HomeMy WebLinkAboutCOMCHECK - 17-00667-00682 - 430 W 2nd S - Providence Square #1-156 COMcheck Software Version 4.0.5.4
�( Envelope Compliance Certificate
Project Information
Energy Code:
2012 IECC
Project Title.
Providence Square - Multi -Family
Location:
Rexburg, Idaho
Climate Zone:
6b
Project Type:
New Construction
Vertical Glazing /Wall Area:
11%,
Construction Site:
Owner/Agent:
Designer/Contractor:
430 W 2nd North
Greg Nelson
James Wyatt
Rexburg, ID
Sweetwater Properties
NBW Archiects, P.A.
PO Box 142
P.O. Box 2212
Window 2: Vinyl Frame:Operable, Pert. Specs.: Product ID Pending,
Menan, ID 83434
Idaho Falls, ID 83401
0.430
208-390-3424
208.522.8779
jhw@nbwarchitects.com
Building Area
0.400
Floor Area
1 -Apartments (Multifamily)
: Nonresidential
3177
Additional Efficiency Package
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations
Envelope Assemblies
Assembly
Gross Area Cavity Cont. Proposed Budget U -
or R -Value R -Value U -Factor Factor(.)
Perimeter
Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Apartments]
3177 58.0 0.0
0.018
0.021
Basement Wall 1: Solid Concrete:8" Thickness, Normal Density,
2440 21.0 0.0
0.058
0.108
Furring: Wood, Wall Ht 8.0, Depth B.G. 5.5, [Bldg. Use 1 - Apartments]
Window 2: Vinyl Frame:Operable, Pert. Specs.: Product ID Pending,
185 -- ---
0.300
0.430
SHGC 0.40, [Bldg. Use 1 - Apartments] (b)
Door 2: Insulated Metal, Swinging, [Bldg. Use 1 - Apartments]
80 --- ---
0.400
0.370
Exterior Wall 1: Wood -Framed, 16" o.c., [Bldg. Use 1 - Apartments]
6600 21.0 0.0
0.062
0.051
Window 1: Vinyl Frame:Operable, Pert. Specs.: Product ID Pending,
607 --- ---
0.300
0.430
SHGC 0.40, [Bldg. Use 1 - Apartments] (b)
Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Apartments]
240 --- ---
0.400
0.370
Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Apartments] (c)
305 --- ---
0.730
0.540
(a) Budget U -factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c) Slab -On -Grade proposed and budget U -factors shown in table are F -factors.
Project Title: Providence Square - Multi -Family Report date: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 1 of 9
Square ComCheck.cck
Doe PASSES: Desian 1% better than node
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.0.5.4 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title: Providence Square - Multi -Family Report date: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 2 of 9
Square ComCheck.cck
COMcheck Software Version 4.0.5.4
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 3.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Plan Review
Complies?
Comments/Assumptions
& Re .ID
C103.2
i Plans and/or specifications provide all
❑Complies
[PR1]1
information with which compliance
❑Does Not
can be determined for the building
❑Not Observable;
!envelope
and document where
exceptions to the standard are
❑Not Applicable
claimed.
C406
Plans, specifications, and/or
.❑Complies
[PR9]1
calculations provide all information
❑Does Not
.with
which compliance can be
-❑Not Observable
determined for the additional energy
[]Not Applicable
efficiency package options.
C402.3.1
The vertical fenestration area <= 30
!❑Complies
[PR10]1
percent of the gross above -grade wall ',❑Does
Not
area.
❑Not Observable;
❑Not Applicable
C402.3.1
The skylight area <= 3 percent of the
❑Complies
[PR1111
gross roof area.
❑Does Not
❑Not Observable
❑Not Applicable
C402.3.2.
Skylights in office, storage,
❑Complies
2
automotive service, manufacturing,
❑Does Not
[PR15]1
non -refrigerated warehouse, retail'
Observable',
store, and distribution/sorting area :❑Not
have a measured haze value > 90❑Not
Applicable'
percent unless designed to exclude
direct sunlight.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 12 IMedium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Providence Square - Multi -Family
Data filename: N:\Projects\Other\Providence Square Apartments
Square ComCheck.cck
Report date: 10/30/17
14030\40 Construction Documents\Providen Page 3 of 9
Section
#
Footing / Foundation Inspection
Complies? Comments/Assumptions
& Req.ID
C402.2.4
j Below -grade wall insulation R -value.
❑Complies !See the Envelope Assemblies table for values.
[FOi]2
❑Does Not
(-]Not Observable'
❑Not Applicable
C303.2
(Below -grade wall insulation installed
❑Complies
[FOZ]'
per manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
0402.2.6 (Slab
edge insulation R-value.❑Complies
See the Envelope Assemblies table for values.
[F03]2❑Does
Not
❑Not Observable
❑Not Applicable !
C303.2 ':"Slab
edge insulation installed per
❑Complies
[FO4]2 - ":manufacturer's
instructions. :❑Does
Not
[]Not Observable:
[]Not Applicable
0402.2.6
Slab edge insulation depth/length.
❑Complies ,See the Envelope Assemblies table for values.
[FOS]'
Slab insulation extending away from
❑Does Not
building is covered by pavement or
❑Not Observable
>= 10 inches of soil.
❑Not Applicable
C403.2.8.
Exterior Insulation protected against
❑Complies
1
damage, sunlight, moisture, wind,
❑Does Not
[FO6]1
landscaping and equipment
Observable!
maintenance activities.❑Not
:❑Not
Applicable
0402.2.8
Bottom surface of floor structures
❑Complies !.Exception: Requirement does not apply.
[FO12]3
incorporating radiant heating❑Does
Not
insulated to >=R-3.5.
See the Envelope Assemblies table for values.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Providence Square - Multi -Family Report date: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 4 of 9
Square ComCheck.cck
Section
#
Framing / Rough -in Inspection
Complies?
Comments/Assumptions
& Req.ID
C402.4.1,
The building envelope contains a
-[]Complies
C402.4.2
continuous air barrier that is sealed in❑Does
Not
[FR16]1
an approved manner and either
[]Not Observable'
'manner.
constructed or tested in an approved
❑Not
Air barrier penetrations are
Applicable
:sealed
in an approved manner.
C402.4.3, '..Factory
-built fenestration and doors
❑Complies
C402.4.4
are labeled as meeting air leakage
❑Does Not
[FR18]3
requirements.
❑Not Observable
[]Not Applicable
C402.4.7
Vestibules are installed on all building
❑Complies
[FR17]3
entrances. Doors have self-closing
❑Does Not
devices.
❑Not Observable
❑Not Applicable
C402.3.3,
Vertical fenestration U -Factor.
❑Complies
See the Envelope Assemblies table for values.
C402.3.4
[]Does Not
[FR8]1❑Not
Observable
❑Not Applicable
C402.3.3
Vertical fenestration SHGC value.
❑Complies .See
the Envelope Assemblies table for values.
[FR10]1
❑Does Not
[-]Not Observable
-,,❑Not
Applicable
C303.1.3
Fenestration products rated in❑Complies
[FR12]' "accordance
with NERC. !❑Does
Not
❑Not Observable
❑Not Applicable
0303.1.3
Fenestration products are certified as❑Complies
[FR1311
to performance labels or certificates
❑Does Not
provided.
❑Not Observable
❑Not Applicable i
C402.2.7
U -factor of opaque doors associated
❑Complies ;See
the Envelope Assemblies table for values.
[FR14]2
with the building thermal envelope
❑Does Not',
meets requirements.
❑NotObservablej
❑Not Applicable',
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Providence Square - Multi -Family Report date: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 5 of 9
Square ComCheck.cck
# Mechanical Rough -In Inspection Complies? Comments/Assumptions
& Recl.ID
C402.4.5. Stair and elevator shaft vents have ❑Complies
1 motorized dampers that automatically❑Does Not
[ME3]3 '.close.
❑Not Observable
❑Not Applicable
C402.4.5. Outdoor air and exhaust systems have I❑Complies
2 motorized dampers that automatically❑Does Not
[ME58]3 .shut when not in use and meet
maximum leakage rates. Check ❑Not Observable
gravity dampers where allowed. ❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Providence Square - Multi -Family Report date: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 6 of 9
Square ComCheck.cck
Section
#
Insulation Inspection
Complies?
Comments/Assumptions
6 Re .ID
C402.4.1.
IAII sources of air leakage in the
❑Complies
1
'building thermal envelope are sealed,
❑Does Not
[IN111 :caulked,
gasketed, weather stripped
❑Not Observable
I
'permeable
or wrapped with moisture vapor -
wrapping material to I❑Not
Applicable
minimize air leakage.
C402.4.2. (Roof
R -value. For some ceiling❑Complies
See the Envelope Assemblies table for values.
systems, verification may need to❑Does
Not
[IN2]1 ',occur
during Framing Inspection.
❑Not Observable
❑Not Applicable
C303.2
Roof insulation installed per
❑Complies
[IN311
manufacturer's instructions. Blown or
❑Does Not
poured loose -fill insulation is installed
only where the roof slope is <=3 in
❑Not Observable
12.
❑Not Applicable
C303.2 .Above
-grade wall insulation installed
❑Complies
[IN711
per manufacturer's instructions. "❑Does
Not
❑Not Observable
❑Not Applicable
C402.2.5 :Floor
insulation R -value.
❑Complies ISee the Envelope Assemblies table for values.
[IN 812
❑Does Not
❑Not Observable
❑Not Applicable
C303.1
Building envelope insulation is labeled !❑Complies
[IN 1012
with R -value or insulation certificate
❑Does Not
providing R -value and other relevant ;
data.❑Not
Observable
❑Not Applicable
C303.2.1
Exterior insulation is protected from❑Complies
[IN14]2
damage with a protective material.
❑Does Not
Verification for exposed foundation
insulation may need to occur during
❑Not Observable
Foundation Inspection.
❑Not Applicable
C402.2.1
Insulation intended to meet the roof
❑Complies
[IN17]3
insulation requirements cannot be
❑Does Not
installed on top of a suspended
ceiling. Mark this requirement
❑Not Observable
,compliant
if insulation is installed
❑Not Applicable
!accordingly.
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Providence Square - Multi -Family Report date: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 7 of 9
Square ComCheck.cck
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Re .ID.
C402.4.6
Weatherseals installed on all loading❑Complies
[FI3711
'�, dock cargo doors.❑Does
Not
❑Not Observable',
❑Not Applicable
C402.4.8
(Recessed luminaires in thermal
❑Complies
[FI26]3
envelope to limit infiltration and be IC
❑Does Not
rated and labeled. Seal between
❑Not Observable;
interior finish and luminaire housing.
❑Not Applicable
C406
Efficient HVAC performance, efficient
❑Complies
[FI3411
'.lighting system, or on-site supply of❑Does
Not
'renewable energy consistent with❑Not
Observable
what is shown the approved plans.
I❑Not
Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 Law Impact (Tier 3)
Project Title: Providence Square - Multi -Family Report date: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providers Page 8 of 9
Square ComCheck.cck
Project Title: Providence Square - Multi-Family Reportdate: 10/30/17
Data filename: N:\Projects\Other\Providence Square Apartments - 14030\40 Construction Documents\Providen Page 9 of 9
Square ComCheck.cck