HomeMy WebLinkAboutCOMCHECK - 17-00667-00682 - 430 W 2nd S - Providence Square #1-156 COMcheck Software Version 4.0.5.4 �( Envelope Compliance Certificate Project Information Energy Code: 2012 IECC Project Title. Providence Square - Multi -Family Location: Rexburg, Idaho Climate Zone: 6b Project Type: New Construction Vertical Glazing /Wall Area: 11%, Construction Site: Owner/Agent: Designer/Contractor: 430 W 2nd North Greg Nelson James Wyatt Rexburg, ID Sweetwater Properties NBW Archiects, P.A. PO Box 142 P.O. Box 2212 Window 2: Vinyl Frame:Operable, Pert. Specs.: Product ID Pending, Menan, ID 83434 Idaho Falls, ID 83401 0.430 208-390-3424 208.522.8779 jhw@nbwarchitects.com Building Area 0.400 Floor Area 1 -Apartments (Multifamily) : Nonresidential 3177 Additional Efficiency Package Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations Envelope Assemblies Assembly Gross Area Cavity Cont. Proposed Budget U - or R -Value R -Value U -Factor Factor(.) Perimeter Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Apartments] 3177 58.0 0.0 0.018 0.021 Basement Wall 1: Solid Concrete:8" Thickness, Normal Density, 2440 21.0 0.0 0.058 0.108 Furring: Wood, Wall Ht 8.0, Depth B.G. 5.5, [Bldg. Use 1 - Apartments] Window 2: Vinyl Frame:Operable, Pert. Specs.: Product ID Pending, 185 -- --- 0.300 0.430 SHGC 0.40, [Bldg. Use 1 - Apartments] (b) Door 2: Insulated Metal, Swinging, [Bldg. Use 1 - Apartments] 80 --- --- 0.400 0.370 Exterior Wall 1: Wood -Framed, 16" o.c., [Bldg. Use 1 - Apartments] 6600 21.0 0.0 0.062 0.051 Window 1: Vinyl Frame:Operable, Pert. Specs.: Product ID Pending, 607 --- --- 0.300 0.430 SHGC 0.40, [Bldg. Use 1 - Apartments] (b) Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Apartments] 240 --- --- 0.400 0.370 Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Apartments] (c) 305 --- --- 0.730 0.540 (a) Budget U -factors are used for software baseline calculations ONLY, and are not code requirements. (b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation. (c) Slab -On -Grade proposed and budget U -factors shown in table are F -factors. Project Title: Providence Square - Multi -Family Report date: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 1 of 9 Square ComCheck.cck Doe PASSES: Desian 1% better than node Envelope Compliance Statement Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envelope systems have been designed to meet the 2012 IECC requirements in COMcheck Version 4.0.5.4 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Project Title: Providence Square - Multi -Family Report date: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 2 of 9 Square ComCheck.cck COMcheck Software Version 4.0.5.4 Inspection Checklist Energy Code: 2012 IECC Requirements: 3.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Plan Review Complies? Comments/Assumptions & Re .ID C103.2 i Plans and/or specifications provide all ❑Complies [PR1]1 information with which compliance ❑Does Not can be determined for the building ❑Not Observable; !envelope and document where exceptions to the standard are ❑Not Applicable claimed. C406 Plans, specifications, and/or .❑Complies [PR9]1 calculations provide all information ❑Does Not .with which compliance can be -❑Not Observable determined for the additional energy []Not Applicable efficiency package options. C402.3.1 The vertical fenestration area <= 30 !❑Complies [PR10]1 percent of the gross above -grade wall ',❑Does Not area. ❑Not Observable; ❑Not Applicable C402.3.1 The skylight area <= 3 percent of the ❑Complies [PR1111 gross roof area. ❑Does Not ❑Not Observable ❑Not Applicable C402.3.2. Skylights in office, storage, ❑Complies 2 automotive service, manufacturing, ❑Does Not [PR15]1 non -refrigerated warehouse, retail' Observable', store, and distribution/sorting area :❑Not have a measured haze value > 90❑Not Applicable' percent unless designed to exclude direct sunlight. Additional Comments/Assumptions: 1 High Impact (Tier 1) 12 IMedium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Providence Square - Multi -Family Data filename: N:\Projects\Other\Providence Square Apartments Square ComCheck.cck Report date: 10/30/17 14030\40 Construction Documents\Providen Page 3 of 9 Section # Footing / Foundation Inspection Complies? Comments/Assumptions & Req.ID C402.2.4 j Below -grade wall insulation R -value. ❑Complies !See the Envelope Assemblies table for values. [FOi]2 ❑Does Not (-]Not Observable' ❑Not Applicable C303.2 (Below -grade wall insulation installed ❑Complies [FOZ]' per manufacturer's instructions. ❑Does Not ❑Not Observable ❑Not Applicable 0402.2.6 (Slab edge insulation R-value.❑Complies See the Envelope Assemblies table for values. [F03]2❑Does Not ❑Not Observable ❑Not Applicable ! C303.2 ':"Slab edge insulation installed per ❑Complies [FO4]2 - ":manufacturer's instructions. :❑Does Not []Not Observable: []Not Applicable 0402.2.6 Slab edge insulation depth/length. ❑Complies ,See the Envelope Assemblies table for values. [FOS]' Slab insulation extending away from ❑Does Not building is covered by pavement or ❑Not Observable >= 10 inches of soil. ❑Not Applicable C403.2.8. Exterior Insulation protected against ❑Complies 1 damage, sunlight, moisture, wind, ❑Does Not [FO6]1 landscaping and equipment Observable! maintenance activities.❑Not :❑Not Applicable 0402.2.8 Bottom surface of floor structures ❑Complies !.Exception: Requirement does not apply. [FO12]3 incorporating radiant heating❑Does Not insulated to >=R-3.5. See the Envelope Assemblies table for values. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 I High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) Project Title: Providence Square - Multi -Family Report date: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 4 of 9 Square ComCheck.cck Section # Framing / Rough -in Inspection Complies? Comments/Assumptions & Req.ID C402.4.1, The building envelope contains a -[]Complies C402.4.2 continuous air barrier that is sealed in❑Does Not [FR16]1 an approved manner and either []Not Observable' 'manner. constructed or tested in an approved ❑Not Air barrier penetrations are Applicable :sealed in an approved manner. C402.4.3, '..Factory -built fenestration and doors ❑Complies C402.4.4 are labeled as meeting air leakage ❑Does Not [FR18]3 requirements. ❑Not Observable []Not Applicable C402.4.7 Vestibules are installed on all building ❑Complies [FR17]3 entrances. Doors have self-closing ❑Does Not devices. ❑Not Observable ❑Not Applicable C402.3.3, Vertical fenestration U -Factor. ❑Complies See the Envelope Assemblies table for values. C402.3.4 []Does Not [FR8]1❑Not Observable ❑Not Applicable C402.3.3 Vertical fenestration SHGC value. ❑Complies .See the Envelope Assemblies table for values. [FR10]1 ❑Does Not [-]Not Observable -,,❑Not Applicable C303.1.3 Fenestration products rated in❑Complies [FR12]' "accordance with NERC. !❑Does Not ❑Not Observable ❑Not Applicable 0303.1.3 Fenestration products are certified as❑Complies [FR1311 to performance labels or certificates ❑Does Not provided. ❑Not Observable ❑Not Applicable i C402.2.7 U -factor of opaque doors associated ❑Complies ;See the Envelope Assemblies table for values. [FR14]2 with the building thermal envelope ❑Does Not', meets requirements. ❑NotObservablej ❑Not Applicable', Additional Comments/Assumptions: 111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Providence Square - Multi -Family Report date: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 5 of 9 Square ComCheck.cck # Mechanical Rough -In Inspection Complies? Comments/Assumptions & Recl.ID C402.4.5. Stair and elevator shaft vents have ❑Complies 1 motorized dampers that automatically❑Does Not [ME3]3 '.close. ❑Not Observable ❑Not Applicable C402.4.5. Outdoor air and exhaust systems have I❑Complies 2 motorized dampers that automatically❑Does Not [ME58]3 .shut when not in use and meet maximum leakage rates. Check ❑Not Observable gravity dampers where allowed. ❑Not Applicable Additional Comments/Assumptions: 11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) Project Title: Providence Square - Multi -Family Report date: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 6 of 9 Square ComCheck.cck Section # Insulation Inspection Complies? Comments/Assumptions 6 Re .ID C402.4.1. IAII sources of air leakage in the ❑Complies 1 'building thermal envelope are sealed, ❑Does Not [IN111 :caulked, gasketed, weather stripped ❑Not Observable I 'permeable or wrapped with moisture vapor - wrapping material to I❑Not Applicable minimize air leakage. C402.4.2. (Roof R -value. For some ceiling❑Complies See the Envelope Assemblies table for values. systems, verification may need to❑Does Not [IN2]1 ',occur during Framing Inspection. ❑Not Observable ❑Not Applicable C303.2 Roof insulation installed per ❑Complies [IN311 manufacturer's instructions. Blown or ❑Does Not poured loose -fill insulation is installed only where the roof slope is <=3 in ❑Not Observable 12. ❑Not Applicable C303.2 .Above -grade wall insulation installed ❑Complies [IN711 per manufacturer's instructions. "❑Does Not ❑Not Observable ❑Not Applicable C402.2.5 :Floor insulation R -value. ❑Complies ISee the Envelope Assemblies table for values. [IN 812 ❑Does Not ❑Not Observable ❑Not Applicable C303.1 Building envelope insulation is labeled !❑Complies [IN 1012 with R -value or insulation certificate ❑Does Not providing R -value and other relevant ; data.❑Not Observable ❑Not Applicable C303.2.1 Exterior insulation is protected from❑Complies [IN14]2 damage with a protective material. ❑Does Not Verification for exposed foundation insulation may need to occur during ❑Not Observable Foundation Inspection. ❑Not Applicable C402.2.1 Insulation intended to meet the roof ❑Complies [IN17]3 insulation requirements cannot be ❑Does Not installed on top of a suspended ceiling. Mark this requirement ❑Not Observable ,compliant if insulation is installed ❑Not Applicable !accordingly. Additional Comments/Assumptions: 1 I High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) Project Title: Providence Square - Multi -Family Report date: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 7 of 9 Square ComCheck.cck Section # Final Inspection Complies? Comments/Assumptions & Re .ID. C402.4.6 Weatherseals installed on all loading❑Complies [FI3711 '�, dock cargo doors.❑Does Not ❑Not Observable', ❑Not Applicable C402.4.8 (Recessed luminaires in thermal ❑Complies [FI26]3 envelope to limit infiltration and be IC ❑Does Not rated and labeled. Seal between ❑Not Observable; interior finish and luminaire housing. ❑Not Applicable C406 Efficient HVAC performance, efficient ❑Complies [FI3411 '.lighting system, or on-site supply of❑Does Not 'renewable energy consistent with❑Not Observable what is shown the approved plans. I❑Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 Law Impact (Tier 3) Project Title: Providence Square - Multi -Family Report date: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providers Page 8 of 9 Square ComCheck.cck Project Title: Providence Square - Multi-Family Reportdate: 10/30/17 Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 9 of 9 Square ComCheck.cck