HomeMy WebLinkAboutCOMCHECK - 17-00719 - 407 S 3rd E - Addition�( COMcheck Software Version 4.3.5.2
Envelope Compliance Certificate
Project Information
Energy Code: 2012 IECC
Project Title:
Location: Rexburg, Idaho
Climate Zone: 61b
Project Type: Addition
Vertical Glazing / Wall Area: 9%
Construction Site: Owner/Agent: Designer/Contractor:
407 5 3rd E Sephlin Hepworth
Rexburg, Idaho 83440 407 S 3rd E
Rexburg, Idaho 83440
208-757-8888
sephlinhepworth@aol.com
Building Area Floor Area
1 -Kitchen / Dining Area (Dining: family) : Residential 780
Envelope Assemblies
Assembly
Gross Area
Cavity
Cont.
Proposed
Budget U -
or
R -Value
R -Value
U -Factor
Facton.,i
Perimeter
Roof: Attic Roof, Wood Joists, [Bldg. Use 1 - Kitchen / Dining Area]
784
49.0
49.0
0.010
0.021
Ext. Wall: Wood -Framed, 161n. o.c., [Bldg. Use 1 - Kitchen / Dining
784
14.0
14.0
0.037
0.051
Area]
Window: Vinyl Frame: Operable, Pert. Type: Energy code default,
64
--
---
0.550
0.430
Double Pane with Low -E, Tinted , SHGC 0.60, [Bldg. Use 1 - Kitchen /
Dining Area]
Door: , Pert. Type: Energy code default, Double Pane with Low -E, Clear
36
---
---
0.550
0.770
, SHGC 0.70, [Bldg. Use 1 - Kitchen / Dining Area]
Basement: Solid Concrete, lon. Thickness, Normal Density, Furring:
620
25.0
25.0
0.023
0.108
Wood, Wall Ht 8.0, Depth B.G. 4.0, [Bldg. Use 1 - Kitchen / Dining Area]
Floor: Concrete Floor (over unconditioned space), [Bldg. Use 1 -
77
---
0.0
0.322
0.057
Kitchen / Dining Area]
Floor: Wood -Framed, [Bldg. Use 1 - Kitchen / Dining Area]
77
14.0
14.0
0.033
0.033
(a) Budget U -factors are used for software baseline calculations ONLY, and are not code requirements.
Project Title: Reportdate: 11/17/17
Data filename: Page 1 of 14
Dae PASSES: Desian 14% better than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.3.5.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature
Project Title: Report date: 11/17/17
Data filename: Page 2 of 14
�( COMcheck Software Version 4.3.5.2
Interior Lighting Compliance Certificate
Project Information
Energy Code: 2012 IECC
Project Title:
Project Type: Addition
Construction Site: Owner/Agent: Designer/Contractor:
407 S 3rd E Sephlin Hepworth
Rexburg, Idaho 83440 407 S 3rd E
Rexburg, Idaho 83440
208-757-8888
sephlinhepworth@aol.com
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Wafts / ft2
1 -Kitchen Dining Area (Common Space Types:Family dining area) 780 1.40 1092
Total Allowed Watts = 1092
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
1 -Kitchen Dining Area (Common Space Tyoes:Family dining area)
LED: LED Panel Unit 19W: 1 10 35 350
Linear Fluorescent: 36" T12 30W: Electronic: 2 4 35 140
Total Proposed Watts = 490
Interior Lighting Compliance Statement
Compliance Statement., The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2012 ECC requirements in COMcheck Version 4.3.5.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Project Title: Report date: 11/17/17
Data filename: Page 3 of 14
n�(
COMcheck Software Version 4.3.5.2
Exterior Lighting Compliance Certificate
Project Information
Energy Code:
Project Title:
Project Type:
Exterior Lighting Zone
Construction Site:
407 S 3rd E
Rexburg, Idaho 83440
Allowed Exterior Lighting Power
A
Area/Surface Category
20121ECC
Addition
2 (Residentially zoned area)
Owner/Agent:
Sephlin Hepworth
407 S 3rd E
Rexburg, Idaho 83440
208-757-8888
sephlinhepworth@aol.com
B
Quantity
Designer/Contractor:
C D E
Allowed Tradable Allowed Watts
Watts / Wattage (B X C)
Total Tradable Watts (a) = 40
Total Allowed Watts = 40
Total Allowed Supplemental Watts (b) = 600
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non -tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
Other door (not main entry) (2 ft of door width), Tradable Wattage
HID: Ceramic Metal Halide: Standard:
2 2 35 70
Total Tradable Proposed Watts = 70
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.3.5.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Project Title: Report date: 11/17/17
Data filename: Page 4 of 14
�( COMcheck Software Version 4.3.5.2
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
407 5 3rd E
Rexburg, Idaho 83440
Mechanical Systems List
Quantity System Type & Description
Mechanical Compliance Statement
2012 IECC
Rexburg, Idaho
6b
Addition
Owner/Agent:
Sephlin Hepworth
407S3rd E
Rexburg, Idaho 83440
208-757-8888
sephlinhepworth@aol.com
Designer/Contractor:
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.3.5.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Project Title: Report date: 11/17/17
Data filename: Page 5 of 14
COMcheck Software Version 4.3.5.2
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Plan Review
Complies?
Comments/Assumptions
& Re .ID
0103.2
;Plans and/or specifications provide all❑Complies',
[PR1)1
linformation with which compliance
❑Does Not
can be determined for the building
[]Not Observable
lenvelope and document where
I exceptions to the standard are
❑Not Applicable
j claimed.
C103.2
;Plans, specifications, and/or
❑complies
(PR4]1
calculations provide all information
[-]Does Not
:with which compliance can be
;determined for the interior lighting
❑Not Observable
:and electrical systems and equipment
❑Not Applicable
:and document where exceptions to',
;the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
-.
control devices.
C103.2
Tlans, specifications, and/or
❑Complies
[PR8]1
calculations provide all information
❑Does Not
jwith which compliance can be
determined for the exterior lighting
_❑Not Observable
; and electrical systems and equipment
:❑Not Applicable
;and document where exceptions to
;the standard are claimed. Information
;provided should include exterior
-
:lighting power calculations, wattage of
:bulbs and ballasts, transformers and
-control devices.
C402.3.1
The vertical fenestration area <= 30
❑Complies
[PR10]1
percent of the gross above -grade wall❑Does
Not,
area.
❑Not Observable;
❑Not Applicable',
C402.3.1
.The skylight area <= 3 percent of the
❑Complies
[PRll]'
gross roof area.
❑Does Not
❑Not Observable'
❑Not Applicable
C4023.2.',
Skylights in office, storage,❑Complies
2
.automotive service, manufacturing,❑Does
Not
(PR1511
non -refrigerated warehouse, retail ,❑Not
Observable
store, and distribution/sorting area
have a measured haze value > 90 '..❑Not
Applicable j
percent unless designed to exclude
direct sunlight.
-
Additional Comments/Assumptions:
Project Title:
Data filename:
1 I High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Report date: 11/17/17
Page 6 of 14
Section
#
Footing / Foundation Inspection
Complies?
Comments/Assumptions
& Re .ID
C402.2.4
!Below -grade wall insulation R -value.
❑Complies 'See the Envelope Assemblies table for values.
[1701]2
❑Does Not
❑Not Observable
❑Not Applicable
C303.2
;Below -grade wall insulation installed❑Complies
[F02]1
per manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
C403.2.8.
(Exterior Insulation protected against
❑Complies
1
damage, sunlight, moisture, wind,
❑Does Not
[F0611
;landscaping and equipment
❑Not Observable
maintenance activities.
❑Not Applicable
Additional Comments/Assumptions:
1 lHigh Impact (Tier 1) 12 IMedium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Report date: 11/17/17
Data filename: Page 7 of 14
Section
-- ----
#
Framing / Rough -In Inspection
Complies? -
Comments/Assumptions
& Re .ID
C402.4.1,
The building envelope contains a
❑Complies
C402.4.2
continuous air barrier that is sealed in
❑Does Not
[FR16]1
an approved manner and either
[:]Not Observable
constructed or tested in an approved
manner. Air barrier penetrations are
❑Not Applicable
;sealed
in an approved manner.
C402.4.3, IFactory-built
fenestration and doors
❑Complies
C402.4.4 :are
labeled as meeting air leakage
❑Does Not
[FR18]3',
requirements.
❑Not Observable
❑Not Applicable
C402.4.7 'Vestibules
are installed on all building
❑Complies
[FR17]3
entrances. Doors have self-closing
❑Does Not
devices.
❑Not Observable
"
❑Not Applicable
C402.3.3, (Vertical
fenestration U-Factor.❑Complies
See the Envelope Assemblies table for values.
04023,4
❑Does Not
[FRS]'
❑Not Observable
❑Not Applicable
C402.3.3
Vertical fenestration SHGC value.
❑Complies
See the Envelope Assemblies table for values.
[FR1011
❑Does Not
❑Not Observable
❑Not Applicable
0303.1.3 ;
Fenestration products rated in
❑Complies
[FR12]2 'accordance
with NFRC.
❑Does Not
❑Not Observable
❑Not Applicable
C303.1.3
Fenestration products are certified as
❑Complies
[FR13]1 ''to
performance labels or certificates
❑Does Not
provided. '..❑Not
Observable
-❑Not
Applicable
C402.2.7.
U -factor of opaque doors associated❑Complies
See the Envelope Assemblies table for values.
[FR14]'
with the building thermal envelope❑Does
Not
meets requirements.
[-]Not Observable.
❑Not Applicable i
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Reportdate: 11/17/17
Data filename: Page 8 of 14
# Mechanical Rough -In Inspection I Complies? I Comments/Assumptions
C402.4.5. ! Stair and elevator shaft vents have ❑Complies
1 'motorized dampers that automatically ❑Does Not
[ME3]3 close. ❑Not Observable
❑Not Applicable
C402.4.5. ;Outdoor air and exhaust systems have ❑Complies
2motorized dampers that automatically ❑Does Not
[ME58]' ,shut when not in use and meet ❑Not Observable
maximum leakage rates. Check
;gravity dampers where allowed. ❑Not Applicable
Additional Comments/Assumptions:
Project Title:
Data filename:
11 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report date: 11/17/17
Page 9 of 14
Section
--------
#
Rough -In Electrical Inspection
Compiles?
Comments/Assumptions
& Re .ID
C405.2.2.
Automatic controls to shut off all❑Complies
1
building lighting installed in all,❑Does
Not
[EL22]2
buildings.❑Not
Observable
❑Not Applicable
C405.2.1.
Independent lighting controls installed
❑Complies
1 ,per
approved lighting plans and all
❑Does Not
[EL23]2
manual controls readily accessible and
❑Not Observable;
visible to occupants.
❑Not Applicable j
C405.2.1.
Lighting controls installed to uniformly
❑Complies
2
reduce the lighting load by at least
❑Does Not
[EL15]1
50%.
❑Not Observable:
❑Not Applicable',
C405.2.2. :Daylight
zones provided with
❑Complies
3
individual controls that control the
❑Does Not
[EL16]2
lights independent of general area
❑Not Observable;
lighting.
❑Not Applicable j
C405.2.3
Sleeping units have at least one
❑Complies
[EL17]3
master switch at the main entry door
❑Does Not
that controls wired luminaires and
❑Not Observable
.switched
receptacles.
❑Not Applicable
C405.2.2. (Occupancy
sensors installed in !.❑Complies
2 (required
spaces. -.❑Does
Not
[EL1811
!❑Not
Observable
❑Not Applicable
C405.2.2.
Primary sidelighted areas are❑Complies
3
equipped with required lighting❑Does
Not
[EL20]1
controls.
'..❑Not
Observable
❑Not Applicable
C405.2.2..
Enclosed spaces with daylight area❑Complies
3
under skylights and rooftop monitors❑Does
Not
[EL21]1
are equipped with required lighting❑
Not Observable
controls.
❑Not Applicable
C405.2.4
Automatic lighting controls for exterior!❑Complies
[EL25]2
lighting installed. ..❑Does
Not
:.❑Not
Observable',
❑Not Applicable.
C405.2.3 :.Separate
lighting control devices for❑Complies
[EL4]1 'specific
uses installed per approved'❑Does
Not
lighting plans.
❑Not Observable
❑Not Applicable
C405.3
Fluorescent luminaires with odd'❑Complies
[EL19]3
numbered lamp configurations that❑Does
Not
are within 10 feet center to center (if
❑Not Observable
.
recess mounted) or are within 1 foot
edge to edge (if pendant or surface
❑Not Applicable
;mounted)
shall be tandem wired.
C405.4
Exit signs do not exceed 5 watts per
❑Complies
[EL6]1 'face.
❑Does Not
❑Not Observable:
❑Not Applicable
1 111igh Impact (Tier 1) 12-.1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Report date: 11/17/17
Data filename: Page 10 of 14
--
Section-
#
& Re .ID
Rough -In Electrical Inspection
Complies?
�--------- - ""
Comments/Assumptions
C405.6
Exterior grounds lighting over 100 W❑Complies
[EL24]1
provides >60 Im/W unless on motion
-❑Does Not.
sensor or fixture is exempt from scope
-,❑Not Observable'.
of code or from external LPD.
❑Not Applicable
C405.2.3
Additional interior lighting power❑Complies
[EL811
allowed for special functions per the
❑Does Not
approved lighting plans and is❑Not
Observable
automatically controlled and
separated from general lighting.❑Not
Applicable',
Additional Comments/Assumptions:
11 High Impact (Tier 1) '2:1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Report date: 11/17/17
Data filename: Page 11 of 14
Section---
-- __.-------..-_._ __.._-------...
#
Insulation Inspection
Complies?
Comments/Assumptions
& Re .ID
C402.4.1.
All sources of air leakage in the❑Complies
-
1
building thermal envelope are sealed,
[]Does Not
[IN111
caulked, gasketed, weather stripped
❑Not Observable;
or wrapped with moisture vapor -
❑Not
permeable wrapping material to
Applicable
minimize air leakage.
0402.4.2.
Roof R -value. For some ceiling
❑complies ;See the Envelope Assemblies table for values.
1
systems, verification may need to
.❑Does Not
[IN2]1
occur during Framing Inspection.
❑Not Observable
❑Not Applicable
C303.2
Roof insulation installed per
❑Complies
[I1\1311
manufacturer's instructions. Blown or
❑Does Not
poured loose -fill insulation is installed
❑Not Observable'
only where the roof slope is <=3 in
Applicable
12,,❑Not
C303.2
Above -grade wall insulation installed❑Complies
[IN7]1
per manufacturer's instructions.❑Does
Not
❑Not Observable
❑Not Applicable',
C402.2,5
Floor insulation R-value.❑Complies
See the Envelope Assemblies table for values.
[INB]2❑Does
Not
:❑Not
Observable'
❑Not Applicable
C303.2
Floor insulation installed per !❑Complies
[IN9]2
manufacturer's instructions..❑Does
Not
I❑Not
Observable I
❑Not Applicable j
C3031
Building envelope insulation is labeled
❑Complies
[IN10]2
with R -value or insulation certificate
❑Does Not
providing R -value and other relevant
data.
[]Not Observable
El Not Applicable',
0303.2.1 .Exterior
insulation is protected from
from
ECO
❑Complies
[IN14]' 'damage
with a protective
Not
Verification for exposed foundation'
Observable
insulation may need to occur during -❑Not
'..❑Not
Applicable
Foundation Inspection.
C402.2.1
Insulation intended to meet the roof '..❑Complies
[IN17]3 'insulation
requirements cannot be❑Does
Not
'installed
on top of a suspended
ceiling. Mark this requirement
❑Not Observable;
compliant if insulation is installed'.❑Not
Applicable
accordingly.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Report date: 11/17/17
Data filename: Page 12 of 14
Section
#Final
Inspection
Compiles?
Comments/Assumptions
& Re .ID
C402.4.6
I Weatherseals installed on all loading❑Complies
(FI37]1
dock cargo doors.
,❑Does Not
❑Not Observable',
❑Not Applicable',
C402,4.8
(Recessed luminaires in thermal
❑Complies
[FI26]3
'envelope to limit infiltration and be IC
❑Does Not
rated and labeled. Seal between
❑Not Observable
interior finish and luminaire housing.
❑Not Applicable
C408.2.5. (
Furnished as -built drawings for
❑Complies
1 !
electric power systems within 30 days
❑Does Not
[FI16]3 :of
system acceptance.
❑Not Observable
❑Not Applicable',
C303.3,
Furnished O&M instructions for
E]
C408.2.5.
systems and equipment to the.❑Does
Not
2
[FI17]3 ;representative.
building owner or designated
❑Not Observable.
❑Not Applicable
C405.5.2
Interior installed lamp and fixture
❑Complies See the Interior Lighting fixture schedule for values.
[FI18]1 :lighting
power Is consistent with what
',.❑Does Not
is shown on the approved lighting
[]Not Observable'
;plans,
:are
demonstrating proposed watts
less than or equal to allowed
❑Not Applicable
j
watts.
0405.6.2 '
Exterior lighting power is consistent❑Complies
See the Interior Lighting fixture schedule for values.
[FI19]1 :with
what is shown on the approved❑Does
Not
lighting plans, demonstrating❑Not
Observable..
1
proposed watts are less than or equal
P allowed watts.
❑Not Applicable
C408.3 :Lighting
systems have been tested to❑Complies
[F133]1 :ensure
proper calibration, adjustment,❑Does
Not
jprogramming,
and operation.
[]Not Observable:
❑Not Applicable j
C408.3 f
Lighting systems have been tested to❑Complies
[F14811
ensure proper calibration, adjustment,❑Does
Not
;programming,
and operation.
❑Not Observable ;
❑Not Applicable j
Additional Comments/Assumptions:
1 111igh Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 ILOW Impact (Tier 3)
Project Title: Report date: 11/17/17
Data filename: Page 13 of 14
Project Title: Report date: 11/17/17
Data filename: Page 14 of 14