HomeMy WebLinkAboutFIRE ALARM PLANS - 17-00695 - 66 E Main St - Progrexion - RemodelS F F A C P FT F NOTES:1.CANDELA SETTINGS OFHORN/STROBE AND STROBE DEVICES SHALL ADHERE TO 2013 NFPA-72 18.5.5.4 FOR ADEQUATE INTENSITY2. STROBES AND HORN/STROBES IN HALLWAYS SHALL BE LOCATED NO MORE THAN 15' FROM THE BEGINNING/END OF A HALLWAY ANDBE SPACED NO MORE THAN 100' FROM EACH OTHER3. ALL HORN/STROBES SHALL BE PLACED ON HIGH VOLUME SETTING UNLESS NOTED OTHERWISE4. VERIFY THAT VERIZON CELLULAR COVERAGE IS ADEQUATE AT FACP LOCATION. IF IT IS NOT WIRE 18 AWG 4 COND FROM FACP TOLOCATION WHERE VERISON CELLULAR SERVICE IS ADEQUATE5. DUCT SMOKE DETECTORS WITH AUTOMATIC UNIT SHUTDOWN SHALL BE INSTALLED IN ANY UNIT, OR AGGREGATE OF UNITS THATSUPPLY AIR TO THE SAME AREA, FOR A TOTAL AMOUNT OF AIR FLOW EQUAL TO OR EXCEEDING 2000 CFM. COORDINATE WITH HVACCONTRACTOR FOR CLARIFICATION6. ALL CIRCUITS ARE CLASSIFIED AS CLASS B WITH A SURVIVABILITY LEVEL OF 1. FPL IS ACCEPTABLE WHERE PERMITTED BY NFPA-70AND ABOVE 10' AFF. ALL WIRING BELOW 10' AFF SHALL BE IN CONDUIT OR CONCEALED7. ALL WIRING IS NOTED WITH HASH MARKS TO INDICATE THE NUMBER OF CONDUCTORS REQUIRED F A C P Z O N E 1 A N N A P U S D F A C P F H M M F S T F I R E A L A R M C O N T R O L P A N E L R E M O T E A N N U N C I A T O R N A C P O W E R S U P P L Y F I R E A L A R M B E L L D U C T S M O K E D E T E C T O R S M O K E D E T E C T O R H O R N S T R O B E R E L A Y M O D U L E M A N U A L P U L L S T A T I O N S P R I N K L E R T A M P E R H E A T D E T E C T O R M A G N E T I C D O O R H O L D E R M O N I T O R M O D U L E S P R I N K L E R F L O W 2 - # 1 8 A L L Z O N E S 3 - # 1 2 1 2 0 V A C N A C 1 2 - # 1 4 ( A L L N A C S ) S I L E N T K N I G H T 5 2 0 8 L E G E N D O F S Y M B O L S O N E L I N E D R A W I N G S P R I N K L E R F L O W S P R I N K L E R T A M P E R F S R 4 . 7 K E O L N A C 2 4 . 7 K E O L N A C 3 4 . 7 K E O L 4 . 7 K E O L Z O N E 2 4 . 7 K E O L Z O N E 3 4 . 7 K E O L Z O N E 4 4 . 7 K E O L Z O N E 5 4 . 7 K E O L F PINNACLE TECHNOLOGIES FIRE ALARM M A T R I X GENERAL CAUSEEFFECTSOUND GENERALBUILDING ALARM NOTIFY FIREDEPARTMENT INITIATESUPERVISORYSIGNAL TOMAINTENANCE DISPLAY EVENTON FACP DISPLAY D I S P L A Y E V E N T O N R E M O T E A N N U N C I A T O R D I S P L A Y MANUAL PULL STATIONXXX X SMOKE DETECTORXXX X HAT DETECTORXXX X SPRINKLER WATERFLOWXXX X SPRINKLER TAMPERXX X A/C POWER LOSSXX X LOSS OF BATTERYINTEGRITYXX X GROUND FAULTXX X OPEN NAC CIRCUITXX X OPEN INITIATING CIRCUITXX X