Season's II Medical Office
36 South Professional Plaza
Building - Commercial
Permit Issued Date: 06/23/2014
Permit Inspection Statistics
46Total Inspections Completed:
35Total Inspections Passed:
Inspection Pass Rate
76.09%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
05/21/2014PassTed DyeFooting Inspection
05/30/2014PassTed DyeFoundation Inspection
Inspection for pour from grid lines 3 through 6 and A through J
All rebar looked good.
Inspector Comments:
06/10/2014PassQuinton OwensFoundation Inspection
West end of south wall & stairwell & west wall almost to parking entrance.Inspector Comments:
06/19/2014PassTed DyeFooting Inspection
07/17/2014PassQuinton OwensFoundation Inspection
Finished previous day's inspection and arrived after pour started. Remaining
footing for parking canopy appeared properly placed. Special inspector on site
said it all was good.
Inspector Comments:
07/23/2014PassQuinton OwensFoundation Inspection
Peir foundations at exterior parking. Rebar installed per plans.Inspector Comments:
07/23/2014PassQuinton OwensCommercial Footing Inspection
Footing on north side of pool location. Rebar as per plans.Inspector Comments:
09/25/2014PassQuinton OwensCommercial Framing/Structure Inspection
Concealed locations to be covered only. No rough-in work done. Not ready for full
framing inspection.
Inspector Comments:
10/22/2014PassQuinton OwensSheeting
Only South section of roof sheathing inspected.Inspector Comments:
10/29/2014PassQuinton OwensSheeting
Added missed nailing while doing inspection. All exterior sheathing ok to cover.Inspector Comments:
10/30/2014PassQuinton OwensSheeting
Middle and North section of roof sheathing inspected.Inspector Comments:
12/11/2014PassQuinton OwensCommercial Framing/Structure Inspection
Hold down inspection only.Inspector Comments:
01/06/2015FailQuinton OwensCommercial Insulation Inspection
Parking garage insulation incomplete at plumbing pipes near center of building.
Call back when plumbing passes inspection and insulation is installed.
Inspector Comments:
Page 1 of 4
(Continued)
Permit Details Permit Number: 13-00526
Season's II Medical Office
36 South Professional Plaza
Building - Commercial
Permit Status of (Expired) as of Report Date: 02/20/2018 12:38 pm
Permit
Inspection
Summary
01/16/2015PassQuinton OwensCommercial Insulation Inspection
seal 2nd level window on east side above stairs.Inspector Comments:
01/26/2015PassQuinton OwensCommercial Sheetrock/Drywall Inspection
One line of screws on one sheet missing in west bathroom upstairs, and a few
spots in west stairwell. Fasten as required.
Inspector Comments:
02/11/2015FailTed DyeCommercial Sheetrock/Drywall Inspection
02/12/2015PassQuinton OwensCommercial Insulation Inspection
Insulation in floor overhang over parking on West side. Double layer of what
seems to be R-19 batts (cannot read labeling on insulation).
Inspector Comments:
05/22/2015FailQuinton OwensCommercial Building Final
Window by west stairs is not labeled as tempered. South wall to be fire rated
from the inside (both levels). Handrail on wall at bottom of west stairs is
missing. Exterior handrails are not installed. All penetrations and perimeter of
ceiling in parking area under building must be fire rated. Fire rate framed wall on
east side parking area and penetrations above area behind wall. Exterior work
still in progress.
Inspector Comments:
07/23/2015FailQuinton OwensCommercial Building Final
Windows tempered as required (window by west stairs added "armorcoat" to
glazing).
Several penetrations not rated on ceiling of garage and orange foam is not fire
rated.
Handrails are not completed yet.
Warning sign/bar not installed at garage entry yet.
South wall on will not have to be fire rated on the inside until tenant finish is
done.
Building identification numbers installed?
Inspector Comments:
07/31/2015FailQuinton OwensCommercial Building Final
Handrails down to parking garage not completed. Waiting on fire collars needed
at plastic pipe boxed cover on west wall. Large drain pipe goes through rated
wall or place damper in ceiling fan (unless fan housing and duct is all metal) -
where is outlet.
Post address numbers (temp #'s ok), Post restrom signage (temp signs ok for
now) - also needed on tenant ADA restroom.
Inspector Comments:
08/14/2015FailQuinton OwensCommercial Building Final
Handrails down to parking garage not completed on exterior stairs.
ADA restroom signs are required (temp signs will be ok until additional tenant
spaces are finished).
Inspector Comments:
09/23/2015PassQuinton OwensCommercial Building Final
ADA restroom signs are required (temp signs will be ok until additional tenant
spaces are finished).
One hour fire rating on south wall to be done with tenant finish.
Inspector Comments:
Page 2 of 4
(Continued)
Permit Details Permit Number: 13-00526
Season's II Medical Office
36 South Professional Plaza
Building - Commercial
Permit Status of (Expired) as of Report Date: 02/20/2018 12:38 pm
Permit
Inspection
Summary
Electrical Inspection Type
12/11/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
01/20/2015PassBret StoddardCommercial Electrical Rough-in
02/10/2015PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
02/10/2015PassBret StoddardCOM & MFR Electrical Service Inspection
02/18/2015PassBret StoddardCOM & MFR Electrical Service Inspection
02/25/2015PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
02/26/2015PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
Fire Inspection Type
12/24/2014FailDale PickeringFire Sprinkler Rough-in
12/24/2014FailDale PickeringFire Sprinkler Rough-in
01/09/2015PassDale PickeringFire Sprinkler Rough-in
Heads missing on the ends of branch lines, on order, will be installed for next
rough-in inspection. DD
Inspector Comments:
02/09/2015PassDale PickeringFire Sprinkler Rough-in
Rough-in inspection for attic dry system only. DPInspector Comments:
05/05/2015PassDale PickeringFire Sprinkler Hydro
05/06/2015FailBret StoddardFire Alarm Final Inspection
05/06/2015PassDale PickeringFire Sprinkler Final Inspection
Page 3 of 4
(Continued)
Permit Details Permit Number: 13-00526
Season's II Medical Office
36 South Professional Plaza
Building - Commercial
Permit Status of (Expired) as of Report Date: 02/20/2018 12:38 pm
Permit
Inspection
Summary
Mechanical Inspection Type
12/22/2014PassDon AllenHVAC Rough-in
looked at the duct in the attic and presser test on the snow melt both look goodInspector Comments:
01/07/2015PassDon AllenGas Pressure Test
gas presser held at 60lbInspector Comments:
01/15/2015PassDon AllenHVAC Rough-in
All the duck in the ceiling lookd goodInspector Comments:
02/03/2015PassDon AllenHVAC Rough-in
looked at the duct in the hall ways they are all good to cover.Inspector Comments:
04/28/2015FailDon AllenHVAC Final Inspection
Mech. units in the hall way would not turn on. Call for reinspectInspector Comments:
05/21/2015PassDon AllenHVAC Final Inspection
the main hallways on the 1 and 2 floor are good for the c/oInspector Comments:
07/30/2015PassDon AllenHVAC Final Inspection
GOOD FOR THE C/OInspector Comments:
Plumbing Inspection Type
01/07/2015PassDon AllenPlumbing Rough-in
All the plumbing in the parking garage ceiling looks goodInspector Comments:
02/26/2015PassDon AllenPlumbing Rough-in
water line held at 100 lb. good to coverInspector Comments:
05/06/2015PassDon AllenPlumbing Final Inspection
Inspections Required
Commercial Sheetrock/Drywall Inspection
Commercial Sheetrock/Drywall Inspection
Fire Alarm Final Inspection
Page 4 of 4