HomeMy WebLinkAboutFIRE ALARM SUBMITTAL - 17-00695 - 66 E Main St - Progrexion - RemodelFire : Security : Audio : Video : Camera Systems :Networking :Automation : Access Control : PERS Progrexion Fire Alarm Submittals 66 E. Main St Rexburg, ID 83440 Jason Perron ID ELE #25206 NICET III #129957 jasonp@pinn-tech.net Cell –(208) 404-2002 Fire : Security : Audio : Video : Camera Systems :Networking :Automation : Access Control : PERS This is a remodel project of an existing small call center. The basement is protected by a fire sprinkler system but the main level is not, so the intent of this system is for notification upon fire sprinkler activation. Elevations were not provided by the architect/engineer so a site visit was performed to determine ceiling heights. All candela ratings were determined for a maximum of a 10’ceiling in the basement and a maximum of a 20’ceiling on the main level Features•10 zones, 8 Class B (Style B) and 2Class A (Style D) or Class B (StyleB) zones, expandable to 30 zones•Supervised zone expanders and I/Omodules can be mounted remotelyfrom the main control panel•Event History Buffer (150 events)with date/time stamp•All zones are compatible with 2- or4-wire detectors•8 selectable/programmable outputpatterns for notification appliancecircuits•Built-in Digital Alarm CommunicatorTransmitter (DACT)•4 Notification Appliance Circuits•4 programmable general purposerelays•Programmable smoke verification,pre-alarm delay, cross zoning andenhanced verification mode featuresthat can help minimize false alarms•Programmable from the built-incontrol panel touchpad, remoteannunciator, or Windows®SKSSdownloading software•Direct connect port for on-siteup/downloading with Windows®SKSS downloading software•Built-in walk test feature•Single or dual interlock waterreleasing capability•Plex door option combines a deadfront cabinet door with a clearwindow, limiting access to the panelwhile providing single buttonoperation of the reset and silencefunctions•Programmable AC trouble relay •Built-in synchronization forappliances from AMSECO®,Gentex®, Faraday, System Sensor®,and Wheelock®•Programmable date settings forDaylight Saving Time•Clock source setting options for 50Hz, 60 Hz, or internal (uses thepanel’s internal clock)SpecificationsOperating Voltage: 24 VDCPrimary AC: 120 Vrms @ 60Hz, 2ATotal DC Load:6 AmpCurrent Draw:Standby:140 mAAlarm:460 mAFlush Mounting Dimensions:Height:24.75” (62.9 cm)Width:14.5” (36.8 cm)Depth:3-7/16” (8.73 cm)with 5/8” protrudingOverall Dimensions:Height:26-3/8” (67 cm)Width:17-3/16” (43.66 cm)Total Depth:4” (10.16 cm)Operating Temp:32° to 120° F(0° to 49° C)Humidity:10 - 93% noncondensingOptional Accessories•SK-5235 LCD Remote Annunciator•SK-5217 10 Zone Expander(2 max. per system)•SK-5280 Status Display Module (8max. per system)•5220 Direct Connect Module•5824 Serial/Parallel Printer InterfaceModule•SKSS Downloading Software •Plex-2 Door Option•SK-SCK Seismic Compliance KitListings and Approvals•UL Listed•CSFM Listed•MEA approval 429-92-E Vol. XIII•OSHPD (CA) OSP-0065-10 Model 5208Fire Alarm Control Panel with Digital Communicator The SK-5208 is a microprocessor based control panel with built-in UL listed communicator designed forapplications requiring smoke detection, manual pull stations, and sprinkler supervision. It features an easy toread LCD display with programmable English readout and user friendly tactile keys. The basic unit offers 10zones of initiation and is expandable up to 30 zones for larger applications. The SK-5208 has a complete line ofsupervised accessories that provide remote annunciation, auxiliary control zone expansion. Ideal for new andretrofit applications, the SK-5208 delivers the performance to handle your installation. The Fire Alarm Control Designed to Grow with Your Systems Needs, Without The Growing Pains. SK-5208 FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL Model 5208Fire Alarm Control Panel with Digital Communicator Engineering Specification The system shall contain a fire alarm control panel to supervise and operate heat and smoke detection devices,manual fire alarm devices, alarm notification devices and visual annunciators. The system shall also be capableof monitoring for sprinkler supervisory and water flow conditions. The system must have a built in UL listed firecommunicator that can be enabled/disabled as needed on a per job basis. In addition, the system will soundalarms locally for purpose of evacuation. MADE IN AMERICA FORM# 350318 Rev E© 2013 Honeywell International Inc. This document is not intended to be used for installation purposes. We try tokeep our product information up-to-date and accurate. We cannot cover allspecific applications or anticipate all requirements. All specifications aresubject to change without notice. For more information, contact Silent Knight12 Clintonville Road, Northford, CT 06472-1610 Phone: (800) 328-0103,Fax: (203) 484-7118. For Technical support, Please call 800-446-6444.www.silentknight.com 24 5 1.2 Date:1/3/2018 10 Panel ID:Model:3.0 Amps Location:Volts:24 VDC 6.0 Amps Wire AWG Ohms Per Length(ft)Actual Volts @ Standby Alarm & Type 1000 Ft.One-Way Ohms EOL SK-5208 1 0.140 0.550 SK-5217 SK-5217 Zone Expdr 0.000 0.000 SK-5235 0.000 0.000 SK-5280 0.000 0.000 SK-5220 0.000 0.000 SK-7181 0.000 0.000 IDC-1 NA**0.000 NA** IDC-2 NA**0.000 NA** IDC-3 NA**0.000 NA** IDC-4 NA**0.000 NA** IDC-5 NA**0.000 NA** IDC-6 NA**0.000 NA** IDC-7 NA**0.000 NA** IDC-8 NA**0.000 NA** IDC-9 NA**0.000 NA** IDC-10 NA**0.000 NA** IDC-11 NA**0.000 NA** IDC-12 NA**0.000 NA** IDC-13 NA**0.000 NA** IDC-14 NA**0.000 NA** Circuit Name Initiating Device Ckt 5 Initiating Device Ckt 6 N/A Initiating Device Ckt 3 Initiating Device Ckt 4 %Drop SK-5280 Display Mod Current Draw Version 02.26.09 SK-5208 SK-5208 Fire Alarm Control Panel Voltage Drop Warning Threshold % : Ckt.#Qty Progrexion Project ID: Prepared By:Jason Perron SK-5208 Calculations Max NAC Current: Max Panel Current:Twin Falls, ID Standby Hours: Alarm Mins: Derating Factor: Project Name: Initiating Device Ckt 9 Initiating Device Ckt 10 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 SK-5208 Main Control SK-5235 LCD Remote SK-7181 Zn Cnvtr SK-5220 Dir Con Mod Initiating Device Ckt 7 Initiating Device Ckt 8 Initiating Device Ckt 2 Initiating Device Ckt 1 Global Project Values: Configure Circuits Print Page IDC-14 NA**0.000 NA** IDC-15 NA**0.000 NA** IDC-16 NA**0.000 NA** IDC-17 NA**0.000 NA** IDC-18 NA**0.000 NA** IDC-19 NA**0.000 NA** IDC-20 NA**0.000 NA** IDC-21 NA**0.000 NA** IDC-22 NA**0.000 NA** IDC-23 NA**0.000 NA** IDC-24 NA**0.000 NA** IDC-25 NA**0.000 NA** IDC-26 NA**0.000 NA** IDC-27 NA**0.000 NA** IDC-28 NA**0.000 NA** IDC-29 NA**0.000 NA** IDC-30 NA**0.000 NA** NAC-1 ###0.000 0.984 #14 Solid 2.52 135 0.68 19.73 3.28% NAC-2 ###0.000 0.864 #14 Solid 2.52 145 0.73 19.77 3.10% NAC-3 ###0.000 1.458 #14 Solid 2.52 275 1.39 18.38 9.91% NAC-4 ###0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% Aux ###0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 0.140 3.856 24 0.083 (5 Mins) 3.366 0.321 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 N/A Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Total Standby AH Required Notification Appl Ckt 4 Notification Appl Ckt 2 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Inactive, Add SK-5217 Multiply By The Derating Factor Notification Appl Ckt 3 Standby Time In Hours Aux Power Out 3.69Total Combined AH Required Notification Appl Ckt 1 Total Alarm Current (Amps)Total Standby Current (Amps) Inactive, Add SK-5217 Inactive, Add SK-5217 Alarm Time In Minutes / 60 Total Alarm AH Required Command Shortcuts Minimum Battery AmpHours Required 4.43 1.20 **The SK-5208 and SK-5217 limits alarm current to 95mA per zone. The SK-5208 alarm current includes 10% of system zones inalarm, but in no case less than three zones per UL 864. Global Project Values: Configure Circuits Print Page Project Name:Progrexion Prepared By:Jason Perron Ckt. Number:IDC-1 Panel ID: Ckt. Name:Initiating Device Ckt 1 Standby Alarm Standby Alarm 1 System Sensor 2W-B 0.000 0.095 0.000 0.095 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.095 Ckt. Number:IDC-2 Panel ID: Ckt. Name:Initiating Device Ckt 2 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Qty SK-5208 Qty Device Current Draw Each Current Draw Total 1/3/2018 Project ID: Date: Circuit Configuration Current Draw Each Current Draw TotalDevice SK-5208 0 Project Information Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 1 SILENT KNIGHT PULL STATION 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number:IDC-3 Panel ID: Ckt. Name:Initiating Device Ckt 3 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 1 SPRINKLER TAMPER 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Qty Device Current Draw Each Current Draw Total SK-5208 Project Information Project Name:Progrexion Prepared By:Jason Perron 1/3/2018 Project ID: Date: Circuit Configuration 0 Project Information Ckt. Number:IDC-4 Panel ID: Ckt. Name:Initiating Device Ckt 4 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 1 SPRINKLER FLOW 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number:IDC-5 Panel ID: Ckt. Name:Initiating Device Ckt 5 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Qty Device Current Draw TotalCurrent Draw Each SK-5208 Current Draw Each Current Draw Total SK-5208 Qty Device Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 1 SILENT KNIGHT PULL STATION 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number:IDC-6 Panel ID: Ckt. Name:Initiating Device Ckt 6 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Qty SK-5208 Current Draw Each Current Draw TotalDevice Project Name:Progrexion Prepared By:Jason Perron 1/3/2018 Project ID: Date: Circuit Configuration 0 Project Information Ckt. Number:IDC-7 Panel ID: Ckt. Name:Initiating Device Ckt 7 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number:IDC-8 Panel ID: Ckt. Name:Initiating Device Ckt 8 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Qty Device Qty Device Current Draw Each Current Draw Total Current Draw Each Current Draw Total SK-5208 SK-5208 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number:IDC-9 Panel ID: Ckt. Name:Initiating Device Ckt 9 Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Current Draw TotalQtyDeviceCurrent Draw Each SK-5208 Project Name:Progrexion Prepared By:Jason Perron 1/3/2018 Project ID: Date: Circuit Configuration 0 Project Information Ckt. Number:NAC-1 Panel ID: Ckt. Name:Notification Appl Ckt 1 3.0 Amps Standby Alarm Standby Alarm 3 Gentex GEC324 Horn/Strobe (15cd)0.000 0.134 0.000 0.402 2 Gentex GEC24 Horn/Strobe (30cd)0.000 0.151 0.000 0.302 1 Gentex GEC324 Horn/Strobe (110cd)0.000 0.280 0.000 0.280 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.984 Ckt. Number:NAC-2 Panel ID: Ckt. Name:Notification Appl Ckt 2 3.0 Amps Standby Alarm Standby Alarm 2 Gentex GEC324 Horn/Strobe (30cd)0.000 0.152 0.000 0.304 2 Gentex GEC324 Horn/Strobe (110cd)0.000 0.280 0.000 0.560 SK-5208 Max NAC Current: Qty Device Current Draw Each Current Draw Total SK-5208 Max NAC Current: Qty Device Current Draw Each Current Draw Total 2 Gentex GEC324 Horn/Strobe (110cd)0.000 0.280 0.000 0.560 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.864 Ckt. Number:NAC-3 Panel ID: Ckt. Name:Notification Appl Ckt 3 3.0 Amps Standby Alarm Standby Alarm 3 Gentex GEC324 Horn/Strobe (15cd)0.000 0.134 0.000 0.402 2 Gentex GEC324 Horn/Strobe (30cd)0.000 0.152 0.000 0.304 2 Gentex GEC324 Horn/Strobe (75cd)0.000 0.236 0.000 0.472 1 Gentex GEC324 Horn/Strobe (110cd)0.000 0.280 0.000 0.280 0.000 0.000 Totals 0.000 1.458 SK-5208 Max NAC Current: Qty Device Current Draw Each Current Draw Total Project Name:Progrexion Prepared By:Jason Perron 1/3/2018 Project ID: Date: Circuit Configuration 0 Project Information Ckt. Number:NAC-4 Panel ID: Ckt. Name:Notification Appl Ckt 4 3.0 Amps Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number:Aux Panel ID: Ckt. Name:Aux Power Out 1.0 Amps Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 SK-5208 Max Aux Current: Qty Device Current Draw Each Current Draw Total SK-5208 Max NAC Current: Qty Device Current Draw Each Current Draw Total Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 GCS/GCC 24VDC S E R I E S Commander4 Series Selectable Candela Evacuation Signals •• AANNSSII//UULL 446644 aanndd AANNSSII//UULL 11997711 LLiisstteedd •• FFMM AApppprroovveedd •• CCSSFFMM::77113355--00556699::112222 ((GGCCCC)) 77112255--00556699::112233 ((GGCCSS)) •• MMEEAA::228855--9911--EE Product Listings Product Compliance •• NNFFPPAA 7722 •• AAmmeerriiccaannss wwiitthh DDiissaabbiilliittiieess AAcctt ((AADDAA)) •• IIBBCC//IIFFCC//IIRRCC •• CCiittyy && SSttaattee oorrddiinnaanncceess//LLaawwss//RReegguullaattiioonnss •• QQuuaalliittyy MMaannaaggeemmeenntt SSyysstteemm iiss cceerrttiiffiieedd ttoo:: IISSOO 99000011::22000088 Applications The GCS/GCC Series is a ceiling mount strobe or horn/strobe combination that offers dependable audible and visual alarms and the lowest current consumption. The GCS/GCCoffers tamperproof field selectable candela options of 15, 30, 75, 95, 115 and 150 candela. The GCC horn offers a continuous or synchable temporal three in 2400Hz and mechanical tone. All tones are easy for the professional to change in the field by using switches. The models are shipped from the factory in the temporal three alarm mode. The GC Series has a very minimal operating current and has a minimum flash rate of 1Hz regardless of input voltage. The Commander4 Series comes standard with the 4" mounting plate which incorporates the popular Super-Slide®feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The Commander4 also features the patented Checkmate®- Instant Voltage Verification feature which allows the installer to check the voltage drop draw without removing the signal. The GC Series appliances are ANSI/UL 464 and ANSI/UL 1971 listed for use with fire protective systems and are warranted for three years from the date of purchase. Standard Features • Nominal voltage 24VDC •Tamperproof field selectable candela options of 15, 30, 75, 95,115 & 150 •Super-Slide®Bracket - Ease of Supervision Testing • Checkmate®- Instant Voltage Verification • Unit Dimensions: 6” (15.24 cm) x 2.6” (6.604 cm) •Synchronize strobe and/or horn with Gentex AVSM Control Module •Prewire entire system, install mounting bracket, then install signals • Documented lower installation and operating costs • Input Terminals 12 to 18 AWG •Switch Selection for High or Low dBA •Switch Selection for 2400Hz or Mechanical Tone •Switch Selection for Continuous or Temporal 3 •Tamperproof re-entrant grill • Surface mount with the GCSB (Gentex Ceiling Surface Mount Box) • Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions) •Faceplate available in red or off-white Patents •• 77,,337755,,661177 MMaayy 2200,, 22000088 MMooddeell NNuummbbeerr PPaarrtt NNuummbbeerr NNoommiinnaall VVoollttaaggee CCaannddeellaa GCS24CR 904-1213-002 24VDC 15, 30, 75, 95, 115, 150 GCS24CW 904-1215-002 24VDC 15, 30, 75, 95, 115, 150 GCS24PCR 904-1214-002 24VDC 15, 30, 75, 95, 115, 150 GCS24PCW 904-1216-002 24VDC 15, 30, 75, 95, 115, 150 MMooddeell NNuummbbeerr PPaarrtt NNuummbbeerr NNoommiinnaall VVoollttaaggee CCaannddeellaa RReevveerrbbeerraanntt ddBBAA @@ 1100fftt.. ppeerr AANNSSII//UULL 446644 IInn AAnneecchhooiicc RRoooomm ddBBAA @@ 1100fftt.. GCC24CR 904-1209-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCC24PCR 904-1210-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCC24CW 904-1211-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCC24PCW 904-1212-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCS Series 24 Volt Ceiling Mount Selectable Strobe GCC Series 24 Volt Ceiling Mount Selectable Horn/Strobe HHoorrnn MMooddee MMiinniimmuumm ddBBAA @@ 1100fftt.. ppeerr AANNSSII//UULL 446644 ((HHIIGGHH)) MMiinniimmuumm ddBBAA @@ 1100fftt.. ppeerr AANNSSII//UULL 446644 ((LLOOWW)) RReegguullaatteedd 2244VVDDCC MMaaxx.. OOppeerraattiinngg @@ HHiigghh SSeettttiinngg ((mmAA)) Temp 3 2400Hz 83 75 23 Temp 3 Mechanical 81 73*22 Continuous 2400Hz 86 78 23 Continuous Mechanical 84 76 22 Candela 15cd 30cd 75cd 95cd 115cd 150cd 2244VVDDCC ((1166--3333 VVoollttss))2244VVDDCC 7722mmAA 110011mmAA 116677mmAA 220000mmAA 221144mmAA 228866mmAA UL Max1 120mA 120mA 200mA 220mA 290mA 321mA NOTES: •Operating temperature: 32°to 120°F (0° to 49°C). The GC Series is not listed for outdoor use. •The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. •For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual. •Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe products (see Technical Bulletin Number 014). *Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). 11 RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual. MMooddeell DDeessiiggnnaattiioonnss:: C = Ceiling Mount R = Red Faceplate W = White Faceplate All units are available in plain (no lettering). PPllaaiinn uunniittss aarree nnoonn--rreettuurrnnaabbllee.. GC24 Product Strobe Current Ratings (mA) GCC24 Product Horn Decibel and Current Ratings (mA) Mounting Super-Slide® 1. SLIDE ONTO BRACKET 2. INSERT LOCKING SCREW Checkmate®Instant Voltage Verification Switch positions 1 and 2 in the down position to select isolated horn and strobe power inputs. Switch 3 selects between temporal or non-temporal tone. Up is temporal. Switch 4 selects between mechanical or high frequency tone. Up is mechanical. Switch 5 selects between high or low dBA. Up is high dBA. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. NOTICE:CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES. 3. SNAP COVER OVER ASSEMBLY Switch Locations GCS/GCC 24VDC S E R I E S 551-0051-06 24 units per carton 29 pounds per carton Important Notice: These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. Architect & Engineering Specifications The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSI/UL 1971 for the GCS and ANSI/UL 464 for the GCC. The notification appliance shall also be listed with the California State Fire Marshal (CSFM) and the Bureau of Standards and Appeals (NYC). The notification appliance (combination audible/visible units and audible units only) shall produce a peak sound output of 90dBA or greater as measured at 24VDC in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The appliance shall have an operating current of 72mA or less at 24VDC for the 15 candela strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. NOTES: •All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. See Technical Bulletin 014 for additional information. •FFOORR SSYYNNCCHHRROONNIIZZAATTIIOONN WWIIRRIINNGG IINNFFOORRMMAATTIIOONN,, RREEFFEERREENNCCEE AAVVSSMM CCOONNTTRROOLL MMOODDUULLEE DDAATTAA SSHHEEEETT ((555511--00003311)) AANNDD//OORR AAVVSSMM CCOONNTTRROOLL MMOODDUULLEE MMAANNUUAALL ((555500--00228844)) FFOORR SSYYNNCCHHRROONNIIZZAATTIIOONN MMOODDUULLEE WWIIRRIINNGG DDIIAAGGRRAAMMSS.. AAVVSSMM CCOONNTTRROOLL MMOODDUULLEE DDAATTAA SSHHEEEETT AANNDD MMAANNUUAALL CCAANN BBEE OOBBTTAAIINNEEDD AATT hhttttpp::////wwwwww..ggeenntteexx..ccoomm OORR CCAALLLL GGEENNTTEEXX CCOORRPPOORRAATTIIOONN AATT 11--880000--443366--88339911.. Conventional GC Series Wiring Diagrams OperationThe single-action pull-station isactivated by a single pull-down ofthe alarm handle. The dual-actionversions require pushing in thehandle, then pulling the handledown for activation. The PS-DA/PS-SA manual pull stations areULlisted and meet the ADArequirement of a 5-lbs. maximumpull force to activate. Operatinginstructions are molded into thehandle along with Braille text.Molded terminal numbers can befound adjacent to the wiring termi-nals.Models:PS-SA–Single action with ‘pigtail’connections and a key lock reset.Pigtail wires are provided for con-nection to the Fire Alarm ControlPanel’s (FACP) initiation circuit.PS-DA –Dual action model withscrew terminal connections and akey lock reset.PS-DAH –Same as PS-DA exceptwith hex lock reset. PS-DALOB –Same as PS-DA with“outdoor use” listing. Includes SB-I/O backbox and sealing gasket.PS-DASP –Same as PS-DAexcept with both English andSpanish operating instructions. Features:•UL Listed• CSFM Listed• Meets ADA requirements• Operating instructions are mold-ed into the handle along withBraille text.• Made of durable Lexan• Available in Spanish• Key resettable• Easy to Install and operate• Single or dual action•Surface mount box available Specification:Dimensions:Height: 5-1/2” (13.97 cm)Width: 4” (10.16 cm)Depth:1-7/16” (3.65 cm)Operatingtemperature:32°F to 120°F(0°C to 49°C)Electrical:Switch ContactRating: 0.25 A @ 30 VAC or VDCAccessories:SB-I/O Surface Mount Back-boxBG-TR Trim Ring PS-DA and PS-SAConventional Pull-stations The PS-DA/PS-SA Pull Stations are non-coded manual pull stations which provide a Fire Alarm Control Panel(FACP) with a single alarm initiating input signal. The PS-DA/PS-SA pull stations includes both single-action anddual-action models equipped with key lock / reset. It was designed to meet multiple applications with the installerand end-user in mind. Its innovative design, durable construction, and multiple mounting options make the PS-DA and PS-SA simple to install, maintain, and operate. Easy to Install and Operate PS-DA PS-DASP CONVENTIONAL FIRE CONTROL PANEL ACCESSORY CONVENTIONAL FIRE CONTROL PANEL ACCESSORY PS-DA and PS-SAConventional Pull-Stations Engineering Specification Manual Fire Alarm Stations shall be non-code, with a key-operated reset lock in order that they may be tested,and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of akey. An operated station shall automatically condition itself so as to be visually detected as activated. Manualstations shall be constructed of red colored LEXAN® (or polycarbonate equivalent) with clearly visible operatinginstructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00inches (25.4 mm) or larger.* Stations shall be suitable for surface mounting on matching back-box SB-10; orsemi-flush mounting on a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box, and shallbe installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local require-ments. Manual Stations shall be Underwriters Laboratories listed.*NOTE:The words “FIRE/FUEGO” on the PS-DASP shall appear on the front of the station in white letters,approximately 3/4" high. PS-SA Front View PS-DA Front View PS-SA Rear View PS-DA Rear View MADE IN AMERICA P/N 350241 Rev.D©2011 Honeywell International Inc. This document is not intended to be used for installation purposes. We try tokeep our product information up-to-date and accurate. We cannot cover allspecific applications or anticipate all requirements. All specifications are sub-ject to change without notice. For more information, contact Silent Knight 12Clintonville Road Northford, CT 06472-1610 Phone: (800) 328-0103, Fax: (203) 484-7118. www.silentknight.com Agency Listings Photoelectric Smoke Detectors System Sensor i3™ series smoke detectors represent significant advancement in conventional detection. The i3 family is founded on three principles: installation ease, intelligence, and instant inspection. Features Plug-in detector line, mounting base included• Large wire entry port• In-line terminals with SEMS screws• Mounts to octagonal and single-gang back boxes, 4-square back • boxes, or direct to ceiling Stop-Drop ’N Lock attachment to base• Removable detector cover and chamber• Built-in remote maintenance signaling• Drift compensation and smoothing algorithms• Simplified sensitivity measurement • Wide-angle, dual-color LED indication• Loop testing via EZ Walk feature• Built-in test switch• Installation ease. The i3 line redefines installation ease with its plug-in design. This allows an installer to pre-wire bases (included with heads). The large wire entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods as well as direct mounting with drywall anchors. To complete the installation, i3 heads plug into the base with a simple Stop-Drop ’N Lock™ action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i3 line to minimize nuisance alarms. 2-wire i3 detectors can generate a remote LED- indicated maintenance signal when connected to the 2W-MOD2 loop test/maintenance module or a panel equipped with the i3 protocol. The SENS-RDR, a wireless device, displays the sensitivityof i3 detectors in terms of percent-per-foot obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector’s condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on 2-wire i3 detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector. 2093290-01-E7272-1653:1523011446S911 3180932 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2009 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet.A05-0318-007 • 6/09 • #2169 Ordering Information Model Thermal Wiring Alarm Current 2W-B No 2-wire 130 mA max. limited by control panel 2WT-B Yes 2-wire 130 mA max. limited by control panel 4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24 V 4WT-B Yes 4-wire 20 mA @ 12 V, 23 mA @ 24 V Accessories 2W-MOD2 2-wire loop test / maintenance module RT Removal / replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter Smoke Detector Specifications Architectural/Engineering Specifications Smoke detector shall be a System Sensor i3 Series model number_______, listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F (57.2°C). The detector shall include a mounting base for mounting to 3½-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box. The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dual- color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24 V non-polarized Minimum: 8.5 V Maximum: 35 V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2-wire: 50 µA maximum average; 4-wire: 50 µA maximum average Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @ 24 V Peak Standby Current 2-wire: 100 µA; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30 V AC/DC Physical Specifications Dimensions (including base)5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz (178 g) Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT-B and 4WT-B: 32°F to 100°F (0°C to 37.8°C) Operating Humidity Range 0 to 95% RH non-condensing Thermal Sensor 135°F (57.2°C) fixed Freeze Trouble 2WT-B and 4WT-B only: 41°F (5°C) Sensitivity 2.5%/ft nominal Input Terminals 14 to 22 AWG Mounting 3½-inch octagonal back box 4-inch octagonal back box Single-gang back box 4-inch square back box with a plaster ring Direct mount to ceiling LED Modes Power-Up Sequence for LED Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby)Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Code-compliant standard or mercantile metal models (right and left, respectively) . • Sole Path Cellular and Dual Path Cellular &/or IP Models • Choice of plans (varies by model) - check-ins from 200 seconds, to 5-minutes to 1 hour, Verizon or AT&T • Patented Signal Boost™ signal amplification circuit and high-gain performance antenna for longer range and reliability nationwide • Money-saving 2G Tradeup incentive credit • Bonus: Full High-Speed Napco Panel remote uploading/ downloading • COMPLIANCES: NFPA72 Editions: 2013, 2010, 2007; UL 864, 9th Ed., UL1610, UL985, UL1023, NYFD (as back-up); CSFM Commercial Fire Alarm Communicators: Sole & Dual Path Cellular &/or IP Napco StarLink3 Universal Fire Alarm Communicators UL and NFPA 72 Fire Code-Compliant, the StarLink Series Wireless Commercial Fire Alarm Sole Path & Dual Path Communicators provide universal support for any brand 12V to 24V fire alarm control panel, reporting in Contact ID and 4/2. With broadest coverage footprint available in Verizon Network Certified ™ CDMA or GSM 3/4G models on the AT&T network, as well as mercantile models, all provide the most economical solution and for easy, versatile installation. Safeguard Accounts & Reliability. For applications currently relying upon quickly-disappearing traditional phone lines, StarLink wireless communicators can be used for primary or backup communications, and will not only safeguard the fire alarm reporting transmissions for the future, but provide the end-user monthly savings for each costly FACP-dedicated landline they replace. And, for upgrading older wireless fire alarm communicators on 2G and other phased-out cellular networks, all StarLink Fire radios, offer a $100 tradeup incentive to help defray the cost of the hardware replacement to the advanced state-of- the-art StarLink model of choice. Flexible Performance & Reporting Options. StarLink Fire provides full data reporting, in sole and dual path, as a primary or backup, to any central station of your choice, without requiring any special equipment on premises. Ultra-affordable plans are available to meet various codes and requirements, with supervisory check-ins from 200 seconds, to 5-minutes, to an hour. The units are very easily activated, plans and options are selected, and 24/7 account management is provided all through www. napcocomnet.com. And, StarLink Fire Communicators are easily connected to any panel or Fire Alarm Control Panel (FACP) standardly operating between 12V and 24V. Flexible in any application, StarLink Fire also comes in standard, or Mercantile Models in metal housings, with code- compliant supervision, with or without using conduit; and choice of power options, powered by the panel or using its own 120V Power Supply. • Universal full event sole path cellular & dual path cellular &/or IP commercial fire alarm reporting from any panel brand, virtually anywhere • For use as primary or backup communications on all 12V-24V control panels and FACPs that communicate using Contact ID and 4/2 (such as on legacy panels) • Reports to any Central Station nationwide, with your choice of cellular networks: Verizon Network Certified CDMA or GSM 3/4G on AT&T • Easy, flexible installation, activation & online account management • Cost-saving models and plans for any code requirement. Substantial savings over monthly dedicated landline charges. And, $100 saving incentive with any 2G Communicator upgrade (unlimited). COMMERCIAL FIRE StarLink Fire Specifications STANDARD MODELS: • Durable ABS plastic housing includes three keyhole slots for mounting (for commercial application, aligns with triple gang boxes.) • Dimensions: 5-3/8”x 7-7/8”x 1-7/8” (HxWxD) • Weight: 13.5 oz • 3 LED Indicators - Green, Signal Strength; Amber- Busy/ Activation; Red-Trouble • Patented Signal Boost™ signal amplification circuit and high- gain performance antenna • Operating Environment: 0 to 49º C (32-120ºF), up to 93% humidity (non-condensing) • 12V - 24V Universal FACP Support, auto-current sensing. Support all brands communicating in Contact ID and 4/2 • Powered by Panel, Low current draw, 71mA standby, 200mA transmit MERCANTILE MODELS (similar to above, with): • Locking Metal Enclosure with Hinged door & 2 key-slots for wall mounting (LED indicators, inside). • Dimensions: 9-5/8”x 11-3/4” x 3-3/8”D (HxWxD) • Weight: 8 lbs (max., power supply models) • Electrical Ratings for 120VAC, 60Hz • For Models with Power Supply: • Input Voltage:  120VAC Nominal • Input Current: 400mA maximum • Maximum Charging Current:  200mA • Electrical Ratings for +12V • For Models without Power Supply: • Input Voltage:  11-15VDC (power-limited output from listed control panel) • Input Current: 71mA with peak RF transmission current of 200mA. • Electrical Ratings for the IN 1 Burg/Fire Input: • Input Voltage: 9-15VDC • Maximum Input Current: Up to 2mA from FACP NAC circuit • Electrical Ratings for IN 2 and IN 3: • Maximum Loop Voltage: 15VDC • Maximum Loop Current:  1.2mA • Electrical Ratings for 3 PGM Outputs: • Open Collector Outputs:  Maximum voltage 3V when active; 15V maximum when not active • Maximum PGM Sink Current: 50mA mount. • Operating Environment 0 to 49º C (32-120ºF), up to 93% humidity (non-condensing) • 12V - 24V Universal FACP Support, auto-current sensing. Support all brands communicating in Contact ID and 4/2. Ordering Information COMMERCIAL FIRE SOLE PATH CELLULAR & DUAL PATH CELLULAR &/OR IP (“I” MODELS):* SLE-CDMA-FIRE Standard ABS (Red) Fire Sole Path Alarm Communicator, Cellular CDMA, Verizon-Network Certified SLE-CDMAI-FIRE as above, Dual Path Alarm Communicator, Cellular &/or IP (primary or backup, selectable) SLECDMA-CFB-PS Commercial Fire Mercantile model in red metal housing, CDMA, Verizon-Network Certified. Direct 120VAC Powered (w/ provisions for backup battery/charger). Or, Optional TRF20 plug-in transformer may be used, where codes permit SLECDMA-CFB Commercial Fire Mercantile model in red metal housing on CDMA, Verizon-Network Certified Powered directly from control panel Note: Substitute prefix “SLE3/4G-” on any models above for AT&T 3/4G Network ACCESSORIES: SLE-DLEXT Optional, as above, for downloading, extends distance to Napco panel up to 100’ TRF20 Optional Plug in AC Transformer, 16.5V / 20VA (use is subject to local code compliance) SLE-DLCBL Optional High-Speed Napco Panel Up/download cable 333 Bayview Ave., Amityville, NY 11701 USA 1-800-645-9445 • Fax: 1-631-789-9292 www.napcosecurity.com COMPLIANCES: NFPA 72 Editions: 2013, 2010, 2007; UL 864, 9th Ed., UL1610, UL985, UL1023; NYFD (as back-up); CSFM *StarLink Fire are also rated to support Intrusion/Burglary alarm reports where applicable. StarLink™ and Signal Boost are trademarks of NAPCO. Pats. Pending. Specifications subject to change. ©NAPCO, NAPCO Security Technologies Inc. (NASDAQ:NSSC) A676D 2016.5 * Verizon and Verizon Network Certified, UL, AT&T and other trademarks, are trademarks of their respective companies, and are unaffiliated with NAPCO. SLE-GSM-3/4G Standard Burglary Radio (Black), GSM 3/4G on AT&T Network powered by panel. SLE-CDMA as above, but CDMA communications, Verizon-Network Certified. SLECDMA-CB Commercial Burglary CDMA Radio, Verizon Certified, in white metal housing. Powered directly from control panel. SLE3/4G-CB as above, but GSM 3/4G on AT&T Network. SLE3/4G-CB-TF Commercial Burglary CDMA, Verizon Certified in white metal housing with power supply powered by plug-in 16.5V / 20VA transformer & provision for battery. Also Available: StarLink Intrusion Radios in standard and mercantile versions