HomeMy WebLinkAboutREVIEW REPORT ELECTRICAL - 17-00458 - 1334 N Yellowstone Hwy - U-Wrench Auto - New BuildingReview
Report
Current Electrical Review Status: REVISIONS
Application Number: 17-00458Permit Details
Application Received Date: 08/08/2017
Commercial Addition
Application Approved Date:
Application Approved Status: APPW/EXCP
08/08/2017
1334 N Yellowstone Hwy
U-Wrench Auto - Addition
Status of Plan Reviews Completed
08/10/2017Electrical Review REVISIONS
08/15/2017Fire Department Review - Site Plan COMPLETED
08/24/2017HVAC Review REVISIONS
08/24/2017Plumbing Review REVISIONS
08/24/2017Public Works Review - Site Plan REVISIONS
09/07/2017Building Review REVISIONS
09/15/2017Plumbing Review REVISIONS
09/15/2017HVAC Review COMPLETED
09/19/2017Electrical Review REVISIONS
09/25/2017Planning and Zoning Review - Site Plan REVISIONS
01/10/2018Public Works Review - Site Plan REVISIONS
01/10/2018Electrical Review REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Building Review
Plumbing Review
Planning and Zoning Review - Site Plan
Public Works Review - Site Plan
Electrical Review
HVAC Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Electrical: Service REVISIONSAvailable fault current calculation not included
on drawings.
*Revisions Response :
Electrical: Wiring Method REVISIONSOutlets in shop area noted to be installed at 48"
above floor. Must provide wiring method
proposed. Is this a minor or major repair garage
as it's defined by the NEC? Ventilation may be
required if considered a major repair garage.
*Revisions Response :
Electrical: Exit Signs/Emergency Lighting COMPLETED
Electrical: Wiring-General Reviewed for code compliance. Electrical wiring
is noted on plans to comply with article 511
with the NEC. Please provide notes for
electrical.
COMPLETED
Reviewed By: Bret Stoddard
Review Date: 01/10/2018
Plan Review Details
bret.stoddard@rexburg.org
Electrical Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Electrical Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Page 2 of 2
Approval of plans does not constitue approval of variance from code