HomeMy WebLinkAboutLOAD SHORT FORM - 12-00515-520 - Summerfield Townhomes #7-12Load Short Form Entire House KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR G PLEX Date: NOV,12,2012 By: ROBERT HALL For. 2 -CARE PLEX KARTCHNER HOMES 12 00515 thru 12 00520 REXBURG Summerfield Townhomes #7-12 Office COOV HEATING EQUIPMENT Htg Clg Infiltration Outside db (OF) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Semi -loose Design TD ('F) 74 14 Fireplaces 0 Daily range - H Inside humidity(%) 50 50 Moisture difference(gr/Ib) 57 -31 HEATING EQUIPMENT Area Make n/a Clg load Htg AVF Trade n/a (fF) Model We (Btuh) (cfm) GAMA ID n/a UNIT B FURNACE d 1253 Efficiency n/a 660 Heating input n/a 1253 Heating output 0 Btuh Temperature rise 0 OF Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Space thermostat n/a in H2O COOLING EQUIPMENT Area Make n/a Clg load Htg AVF Trade n/a (fF) Cord n/a (Btuh) (cfm) Coil n/a UNIT B FURNACE d 1253 ARI ref no n/a 7205 660 Efficiency n/a 1253 Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Cig AVF (fF) (Btuh) (Btuh) (cfm) (cfm) UNIT B FURNACE d 1253 15697 7205 660 660 UNIT A FURNACE d 1253 28967 9901 660 660 UNIT C FURNACE d 1251 19606 3873 660 660 Entire House d 3757 64270 20784 1980 2352 Other equip loads 0 0 Equip. @ 0.94 RSM 19537 Latent cooling 0 Tnrnl C I o�c� I r_n��n I nnro� I .Inns I Horn Printout certified by ACCA to meet all requirements of Manual 8th Ed. -tJej- w,j fttagf _ Right-Suite01_nivenea17.1.03 RSU06972 2012 -Nov -1608:23:16 AiC4� C Documents and Settings \ROBERT HALL \My Oocuments \WnghlsoR HVAC \2.CAR 6-PLEX UNITS 1-3.lup Cal Page 1 Load Short Form UNIT A FURNACE KARTCHNER HOMES Job: 2- CAR 6. PLEX Date: NOV,12,2072 By: ROBERT HALL 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Information Htg AVF Cig AVF Htg Clg Project Information Win) For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG ROOM NAME Area Design Information Htg AVF Cig AVF Htg Clg Infiltration (Cfm) Win) Outside db ('F) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Semi -loose Design TO (°F) 74 14 Fireplaces 1447 0 Daily range - H 9564 Inside humidity(%) 50 50 0 Moisture difference(grAb) 57 -31 I I I HEATING EQUIPMENT I COOLING EQUIPMENT Make Intl Comfort Products Make Intl Comfort Products Trade Tempstar - Trade 13 SEER N Series R410A AC Model N9MP2050B12** Cord N4A318A(G)KA1* GAMA ID 70304 Coil ED*4X246**+TD1 ARI ref no 782995 Efficiency 90 AFUE Efficiency 13 SEER Heating input 50000 Btuh Sensible cooling 12390 Btuh Heating output 44000 Btuh Latent cooling 5310 Btuh Temperature rise 72 °F Total cooling 17700 Btuh Actual air flow 660 cfm Actual air flow 660 dm Air flow factor 0.023 cfmBtuh Air flow factor 0.067 cfmBtuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Cig AVF (f?) (Btuh) (Btuh) (Cfm) Win) UNIT A p 1253 28967 10921 660 728 UNIT A FURNACE d 1253 28967 9901 660 660 Other equip loads 1447 274 Equip. @ 0.94 RSM 9564 Latent cooling 0 I I I I I 0 L 1253 30415 Sold /italic values have been manually overridalen 9564 660 660 Printout certified by ACCA to meet all requirements of Manual ath Ed A&� ti �. Right Suite® Unwema17.1.03 RSU06972 2012 -Nov -1608:23:16 14l..Cd1 C:\Documents and Settings \ROBERT HALL \ My Documents \Wrightson HVAC \2-CAR6-PLEX UNITS 1S.rup Cal Paget Load Short Form Jab: CAR 6- PLEX N Date: OV,12,2012 UNIT B FURNACE By: ROBERT HALL KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 For. 2-CAR6 PLED( KARTCHNER HOMES REXBURG HEATING EQUIPMENT Make Intl Comfort Products Intl Comfort Products Design 13 SEER N SERIES R2 AC Cord Htg Clg Infiltration Outside db ff) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Semi -loose Design TD (°F) 74 14 Fireplaces 0 Daily range - H Actual air flow Inside humidity(%) 50 50 0.042 Moisture difference(grAb) 57 -31 in H2O HEATING EQUIPMENT Make Intl Comfort Products Intl Comfort Products Trade Tempstar 13 SEER N SERIES R2 AC Cord Model N9MPD040F08 Coil EB*2X246**++AGKSAPX01 GAMA ID 272480 3317594 0.092 Efficiency 92.1 AFUE in H2O Heating input 40000 Btuh Heating output 37000 Btuh Temperature rise 61 *F Actual air flow 660 dm Air flow factor 0.042 cfmBtuh Static pressure 0.70 in H2O Space thermostat 7204 COOLING EQUIPMENT Make Intl Comfort Products Trade 13 SEER N SERIES R2 AC Cord N2A318A(G)KC* Coil EB*2X246**++AGKSAPX01 ARI ref no 3317594 Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 13 SEER Area 11900 Btuh 5100 Btuh 17000 Btuh 660 cfm 0.092 cfmBtuh 0.70 in H2O 1.00 8419 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (f') (Btuh) (Btuh) (cfm) (cfm) UNIT B p 1253 15697 8419 660 771 UNIT B FURNACE d 1253 15697 7205 660 660 Other equip loads 2428 459 Equip. @ 0.94 RSM 7204 Latent cooling 0 TnTni c I .�Co I .Oa�C I -inns I Ccn I ccn Bold/italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual 8th Ed. iR.IZ.}ov -/�Wrghtall Right-Suite@Univema17.1.03 RSU06972 2012-N-1608:23:16 Z& GADocuments and Settings \ROBERT HALL \My Documents \Wnghtsoh HVAC \2 -CAR 6-PLEX UNITS 1.3.mp Cal Page 3 Load Short Form UNIT C FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6• PLEX Date: NOV,12,2012 By: ROBERT HALL Htg Clg Infiltration Outside db (*F) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Semi -loose Design TD (°F) 74 14 Fireplaces 0 Daily range - H Inside humidity(%) 50 50 Moisture difference(grAb) 57 -31 HEATING EQUIPMENT Make Infl Comfort Products Trade Tempstar Model N9MP2050B12** GAMA ID 70304 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 90 AFUE Intl Comfort Products 50000 Btuh 44000 Btuh 72 `F 660 cfm 0.034 cfmBtuh 0.70 in H2O COOLING EQUIPMENT Make Intl Comfort Products Trade 13 SEER N SERIES F22 AC Cond N2A318P(G)KC* Coil EB*2X246**++AG-KSAPX01 ARI ref no 3317594 Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 13 SEER Area 11900 Btuh 5100 Btuh 17000 Btuh 660 Clint 0.170 cfmBtuh 0.70 in H2O 1.00 5002 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (T) (Btuh) (Btuh) (cfm) (cfm) UNIT C p 1251 19606 5002 660 852 UNIT C FURNACE d 1251 19606 3873 660 660 Other equip loads 1721 326 Equip. @ 0.94 RSM 3946 Latent cooling 0 Bold /italic values have been manually ovenitlCen Printout certified by ACCA to meet all requirements of Manual 8th Ed. 1 .p1y.. w,$Bltitilof. Right -Sul tel) U niv ers al 7.1.03 RSU 06972 2012 -Nov -1608:23:16 AM CADocuments and Settings \ROBERT HALL \My Documents 1WnghLwft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 4 Load Short Form UN/TA KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Project Information For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL HEATING EQUIPMENT Make n/a Trade n/a Model n/a GAMA ID n/a Efficiency n/a Design Heating input Htg AVF (ofm) Htg Clg Infiltration Outside db ('F) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Semi -loose Design TD (°F) 74 14 Fireplaces 0 Daily range - H Latent cooling Inside humidity(%) 50 50 0 Moisture difference(grAb) 57 -31 dm HEATING EQUIPMENT Make n/a Trade n/a Model n/a GAMA ID n/a Efficiency n/a Make n/a Heating input Htg AVF (ofm) Trade n/a Heating output 0 Btuh Temperature rise 0 °F Actual air flow 0 cfm Air flow factor 0 cfmBtuh Static pressure 0 in H2O Space thermostat n/a Latent cooling COOLING EQUIPMENT Area (fal Make n/a Clg load (Btuh) Htg AVF (ofm) Trade n/a STORAGE 17 Cord n/a 0 0 Coil n/a MUD 14 ARI ref no n/a 0 0 Efficiency n/a 34 Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 dm Air flow factor 0 cfmBtuh Static pressure 0 in H2O Load sensible heat ratio 0 22 ROOM NAME Area (fal Htg load (Btuh) Clg load (Btuh) Htg AVF (ofm) Clg AVF (cfm) STORAGE 17 0 0 0 0 MUD 14 0 0 0 0 STAIRS 34 0 0 0 0 POWDER 17 0 0 0 0 KITA7INEIFAM 299 18343 5056 418 337 MASTER BATH 48 948 350 22 23 MASTER WIC 33 290 91 7 6 LAUNDRY 17 0 0 0 0 MASTER BED 151 3680 2671 84 178 UPPER STAIRS 32 0 0 0 0 OPEN FROM ABOVE 39 0 0 0 0 UPPER BATH 34 945 159 22 11 MECH 20 0 0 0 0 BED1 93 2479 1290 56 86 BED2 1 SAI I %A#A%f 97 I,. 2282 1303 52 87 V 1 V V Bold/italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual 8th Ed. �• •rj&-w,Jg1 to fll• Right-SuiteO Universal 7.1.03 RSU 06972 `•M CADocuments and Settings \ROBERT HALL \My Documents \Wrightsotl HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal 2012 -Nov -16 08:23:16 Page 5 bHrWbC H I L4L3 U I U I V I V UNIT A p 1253 28967 10921 660 728 Other equip loads 0 0 Equip. @ 0.94 RSM 10266 Latent cooling 0 Triter I I an I ,r, c I c 1 -rno Bold /italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual8th Ed Thgtst ft- Right Suite®Universa17.1.03 RSU 06972 2012 -Nov 4608:2316 �yvr /�i' � C:Mocuments and Settings \ROBERT HALL Wy D==ents \Wrighisoft HVAC Q -CAR 6-PLE%UNITS 1-3.rup Cal Page Load Short Form Job: 2 - CAR rr PLEX Date: NOV,12,2012 UNIT B By: ROBERT HALL KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Project Information For. 2 -CARE PLEX KARTCHNER HOMES REXBURG Design Information Htg Clg Infiltration Outside db (*F) -6 89 Method Simplified Inside db (°F) 68 75 Construction quality Semi -loose Design TO (°F) 74 14 Fireplaces 0 Daily range - H Inside humidity(%) 50 50 Moisture difference(grAb) 57 -31 HEATING EQUIPMENT Make n/a Trade n/a Model n/a GAMA ID n/a Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat n/a n/a 0 Btuh 0 °F 0 Cfm 0 cfmBtuh 0 in H2O COOLING EQUIPMENT Make n/a Trade n/a Cond n/a Coil n/a ARI ref no n/a Efficiency Sensible cooling Latent cooling Total cooling Actual airflow Air flow factor Static pressure Load sensible heat ratio n/a 0 Btuh 0 Btuh 0 Btuh 0 cfm 0 cfmBtuh 0 in H2O 0 ROOM NAME Area (fl?) Htg load (Btuh) Clg load (Btuh) Htg AVF (Cfm) Clg AVF (Cfm) KIT/DIWFAM B 299 8434 4529 355 415 HALLWAY B 61 0 0 0 0 GARAGE B 248 0 0 0 0 BED 2 B 97 2421 1429 102 131 BED 1 B 93 1358 963 57 88 MECH B 20 0 0 0 0 UPER BATH B 34 123 70 5 6 MASTER BED B 151 2002 651 84 60 UPPER STAIR B 32 0 0 0 0 OPEN TO ABOVE B 39 0 0 0 0 LAUNDRY B 17 0 0 0 0 MASTER WIC B 33 434 418 18 38 MASTER BATH B 48 924 359 39 33 MAIN STAIR B 34 0 0 0 0 POWDER B 17 0 0 0 0 JI yr Ul=D iI v Bold /italic values have been manually overrialaEen Printout certified by ACCA to meet all requirements of Manual 8th Ed A= A&-!.Wrigftt 0fr Right Suite® U niversal 7.1.03 RSU 06972 AM Ci Documents and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.ru0 Cal 2012 -Nov -16 08:23:16 Page 7 MUU 1:3 1 14 1 U I U I U I U UNIT B p 1253 15697 8419 660 771 Other equip loads 0 0 Equip. @ 0.94 RSM 7914 Latent cooling 0 —A ^ I ,oro I ,rr_.r. I ten„ Bold /imlk values have been manuaW overridden Printout certified by ACCA to meet all requirements of Manual 8th Ed Ap— -Fk-weighty K- Right-Suite(D Universal 7.1.03 RSU 06972 2012 -Nov -160823:16 AMCADocuments and Setlings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page a Load Short Form UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 830442 Phone: 745-8468 Project Information For: 2 -CARE PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL ROOM NAME Area (ft') Htg load (Btuh) Design Htg AVF (Cfm) Clg AVF (Cfm) OPEN TO ABOVE C 39 Htg 0 Clg Infiltration HALLWAY C 61 Outside db (*F) -6 0 89 Method Simplified Inside db (°F) 68 94 75 Construction quality Semi -loose Design TD (°F) 74 46 14 Fireplaces 32 0 Daily range - 0 H 20 0 0 Inside humidity(%) 50 UPPER BATH C 50 130 71 4 Moisture difference(grAb) 57 17 -31 0 0 0 HEATING EQUIPMENT 33 COOLING EQUIPMENT 348 Make n/a 59 MASTER BATH C 48 Make n/a 430 52 Trade n/a MASTER BED C 151 2108 Trade n/a 71 124 Model n/a 304 10509 1145 Cond n/a 195 POWDER C GAMA ID n/a 0 0 0 Coil n/a MAIN STAIR C 32 0 0 0 0 ARI ref no n/a 12 0 Efficiency 0 n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 °F Total cooling 0 Btuh Actual air flow 0 Cfm Actual air flow 0 Cfm Air flow factor 0 cfmBtuh Air flow factor 0 cfmBtuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area (ft') Htg load (Btuh) Clg load (Btuh) Htg AVF (Cfm) Clg AVF (Cfm) OPEN TO ABOVE C 39 0 0 0 0 HALLWAY C 61 0 0 0 0 BED 2 C 97 2786 1316 94 224 BED 1 C 93 1360 962 46 164 UPPER STAIR C 32 0 0 0 0 MECH C 20 0 0 0 0 UPPER BATH C 34 130 71 4 12 LAUNDRY C 17 0 0 0 0 MASTER WIC C 33 1169 348 39 59 MASTER BATH C 48 1544 430 52 73 MASTER BED C 151 2108 729 71 124 KIT/DINFAM C 304 10509 1145 354 195 POWDER C 14 0 0 0 0 MAIN STAIR C 32 0 0 0 0 MUD C 12 0 0 0 0 Bold /ilalk values have been manually ovemdden Printout certified by ACCA to meet all requirements of Manual 8th Ed. 1 } Wr tib, Right Suite® Univema17.1.03 RSU 06972 2012 -Nov -1608:23:16 AM C \Documents and Settings 1ROSERT HALL \My Dowments lwrightme HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 9 I�HKHhC V I L4tl I U I U I U I U UNIT C p 1251 19606 5002 660 852 Other equip loads 0 0 Equip. @ 0.94 RSM 4702 Latent cooling 0 Tr.-rni n I ,nu I ,nr_nc I a-�nn I ccn I oco Bold /italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual8th Ed !A_ A&-wriyhtsofi- Right Suite® U nivemal 7.1.03 RSU 06972 2012 -Nov -1608:23:16 /Ri& C:1Documents and Settings \ROBERT HALL\ My Documents \Wnghtsob HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 10 Building Analysis Entire House KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Location: BtuW Indoor: Heating Cooling Idaho Falls, ID, US 17453 Indoor temperature ff) 68 75 Elevation 4741 ft 13.9 Design TD (°F) 74 14 Latitude: 44°N Ceilings Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 57.0 31.5 Dry bulb (OF) -6 89 Infiltration: Ducts Daily range (OF) - 34 ( H ) Method Simplified 0 Wet bulb (OF) - 60 Construction quality Semi -loose 0 Wind speed (mph) 15.0 7.5 Fireplaces 0 Adjustments Component BtuW Btuh % of load Walls 5.0 17453 27.2 Glazing 25.9 8904 13.9 Doors 0 0 0 Ceilings 2.2 4235 6.6 Floors 8.9 17105 26.6 Infiltration 4.2 16572 25.8 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 64270 100.0 Component BtuhffF Btuh % of load Walls 0.6 2217 10.7 Glazing 18.1 6225 29.9 Doors 0 0 0 Ceilings 1.3 2404 11.6 Floors 0.0 62 0.3 Infiltration 0.4 1677 8.1 Ducts 0 0 Ventilation 0 0 Internal gains 8200 39.5 Blower 0 0 Adjustments 0 Total 20784 100.0 Overall Uvalue=0.083 Btuhfff-°F Data entries checked. qC� Ad- yyr�titjpR- Right -Suite® Univema17.1.03 RSUD6972 2012 -Nov .16 08:23:16 JR.C.T C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 1 Building Analysis UNIT A FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 For. 2 -CARE PLEX KARTCHNER HOMES REXBURG Location: BtuhffF Indoor: Idaho Falls, ID, US Walls Indoor temperature ('F) Elevation 4741 ft 26.8 Design TD (°F) Latitude: 440N 3315 Relative humidity(%) Outdoor: Heating Cooling Moisture difference(grAb) Dry bulb ('F) -6 89 Infiltration: Daily range (°F) - 34 ( H ) Method Wet bulb ('F) - 60 Construction quality Wind speed (mph) 15.0 7.5 Fireplaces Component BtuhffF Btuh % of load Walls 5.0 8166 26.8 Glazing 25.9 3315 10.9 Doors 0 0 0 Ceilings 2.3 1462 4.8 Floors 13.1 8502 28.0 Infiltration 4.2 7522 24.7 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 1447 4.8 Adjustments -0 Total 30415 100.0 Component BtuK4f Btuh % of load Walls 0.6 1037 10.2 Glazing 20.6 2639 25.9 Doors 0 0 0 Ceilings 1.3 830 8.2 Floors 0.1 33 0.3 Infiltration 0.4 761 7.5 Ducts 0 0 Ventilation 274 2.7 Internal gains 4600 45.2 Blower 0 0 Adjustments 0 Total 10175 100.0 Overall U-value=0.095 BtuhAf--°F Data entries checked. Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL Heating Cooling 68 75 74 14 50 50 57.0 -31.5 Simplified Semi -loose 0 !C �,yr�tivpR, Righ[Suiie®Universal7.t.03 RSU 06972 2072 -Nov -7608:23:16 /R.C,A C:\Documentsand Settings \ROBERT HALL \My Documents \Wrightsoft HVAC 12 -CAR 6-PLEX UNITS 1-3.rup Cal Page Building Analysis UNIT B FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Project Information For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Heating Component Design Conditions % of load Walls 5.0 3861 Indoor: Heating Cooling Idaho Falls, ID, US 15.1 Indoor temperature ff) 68 75 Elevation 4741 it Ceilings Design TD (°F) 74 14 Latitude: 44°N 6.0 Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 57.0 31.5 Dry bulb ('F) 3 89 Infiltration: 0 Daily range ('F) - 34 ( H ) Method Simplified 0 Wet bulb ('F) - 60 Construction quality Semi -loose Adjustments Wind speed (mph) 15.0 7.5 Fireplaces 0 Heating Component Btuhff Btuh % of load Walls 5.0 3861 21.3 Glazing 25.9 2742 15.1 Doors 0 0 0 Ceilings 2.2 1387 7.6 Floors 6.0 3838 21.2 Infiltration 4.2 3869 21.3 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 2428 13A Adjustments 0 Total 18125 100.0 Cooling Component Btuh/fF Btuh % of load Walls 0.6 491 6.4 Glazing 18.2 1923 25.1 Doors 0 0 0 Ceilings 1.2 787 10.3 Floors 0.0 13 0.2 Infiltration 0.4 392 5.1 Ducts 0 0 Ventilation 459 6.0 Internal gains 3600 47.0 Blower 0 0 Adjustments -0 Total 7664 100.0 Overall Uvalue = 0.073 Btuh/FF--°F Data entries checked. ,,fi�ty -F6. W!'•!0.1bp}t- Right-SuiteSUnivema17.1.03 RSU06972 2012 -Nov .16 08:23:16 AZIN C:\Docunhents and Settings \ROBERT HALL \My Documents 1Wrightsott HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 3 Building Analysis UNIT C FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 7455468 - Project Information For. Location: Idaho Falls, ID, US Elevation 4741 ft Latitude: 44°N Outdoor: Dry bulb (°F) Daily range (°F) Wet bulb (°F) Wind speed (mph) 2-CAR6 PLEX KARTCHNER HOMES REXBURG Heating Component Indoor: Btuh Indoor temperature ff) Walls Design TD (°F) 5426 Relative humidity(%) Heating Cooling Moisture difference(grAb) -6 89 Infiltration: - 34 ( H ) Method - 60 Construction quality 15.0 7.5 Fireplaces Heating Component Btuhff Btuh %of load Walls 5.0 5426 25.4 Glazing 25.9 2847 13.4 Doors 0 0 0 Ceilings 22 1387 6.5 Floors 7.5 4765 22.3 Infiltration 4.2 5180 24.3 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 1721 8.1 Adjustments 0 Total 21327 100.0 Cooling Component Btuww Btuh % of load Walls 0.6 689 16A Glazing 16.9 1857 44.2 Doors 0 0 0 Ceilings 1.2 787 18.7 Floors 0.0 15 0.4 Infiltration 0.4 524 12.5 Ducts 0 0 Ventilation 326 7.8 Internal gains 0 0 Blower 0 0 Adjustments 0 Total 4198 100.0 Overall U -value = 0.078 Btuh/fF--°F Data entries checked. Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Heating Cooling 68 75 74 14 50 50 57.0 31.5 Simplified Semi -loose 0 ,.��+�- -•*. yy�•pti�0/t- Right Suite® U niversal 7.1.03 RSU 06972 2012 -Nov .16 08:23:16 -111 .T C:\Documenlsantl Settings \ROBERT HALL \ My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page Building Analysis UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8466 For. Location: Idaho Falls, ID, US Elevation 4741 ft Latitude: 44'N Outdoor: Drybulb(°F) Daily range (°F) Wet bulb ('F) Wind speed (mph) 2-CAR6 PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Component Indoor: Heating Cooling Walls Indoor temperature ('F) 68 75 Glazing Design TO (°F) 74 14 Doors Relative humidity(%) 50 50 Heating Cooling Moisture difference(grAb) 57.0 -31.5 -6 89 Infiltration: 8502 29.3 - 34 ( H ) Method Simplified 26.0 - 60 Construction quality Semi -loose 0 15.0 7.5 Fireplaces 0 0 Component Btuh/ff Btuh % of load Walls 5.0 8166 28.2 Glazing 25.9 3315 11.4 Doors 0 0 0 Ceilings 2.3 1462 5.0 Floors 13.1 8502 29.3 Infiltration 4.2 7522 26.0 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments -0 Total 28967 100.0 Component Btuh/fP Btuh %of load Walls 0.6 1037 9.5 Glazing 28.6 3659 33.5 Doors 0 0 0 Ceilings 1.3 830 7.6 Floors 0.1 33 0.3 Infiltration 0.4 761 7.0 Ducts 0 0 Ventilation 0 0 Internal gains 4600 42.1 Blower 0 0 Adjustments -0 Total 10921 100.0 Overall U -value = 0.095 BtuhNF-°F Data entries checked. A—-p4a-wrjptitpR. Right-SuitelD Univema17.1.03 RSU06972 2012 -Nov -1608:23:16 'Z& C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsofi HVAC \2 -CAR 6-PLEX UNITS iJ.mp Cal Page 5 Building Analysis UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 For. 2-CAR6 FLEX KARTCHNER HOMES REXBURG Location: Btuh/fF Indoor: Idaho Falls, ID, US Walls Indoor temperature ff) Elevation 4741 ft 24.6 Design TD (°F) Latitude: 44°N 2742 Relative humidity(%) Outdoor: Heating Cooling Moisture difference(grAb) Dry bulb(°F) -6 89 Infiltration: Daily range (°F) - 34 (H ) Method Wet bulb ('F) - 60 Construction quality Wind speed (mph) 15.0 7.5 Fireplaces Component Btuh/fF Btuh % of load Walls 5.0 3861 24.6 Glazing 25.9 2742 17.5 Doors 0 0 0 Ceilings 2.2 1387 8.8 Floors 6.0 3838 24.5 Infiltration 4.2 3869 24.6 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 1 15697 100.0 Component BtuhAft Btuh % of load Walls 0.6 491 5.8 Glazing 29.6 3137 37.3 Doors 0 0 0 Ceilings 1.2 787 9.3 Floors 0.0 13 0.2 Infiltration 0.4 392 4.7 Ducts 0 0 Ventilation 0 0 Internal gains 3600 42.8 Blower 0 0 Adjustments 0 Total 1 1 84191 100.0 Overall U -value = 0.073 BtuhAP--°F Data entries checked. Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL Heating Cooling 68 75 74 14 50 50 57.0 -31.5 Simplified Semi400se 0 -P6- Wf'lOh'CrpT>C- Right -Suite® Univers a[ 7.1.03 RSU06972 2012 -Nov -1608:23:16 AML C:\Documents and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.wp Cal Page 6 Building Analysis UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Component Design Conditions %of load Walls 5.0 5426 Indoor: Heating Cooling Idaho Falls, ID, US 14.5 Indoor temperature ('F) 68 75 Elevation 4741 ft Ceilings Design TD (°F) 74 14 Latitude: 44°N 7.5 Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gdib) 57.0 31.5 Dry bulb ('F) -6 89 Infiltration: 0 Daily range (°F) - 34 (H ) Method Simplified 0 Wet bulb ('F) - 60 Construction quality Semi -loose Adjustments Wind speed (mph) 15.0 7.5 Fireplaces 0 Component BtuhtfF Btuh %of load Walls 5.0 5426 27.7 Glazing 25.9 2847 14.5 Doors 0 0 0 Ceilings 2.2 1387 7.1 Floors 7.5 4765 24.3 Infiltration 4.2 5180 26A Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 19606 100.0 Component Btuhff Btuh % of load Walls 0.6 689 13.8 Glazing 27.2 2986 59.7 Doors 0 0 0 Ceilings 1.2 787 15.7 Floors 0.0 15 0.3 Infiltration 0.4 524 10.5 Ducts 0 0 Ventilation 0 0 Internal gains 0 0 Blower 0 0 Adjustments 0 Total 5002 100.0 Overall U -value = 0.078 BtuW--°F Data entries checked. t } w,S ftt�f!- Right -Suite® U nivers al 7.1.03 RSU 06972 2012 -Nov -1608:23:16 AM C:\Documents and Settings \ROBERT HALL \ My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page Component Constructions Job: 2-CAX p Date: NOV,12,20122,2012 Entire House By: ROBERT HALL KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Project Information For: 2 -CARE PLEX KARTCHNER HOMES REXBURG Construction descriptions - Or Area 1.1 -value Insul R Htg HTM Loss CIg HTM Gain re Bw W --°F V-•Fswh BW W Stun BWNT awn Walls 12E-Osw : Frm wall, vnl ext, 3/8"wood shth , r-19 cav ins, 1/2" gypsum board int fish , 2x6" wood frm Partitions (none) Windows 61C: VINYL .35 U- VALUE; NFRC rated(SHGC 13.35) Doors 11 DO:11 DO Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" gypsum board int fish DftPartGeiL C part ceiling, carpel fir fnsh , frm fir, 12" thkns, 1/2" gypsum board int fnsh Floors 19A-Obwp: Part floor, carpet fir finish , firm flr, 12" thkns, 1/2" gypsum board int fnsh 22A-vpl: Bg floor, light dry soil, vinyl fir fnsh In 825 Design Conditions 5.03 4150 Location: 527 Indoor: Heating Cooling Idaho Falls, ID, US 3804 Indoor temperature ff) 68 75 Elevation 4741 ft 19.0 Design TD (°F) 74 14 Latitude: 44°N W 934 Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 57.0 31.5 Dry bulb ('F) -6 89 Infiltration: - 2217 Daily range (°F) - 34 (H ) Method Simplified 5232 Wet bulb (T) - 60 Construction quality Semi -loose 0 Wind speed (mph) 15.0 7.5 Fireplaces 0 W 25 Construction descriptions - Or Area 1.1 -value Insul R Htg HTM Loss CIg HTM Gain re Bw W --°F V-•Fswh BW W Stun BWNT awn Walls 12E-Osw : Frm wall, vnl ext, 3/8"wood shth , r-19 cav ins, 1/2" gypsum board int fish , 2x6" wood frm Partitions (none) Windows 61C: VINYL .35 U- VALUE; NFRC rated(SHGC 13.35) Doors 11 DO:11 DO Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" gypsum board int fish DftPartGeiL C part ceiling, carpel fir fnsh , frm fir, 12" thkns, 1/2" gypsum board int fnsh Floors 19A-Obwp: Part floor, carpet fir finish , firm flr, 12" thkns, 1/2" gypsum board int fnsh 22A-vpl: Bg floor, light dry soil, vinyl fir fnsh In 825 0.068 19.0 5.03 4150 0.64 527 is 756 0.068 19.0 5.03 3804 0.64 483 S 954 0.068 19.0 5.03 4802 0.64 610 W 934 0.068 19.0 5.03 4697 0.64 597 all 3468 0.068 19.0 5.03 17453 0.64 2217 In 202 0.350 0 25.9 5232 11.5 2332 S 117 0.350 0 25.9 3025 20.6 2411 W 25 0.350 0 25.9 648 37.7 941 all 344 0.350 0 25.9 8904 16.5 5685 n 105 0 0 0 0 0 0 s 63 0 0 0 0 0 0 all 168 0 0 0 0 0 0 1875 0.026 38.0 1.92 3607 1.09 2047 38 0.221 0 16.4 628 9.29 357 40 0.295 229 0.989 0 0 $y.41*. Wr�h1GWR• Right Suite® U niversal 7.1.03 RSU06972 1R.C.T C:\Documents and Settings \ROBERT HALL\My Documents \Wnghlsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal 8.20 328 1.55 62 73.2 16778 0 0 2012-Nav -16 08:23:18 Page 1 Component Constructions UNIT A FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 For. 2 -CARE FLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL Location: Area Indoor: Heating Cooling Idaho Falls, ID, US BWW-'F Indoor temperature ff) 68 75 Elevation 4741 ft 19.0 Design TD (°F) 74 14 Latitude: 44°N s Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gdlb) 57.0 -31.5 Dry bulb (T) -6 89 Infiltration: n 35 0 Daily range ff) - 34 (H ) Method Simplified 0 Wet bulb (*F) - 60 Construction quality Semi -loose 0 Wind speed (mph) 15.0 7.5 Fireplaces 0 0 Construction descriptions Walls 12 E-Osw : Frm wall, vnl ext, 3/8" wood shth , r-19 cav ins, 1/2" gypsum board int fnsh , 2"x6" woad fnn Partitions (none) Windows 61C: VINYL .35 U- VALUE; NFRC rated(SH(30=0.35) Doors 11 DO: 11 DO Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 cell ins, 1/2" gypsum board int fnsh DftPartCeit C part ceiling, carpet flr fnsh , frm fir, 12" thins, 1/2" gypsum board int fnsh Floors 19A-Obscp: Partfloor, carpet flr fnsh , firm fir, 12" thins, 1/2" gypsum board int fnsh 22A-vpl: Bg floor, light dry soil, vinyl flr fnsh Or Area LLvalue Insul R BtuNre R BWW-'F 1t'-'Fatuh In 270 0.068 19.0 e 326 0.068 19.0 s 325 0.068 19.0 W 702 0.068 19.0 all 1623 0.068 19.0 Htg HTM Loss Clg HTM Gain BtuNre Bwh Btuw awn 5.03 1357 0.64 172 5.03 1642 0.64 209 5.03 1635 0.64 208 5.03 3531 0.64 449 5.03 8166 0.64 1037 n 71 0.350 0 25.9 1839 11.5 820 s 32 0.350 0 25.9 829 20.6 661 W 25 0.350 0 25.9 648 37.7 941 all 128 0.350 0 25.9 3315 18.9 2422 n 35 0 0 0 0 0 0 s 21 0 0 0 0 0 0 all 56 0 0 0 0 0 0 625 0.026 38.0 1.92 1202 1.09 682 16 0.221 0 16.4 260 9.29 147 22 0295 0 8.20 177 1.55 33 114 0.989 0 73.2 8325 0 0 � 1y ''74" Wrt'Otittooft- Right -Suite® Univemal7.1.03 RSU06972 2012 -Nov -1608:23:18 ASN C:\Documents and Sebngs \ROBERT HALL \My Documents \WrightWt HVAC \2 -CAR 6-PLEX UNITS 1-3.n1p Cal Page 2 Component Constructions Component Job: Date: 2-CAX NOV,12,20122012 UNIT B FURNACE By: ROBERT HALL KARTCHNER HOMES Indoor temperature ff) 68 197 STOCKMAN BLVD , RIGBY , In 834442 Phone: 745-8468 Elevation 4741 ft W-'FAWh For. 2-CAR6 FLEX KARTCHNER HOMES REXBURG Location: Area Indoor: Heating Cooling Idaho Falls, ID, US CIg HTM Indoor temperature ff) 68 75 Elevation 4741 ft W-'FAWh Design TO (°F) 74 14 Latitude: 44°N It Relative humidity(%a) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 57.0 31.5 Dry bulb (T) 3 89 Infiltration: 5.03 1430 Daily range (T) - 34 (H ) Method Simplified 0.068 Wet bulb (T) - 60 Construction quality Semi -loose 145 Wind speed (mph) 15.0 7.5 Fireplaces 0 5.03 Construction descriptions Walls 12E-Osw : Fnn wall, vnl ext, 3/8"wood shth , r-19 cav ins, 1/2" gypsum board int fish , 2"x6" wood frm Partitions (none) Windows 61 C: VINYL .35 U- VALUE; NFRC rated(SHGG0.35) Doors 11 DO: 11 DO Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 cell ins, 1/2" gypsum board int fish DRPartCeit C part ceiling, carpet flr fnsh , frm fir, 12" thins, 1/2" gypsum board int fnsh Floors 19A-Obscp: Part floor, carpet fir fnsh , frm fir, 12" thkns, 1/2" gypsum board intfnsh 22A-vpl: Bg floor, light dry soil, vinyl fir fnsh Or Area lYvalue Insul R Htg HTM Loss CIg HTM Gain 0.350 r BWW--'F W-'FAWh Stow Stuh BWW BWh It 256 0.068 19.0 5.03 1288 0.64 164 S 284 0.068 19.0 5.03 1430 0.64 182 w 227 0.068 19.0 5.03 1144 0.64 145 all 767 0.068 19.0 5.03 3861 0.64 491 n 60 0.350 0 25.9 1554 11.5 693 s 46 0.350 0 25.9 1188 20.6 947 all 106 0.350 0 25.9 2742 15.5 1640 n 35 0 0 0 0 0 0 S 21 0 0 0 0 0 0 all 56 0 0 0 0 0 0 625 0.026 38.0 1.92 1202 1.09 682 11 0.221 0 16.4 184 9.29 105 8 0.295 0 8.20 69 1.55 13 52 0.989 0 73.2 3769 0 0 "ti .*rf . WrfOt M3,ln- Right -Suite® U niv ers a] 7.1.03 RSU 06972 2012 -Nov -1608:23:18 ACCT CADocuments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 3 Component Constructions Component Job: Date: 2 -CA X NOV,12,20122,2012 UNIT C FURNACE By: ROBERT HALL KARTCHNER HOMES Indoor temperature ff) 68 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 Elevation 4741 ft W-'FBWh For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Location: Area Indoor: Heating Cooling Idaho Falls, ID, US Clg HTM Indoor temperature ff) 68 75 Elevation 4741 ft W-'FBWh Design TD (°F) 74 14 Latitude: 44°N n Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 57.0 -31.5 Dry bulb(°F) -6 89 Infiltration: 5.03 2163 Daily range (T) - 34 (H ) Method Simplified 0.068 Wet bulb(°F) - 60 Construction quality Semi -loose 221 Wind speed (mph) 15.0 7.5 Fireplaces 0 5.03 Construction descriptions Walls 12E Osw : Frm wall, vnl ext, 3/8" wood shth , r-19 cav ins, 1/2" gypsum board int fish , 2'W" wood frm Partitions (none) Windows 61C: VINYL .35 U- VALUE; NFRC mted(SHGC=0.35) Doors 11 DO: 11 DO Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 cell ins, 1/2" gypsum board int fnsh OftPartCeit C part ceiling, carpet flr fnsh , frm flr, 12" thkns, 1/2" gypsum board int fnsh Floors 19A-Obscp: Part floor, carpet flr fnsh , fnn flr, 12" thkns, 1/2" gypsum boardintfnsh 22A-vpl: Bg floor, light dry soil, vinyl flr fnsh Or Area LLvalue Insul R Htg HTM Loss Clg HTM Gain 0.350 N BWh -F W-'FBWh BW W Btuh BWhW awn n 299 0.068 19.0 5.03 1505 0.64 191 e 430 0.068 19.0 5.03 2163 0.64 275 S 345 0.068 19.0 5.03 1736 0.64 221 w 5 0.068 19.0 5.03 23 0.64 3 all 1078 0.068 19.0 5.03 5426 0.64 689 n 71 0.350 0 25.9 1839 11.5 820 s 39 0.350 0 25.9 1008 20.6 804 all 110 0.350 0 25.9 2847 14.8 1624 n 35 0 0 0 0 0 0 s 21 0 0 0 0 0 0 all 56 0 0 0 0 0 0 625 0.026 38.0 1.92 1202 1.09 682 11 0.221 0 16.4 184 9.29 105 10 0.295 0 8.20 81 1.55 15 64 0.989 0 73.2 4684 0 0 $ .4!2tj. WrfOffttsoTt. Right U nivers al 7.1.03 RSU 06972 2012 -Nov -1606:23:18 CADomments and Settings \ROBERT HALL \My Documents \Wrightwfl HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 4 Component Constructions UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, 10 834442 Phone: 745-8468 For. 2 -CARE PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Construction descriptions Design Area U -value Insul R Location: Loss Indoor: Heating Cooling Idaho Falls, ID, US ff Indoor temperature ff) 68 75 Elevation 4741 ft BfuW Design TD (°F) 74 14 Latitude: 44°N 625 Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 57.0 -31.5 Dry bulb(°F) -6 89 Infiltration: 1357 0.64 Daily range (*F) - 34 (H ) Method Simplified 0.068 Wet bulb(°F) - 60 Construction quality Semi -loose 209 Wind speed (mph) 15.0 7.5 Fireplaces 0 19.0 Construction descriptions or Area U -value Insul R Htg HTM Loss Clg HTM Gain all 128 0.350 ff BWI4 'F T.Btuh BWW Btuh BfuW BtA Walls 0 0 625 0.026 38.0 16 0.221 0 12EOsw: Finn wall, vnl ext, 3/8"wood shth , r-19 cav ins, 1/2" It 270 0.068 19.0 5.03 1357 0.64 172 gypsum board int fnsh , 2"x6" wood frm a 326 0.068 19.0 5.03 1642 0.64 209 S 325 0.068 19.0 5.03 1635 0.64 208 w 702 0.068 19.0 5.03 3531 0.64 449 all 1623 0.068 19.0 5.03 8166 0.64 1037 Partitions (none) Windows 61 C: VINYL .35 U- VALUE; NFRC rated(SHGC-0.35) Doors 11 DO: 11 DO Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 veil ins, 1/2' gypsum board int fish DftPartCeit C part ceiling, carpet flr fnsh , frm fir, 12" thims, 1/2" gypsum board int fnsh Floors 19A-Obscp: Part floor, carpet flr fnsh , fnn fir, 12" thims, 1/2" gypsum board int fnsh 22A-vpl: Bg floor, light dry soil, vinyl flr fnsh n 71 0.350 0 S 32 0.350 0 w 25 0.350 0 all 128 0.350 0 n 35 0 0 s 21 0 0 all 56 0 0 625 0.026 38.0 16 0.221 0 22 0.295 0 114 0.989 0 �tiwriyltltYO?t' Right -Suited, U niversa17.1.03 RSU 06972 A05K C:\Documents and Settings \ROBERT HALL \ My Documents \Wrightsoft HVAC 12 -CAR 6-PLEX UNITS 1-3.mp Cal 25.9 1839 11.5 820 25.9 829 20.6 661 25.9 648 37.7 941 25.9 3315 18.9 2422 0 0 0 0 0 0 0 0 0 0 0 0 1.92 1202 1.09 682 16.4 260 9.29 147 8.20 177 1.55 33 73.2 8325 0 0 2012 -Nov -16 08:23:18 Page 5 Component Constructions UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD. RIGBY, ID 834442 Phone: 745-8468 For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Location: Cooling Indoor: Idaho Falls, ID, US 74 Indoor temperature ff) Elevation 4741 ft 50 Design TD (°F) Latitude: 44°N Simplified Relative humidity(a/a) Outdoor: Heating Cooling Moisture difference(grnb) Dry bulb ff) -6 89 Infiltration: Daily range (°F) - 34 (H ) Method Wet bulb (*F) - 60 Construction quality Wind speed (mph) 15.0 7.5 Fireplaces Construction descriptions Walls 12 EOsw : Frm wall, vnl ext, 3/8" wood shth , r-19 cav ins, 1/2" gypsum board int fnsh , 2"x6" wood fnn Partitions (none) Windows 61C: VINYL .35 U- VALUE; NFRC rated(SH1300.35) Doors 11 DO:11 DO Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" gypsum board int fnsh DftPartCeit C part ceiling, carpet fir fish , frm flr, 12" thkns, 1/2" gypsum board int fnsh Floors 19A-Obscp: Part floor, carpet flr fish , fnn fir, 12" thkns, 1/2" gypsum board int fish 22A-vpl: Bg floor, light dry soil, vinyl flr fnsh Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Heating Cooling 68 75 74 14 50 50 57.0 31.5 Simplified T--'FBWh Semi -loose BWh 0 BWh Or Area U -value Insul R Htg HTM Loss Clg HTM Gain 0.350 R BWh -F T--'FBWh BWW BWh BWW BWh n 256 0.068 19.0 5.03 1288 0.64 164 s 284 0.068 19.0 5.03 1430 0.64 182 w 227 0.068 19.0 5.03 1144 0.64 145 all 767 0.068 19.0 5.03 3861 0.64 491 In 60 0.350 0 25.9 1554 11.5 693 S 46 0.350 0 25.9 1188 20.6 947 all 106 0.350 0 25.9 2742 15.5 1640 n 35 0 0 0 0 0 0 s 21 0 0 0 0 0 0 all 56 0 0 0 0 0 0 625 0.026 38.0 1.92 1202 1.09 682 11 0.221 0 16A 184 9.29 105 8 0.295 0 8.20 69 1.55 13 52 0.989 0 73.2 3769 0 0 Qy w+�.V1/. Right Suite® Universal7.1.03 RSU 06972 2012 -Nov -1608:23:18 AC.T.7\ C:\Documents and Settings \ROBERT HALL \My Documents \WdghMoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 6 Com onent Constructions Job: 2-CARrrPLEX p Date: NOV,12,201212 UNIT C By: ROBERT HALL KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Project Information For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Location: Or Indoor: Heating Cooling Idaho Falls, ID, US Loss Indoor temperature (T) 68 75 Elevation 4741 ft V Design TD (°F) 74 14 Latitude: 44°N Btuw Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 57.0 31.5 Dry bulb (T) -6 89 Infiltration: n 299 Daily range (T) - 34 (H ) Method Simplified 0.64 Wet bulb (T) - 60 Construction quality Semi -loose 0.068 Wind speed (mph) 15.0 7.5 Fireplaces 0 275 Construction descriptions Or Area LLvalue Insul R Htg HTM Loss Cig HTM Gain 0 25.9 V B.W--'F T.'Fatah BMW Btuh Btuw BWh Walls 14.8 1624 n 35 0 0 0 0 0 12E-Osw : Fnn wall, vnl ext, 3/8"wood shth , r-19 cav ins, 1/2' n 299 0.068 19.0 5.03 1505 0.64 191 gypsum board int fnsh , 2"x6" wood firm a 430 0.068 19.0 5.03 2163 0.64 275 1.92 s 345 0.068 19.0 5.03 1736 0.64 221 9.29 w 5 0.068 19.0 5.03 23 0.64 3 64 all 1078 0.068 19.0 5.03 5426 0.64 689 Partitions (none) Windows 61 C: VINYL .35 U- VALUE; NFRC rated(SHGCP0.35) Doors 11 D0:11 W Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 mil ins, 1/2" gypsum board int fnsh DftPartCeit C part ceiling, carpet fir fish , fnn fir, 12" thkns, 1/2" gypsum board int fnsh Floors 19A-Obscp: Part floor, carpet fir fish , frm flr, 12" thkns, 1/2" gypsum board int fnsh 22A-vpl: Bg floor, light dry soil, vinyl flr fnsh n 71 0.350 0 25.9 1839 11.5 820 s 39 0.350 0 25.9 1008 20.6 804 all 110 0.350 0 25.9 2847 14.8 1624 n 35 0 0 0 0 0 0 s 21 0 0 0 0 0 0 all 56 0 0 0 0 0 0 625 0.026 38.0 1.92 1202 1.09 682 11 0.221 0 16.4 184 9.29 105 10 0.295 0 8.20 81 1.55 15 64 0.989 0 73.2 4684 0 0 r4 •#}I' Wrlphtsof - Right Suite® U niversal 7.1.03 RSUG6972 2012 -Nov -1608:23:18 iR.C.T C:\Documents and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 7 Project Summary Entire House KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 934442 Phone: 745-8468 Project Information For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Notes: BUILDING FACES EAST Design Information Winter Design Conditions Outside db Inside db Design TO Idaho Falls, ID, US -6 OF 68 OF 74 OF Heating Summary Outside db Structure 64270 Btuh Ducts 0 Btuh Central vent(164 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Stuh Equipment load 64270 Btuh Infiltration Method Outside db Simplified Construction quality Inside db Semi -loose Fireplaces Design TD 0 OF Heating Cooling Area (ftz) 3757 3757 Volume (fF) 33812 33812 Air changes/hour 0.43 0.23 Equiv.AVF(cfm) 242 130 Heating Equipment Summary Make n/a Coil n/a Trade n/a ARI ref no n/a Model n/a Efficiency GAMA ID n/a n/a Sensible cooling Efficiency Btuh n/a Heating input Btuh Total cooling Heating output Btuh 0 Btuh Temperature rise cfm 0 OF Actual air flow cfmBtuh 0 cfm Air flow factor in H2O 0 cfm/Btuh Static pressure 0 in H2O Space thermostat n/a Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Summer Design Conditions Outside db 89 OF Inside db 75 OF Design TD 14 OF Daily range H Use manufacturers data Relative humidity 50 % Moisture difference -31 grAb Sensible Cooling Equipment Load Sizing Structure 20784 Btuh Ducts 0 Btuh Central vent(164 cfm) 0 Btuh Blower 0 Btuh Use manufacturers data In Btuh Rate/swing multiplier 0.94 ton Equipment sensible load 19537 Btuh Latent Cooling Equipment Load Sizing Structure -1451 Btuh Ducts 0 Btuh Central vent(164 cfm) 0 Btuh Equipment latent load 0 Btuh Equipment total load 19537 Btuh Req. total capacity at0.70 SHR 2.3 ton Cooling Equipment Summary Make n/a Trade n/a Cond n/a Coil n/a ARI ref no n/a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfmBtuh Static pressure 0 in H2O Load sensible heat ratio 0 Printout certified by ACCA to meet all requirements of Manual 8th Ed �4J&-wwbg enc&r Right -suite® Universal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 CiDocumems and Settings \ROBERT HALL 1My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 1 Project Summary UNIT A FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR 6. PLEX Date: NOV,12,2012 By: ROBERT HALL For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Notes: BUILDING FACES EAST Design Information Idaho Falls, ID, US Winter Design Conditions Summer Design Conditions Outside db -6 OF Outside db 89 OF Inside db 68 OF Inside db 75 OF Design TD 74 OF Design TD 14 OF Daily range H Relative humidity 50 % Moisture difference -31 grAb Heating Summary Sensible Cooling Equipment Load. Sizing Structure 28967 Btuh Structure 9901 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent(21 cfm) 1447 Btuh Central vent(21 cfm) 274 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 30415 Btuh Use manufacturers data In Ratelswing multiplier 0.94 Infiltration Equipment sensible load 9564 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Semi -loose Fireplaces 0 Structure -178 Btuh Ducts 0 Btuh Heating Cooling Central vent(21 cfm) 381 Btuh Area(f') 1253 1253 Equipment latent load 0 Btuh Volume (fP) 11277 11277 Air changes/hour 0.59 0.31 Equipment total load 9564 Btuh Equiv. AVF(cfm) 110 59 Req. total capacity atO.70 SHR 1.1 ton Heating Equipment Summary Cooling Equipment Summary Make Intl Comfort Products Make Inrl Comfort Products Trade Tempstar Trade 13 SEER N Series R41 OA AC Model N9MP2050B12** Cond N4A318A(G)KA1* GAMA ID 70304 Coil ED*4X246**+TD1 ARI ref no 782995 Efficiency 90 AFUE Efficiency 13 SEER Heating input 50000 Btuh Sensible cooling 12390 Btuh Heating output 44000 Btuh Latent cooling 5310 Btuh Temperature rise 72 OF Total cooling 17700 Btuh Actual air flow 660 cfm Actual air flow 660 cfm Air flow factor 0.023 cfm/Btuh Air flow factor 0.067 GfmBtuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 Bold /italic values have been manually ownridden Printout certified by ACCA to meet all requirements of Manual ath Ed -l�i-yyriphtaoTt- Right Suite® U niv am at 7.1.03 RSU 06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Doaments \Wrightso8 HVAC \2 -CAR 6-PLEX UNITS 1J.mp Cal Page 2 Project Summary UNIT B FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-6468 Project For. 2 -CARE PLEX KARTCHNER HOMES REXBURG Notes: BUILDING FACES EAST DesicIn Information Idaho Falls, ID, US Winter Design Conditions Outside db -6 OF Inside db 68 OF Design TD 74 OF Heating Summary Daily range Structure 15697 Btuh Ducts 0 Btuh Central vent(36 cfm) 2428 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 18125 Btuh Infiltration Method Simplified Construction quality Semi -loose Fireplaces 0 Heating Cooling Area(fF) 1253 1253 Volume (ft+) 11274 11274 Air changes/hour 0.30 0.16 Equiv.AVF(cfm) 57 30 Heating Equipment Summary Make Intl Comfort Products Trade Tempstar Model N9MPD040F08 GAMA ID 272480 Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 92.1 AFUE 40000 Btuh 37000 Btuh 61 OF 660 cfm 0.042 cfm/Btuh 0.70 in H2O Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Summer Design Conditions Outside db 89 OF Inside db 75 OF Design TD 14 OF Daily range H Use manufacturer's data Relative humidity 50 % Moisture difference 31 gr/Ib Sensible Cooling Equipment Load Sizing Structure 7205 Btuh Ducts 0 Btuh Central vent(36 cfm) 459 Btuh Blower 0 Btuh Use manufacturer's data n Air flow factor Rate/swing multiplier 0.94 Cond N2A318A(G)KC* Equipment sensible load 7204 Btuh Latent Cooling Equipment Load Sizing Structure -544 Btuh Ducts 0 Btuh Central vent(36 cfm) -639 Btuh Equipment latent load 0 Btuh Equipment total load 7204 Btuh Req. total capacity at0.70 SHR 0.9 ton Cooling Equipment Summary Make Inrl Comfort Products Air flow factor Trade 13 SEER N SERIES R2 AC cfm/Btuh Cond N2A318A(G)KC* 0.70 Coil EB*2X246**++AGKSAPX01 Load sensible heat ratio ARI ref no 3317594 Efficiency 13 SEER Sensible cooling 11900 Btuh Latent cooling 5100 Btuh Total cooling 17000 Btuh Actual air flow 660 cfm Air flow factor 0.092 cfm/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 1.00 Sold /italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual 8th Ed -rl� wrr•p6laplrC' Right SuiteO U niv am at 7.1.03 RSU 06972 2012 -Nov -1608:23:16 CADocuments and Settings \ROBERT HALL \My Do ments \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page Project Summary UNIT C FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 For. 2-CAR6 PLEX, KARTCHNER HOMES REXBURG Notes: BUILDING FACES EAST Design Information Weather. Winter Design Conditions Outside db -6 °F Inside db 68 °F Design TD 74 °F Heating Summary H Structure 19606 Btuh Ducts 0 Btuh Central vent(25 cfm) 1721 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 21327 Btuh Infiltration Idaho Falls, ID, US Method Simplified Construction quality Semi -loose Fireplaces 0 Heating Cooling Area (ft) 1251 1251 Volume (fl') 11261 11261 Air changesthour 0.40 022 Equiv.AVF(cfm) 76 41 Heating Equipment Summary Make Intl Comfort Products Trade Tempstar Model N9MP205OB12** GAMA ID 70304 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 90 AFUE 50000 Btuh 44000 Btuh 72 *F 660 cfm 0.034 cfm/Btuh 0.70 in H2O Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Summer Design Conditions Outside db 89 °F Inside db 75 *F Design TD 14 *F Daily range H Use manufacturer's data Relative humidity 50 % Moisture difference -31 grAb Sensible Cooling Equipment Load Sizing Structure 3873 Btuh Ducts 0 Btuh Central vent(25 cfm) 326 Btuh Blower 0 Btuh Use manufacturer's data n Btuh Rate/swing multiplier 0.94 ton Equipment sensible load 3946 Btuh Latent Cooling Equipment Load Sizing Structure -729 Btuh Ducts 0 Btuh Central vent(25 cfm) -453 Btuh Equipment latent load 0 Btuh Equipment total load 3946 Btuh Req. total capacity at0.70 SHR 0.5 ton Cooling Equipment Summary Make Infl Comfort Products Trade 13 SEER N SERIES R2 AC Cond N2A318A(G)KC* Coil EB*2X246**++AGKSAPYAI ARI ref no 3317594 Efficiency 13 SEER Sensible cooling 11900 Btuh Latent cooling 5100 Btuh Total cooling 17000 Btuh Actual air flow 660 cfm Air flow factor 0.170 cfm/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 1.00 Bold /italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual 8th Ed. -VJ*- w spiI l V*- Right-SuiteGJUnive.a17.1.03 RSU06972 2012 -Nov -1608:23:18 �.L?. C:\Documents and Settings \ROBERT HALL \My Documents \Wnghtsofl HVAC \2 -CAR 6-PLEX UNITS 1-3.mg Cal Page 4 Project Summary UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 755-6466 Project• For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Notes: BUILDING FACES EAST Design Information Weather. Idaho Falls, ID, US Winter Design Conditions Outside db Inside db Design TD -6 'F 68 °F 74 °F Heating Summary Outside db Structure 28967 Btuh Ducts 0 Btuh Central vent(21 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 28967 Btuh Infiltration Method Outside db Simplified Construction quality Inside db Semi -loose Fireplaces Design TD 0 'F Heating Cooling Area (ft) 1253 1253 Volume (ft') 11277 11277 Air changes/hour 0.59 0.31 Equiv.AVF(cfm) 110 59 Heating Equipment Summary Make n/a Coil n/a Trade n/a ARI ref no n/a Model n/a Efficiency GAMA ID n/a n/a Sensible cooling Efficiency Btuh n/a Heating input Btuh Total cooling Heating output Btuh 0 Btuh Temperature rise cfm 0 °F Actual air flow cfm/Btuh 0 cfm Air flow factor in H2O 0 cfmBtuh Static pressure 0 in H2O Space thermostat n/a Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Summer Design Conditions Outside db 89 'F Inside db 75 °F Design TD 14 'F Daily range H Use manufacturer's data Relative humidity 50 % Moisture difference -31 grAb Sensible Cooling Equipment Load Sizing Structure 10921 Btuh Ducts 0 Btuh Central vent(21 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Btuh Rate/swing multiplier 0.94 ton Equipment sensible load 10266 Btuh Latent Cooling Equipment Load Sizing Structure -178 Btuh Ducts 0 Btuh Central vent(21 cfm) 0 Btuh Equipment latent load 0 Btuh Equipment total load 10266 Btuh Req. total rapacity at0.70 SHR 1.2 ton Cooling Equipment Summary Make n/a Trade n/a Cond n/a Coil n/a ARI ref no n/a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 Printout certified by ACCA to meet all requirements of Manual 8th Ed ,1 4$11- wrfy,.1[wT[- Right Suite® Universa17.1.03 RSU06972 2012 -Nov -1608:23:18 .KA.P C:\Documents and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC Q -CAR 6-PLEX UNITS 1-3.mp Cal Page 5 Project Summary UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Notes: BUILDING FACES EAST Design Information Idaho Falls, ID, US Winter Design Conditions Summer Design Conditions Outside db -6 OF Outside db 89 OF Inside db 68 OF Inside db 75 OF Design TO 74 OF Design TO 14 OF Daily range H Relative humidity 50 % Moisture difference 31 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 15697 Btuh Structure 8419 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent(36 cfm) 0 Btuh Central vent(36 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 15697 Btuh Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load 7914 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Semi -loose Fireplaces 0 Structure -544 Btuh Ducts 0 Btuh Heating Cooling Central vent(36 cfm) 0 Btuh Area(fa) 1253 1253 Equipment latent load 0 Btuh Volume(f3) 11274 11274 Airchanges/hour 0.30 0.16 Equipment total load 7914 Btuh Equiv. AVF(cfm) 57 30 Req. total capacity at0.70 SHR 0.9 ton Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a GAMA ID n/a Coil n/a ARI ref no n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 OF Total cooling 0 Btuh Actual air flow 0 Cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 Printout certified by ACCA to meet all requirements of Manual ath Ed. yyr•Q••[Sp{t RigIeSuit0)Unwema17.1.03 RSU06972 2012 -Nov -1608:23:18 CADocuments and Settings \ROBERT HALL \My Documents \Wdghlso8 HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 6 Project Summa Job: 2-CAR6 PLEX 1 Summary Date: NOV,12,2012 UNIT C By: ROBERT HALL KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Project• • For. 2-CAR6 PLEN KARTCHNER HOMES REXBURG Notes: BUILDING FACES EAST Design Information Idaho Falls, ID, US Winter Design Conditions Outside db -6 °F Inside db 68 OF Design TO 74 OF Heating Summary Heating Structure 19606 Btuh Ducts 0 Btuh Central vent(25 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 19606 Btuh Infiltration Method Outside db Simplified Construction quality 75 OF Semi -loose Fireplaces Daily range 0 Relative humidity Heating Cooling Area (f 2) 1251 1251 Volume (f) 11261 11261 Air changes/hour 0.40 0.22 Equiv.AVF(cfm) 76 41 Heating Equipment Summary Make n/a Coil n/a Trade n/a ARI ref no n/a Model n/a Efficiency GAMA ID n/a n/a Sensible cooling Efficiency Btuh n/a Heating input Btuh Total cooling Heating output Btuh 0 Btuh Temperature rise cfm 0 OF Actual air flow cfmBtuh 0 cfm Air flow factor in H2O 0 cfmBtuh Static pressure 0 in H2O Space thermostat n/a Summer Design Conditions Outside db 89 OF Inside db 75 OF Design TD 14 OF Daily range H Relative humidity 50 % Moisture difference -31 grflb Sensible Cooling Equipment Load Sizing Structure 5002 Btuh Ducts 0 Btuh Central vent(25 cm) 0 Btuh Blower 0 Btuh Use manufacturer's data In Btuh Ratelswing multiplier 0.94 ton Equipment sensible load 4702 Btuh Latent Cooling Equipment Load Sizing Structure -729 Btuh Ducts 0 Btuh Central vent(25 dm) 0 Btuh Equipment latent load 0 Btuh Equipment total load 4702 Btuh Req. total capacity at0.70 SHR 0.6 ton Cooling Equipment Summary Make n/a Trade n/a Cord n/a Coil n/a ARI ref no n/a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfmBtuh Static pressure 0 in H2O Load sensible heat ratio 0 Printout certified by ACCA to meet all requirements of Manual 8th Ed. 1'-s -Iii-wriphtsoft- Righi Suite® Universal 7.1.03 RSU06972 2012 -Nov -1608:23:18 iK.I.A C:\D=nnerna and Settings \ROBERT HALL \My Documents \Wnghtsofl HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 7 Right -JO Worksheet Entire House KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name Entire House UNIT 8 FURNACE 2 Exposed wall 442.3 It 103.3 It 3 Ceiling height 9.0 It d 9.0 It d 4 Room dimensions 5 Room area 3756.9 It' 1252.7 ft2 Ty C mb.r ten number U -value (Btuh MZF) Or I HTM (Btuh/ft') Area (ft') or perimeter (ft) I Load (Bt h) Area (ft2) ar perimeter (ft) Load (Btuh) Herat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool r1 6 0.068 n 5.03 0.64 1732 825 4150 527 351 256 1288 164 61C 61C 0.350 n 25.90 17.55 202 0 5232 2332 60 0 1554 693 7100 0.000 n 0.00 0.00 705 105 0 0 35 35 0 0 W 12E-0sw 0.068 a 5.03 0.64 756 756 3804 483 0 0 0 0 17 12E-0sw 0.068 s 5.03 0.64 1134 954 4802 610 351 264 1430 182 61C 0.350 s 25.90 20.65 117 0 3025 2411 46 0 1188 947 1100 0.000 s 0.00 0.00 63 63 0 0 21 21 0 0 12EOm 0.068 w 5.03 0.64 959 934 4697 597 227 227 1144 145 61C 0.350 w 25.90 37.65 25 0 647 941 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 1875 1875 3607 2047 625 625 1202 682 C DftPartCeii 0.221 16.37 9.29 38 38 628 357 11 11 184 105 F 19A-0bscp 0.295 - 8.20 1.55 40 40 328 62 8 8 69 13 F 22Awpl 0.989 - 73.19 0.00 1882 229 16778 0 628 52 3769 0 6 c) AED exwusion 540 283 Envelope loss /gain 47698 10907 17828 3213 12 a) Infi ration 16572 16773869 392 J) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 4 1000 0 0 Appliances @ 1800 4 7200 2 3600 Subtotal (lines 6 t 13) 64270 20784 15697 7205 0 0 0 0 0 0 0 0 =tnb,.n 0 0 0 -0 M270 20784 15697 7205 0% 01 0 0 0% 0% 0 0 TAotalru 6419287001 223521 1$6601 7205 ed (cfm) I I I I 6601 Printout certified by ACCA to meet all requirements of Manual 8[h Ed. w{+- v�rNptilwoR- Right Suite® U nNemal 7.1.03 RSU 06972 2072 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 1 Right -J@ Worksheet Entire House KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name UNIT A FURNACE UNIT C FURNACE 2 i Exposed all 200.8 ft 138.3 ft 3 Ceiling height 9.0 It d 9.0 It d 4 Room dimensions 5 Room area 1253.0 ft' 1251.2 ft' Ty Construction U -value Or I HTM I Area (ftp I Load I Area (ft 2) I Load number (Btuh/ft;°F)I (Blah/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool IIF —�I 6 12EOaw 0.068 n 5.03 0.64 376 270 1357 172 405 299 1505 191 61C 0.350 n 25.90 11.55 71 0 1839 820 71 0 1839 820 11D0 0.000 n 0.00 0.00 35 35 0 0 35 35 0 0 W 12E-0sw 0.068 a 5.03 0.64 326 326 1642 209 430 430 2163 275 11 12E-0sw 0.068 s 5.03 .0.64 378 325 1635 208 405 345 1736 221 61C 0:350 s 25.90 20.65 32 0 829 661 39 0 1008 804 11DO 0.000 s 0.00 0,00 21 21 0 0 21 21 0 0 12E-0sw 0.068 w 5.03 0.64 727 702 3531 449 5 5 23 3 t --G 61C 0.350 w 25.90 37.65 25 0 647 941 0 0 0 0 C 16BJ8ad 0.026 1.92 1.0,9 625 625 1202 682 625 625 1202 682 C DftPartCeil 0.221 16.37 9.29 16 16 260 147 11 11 184 105 F 19A-0bscp 0.295 - 8.20 1.55 22 22 177 33 10 10 81 15 F 22A�pl 0.989 - 73.19 0.00 628 114 8325 0 626 64 4684 0 61 c)AED excursion 218 233 Envelope loss /gain 21445 4540 14425 3348 12 a) Infiltration 7522 761 5180 524 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 4 10110 0 0 Appliances @ 1800 2 3600 0 0 Subtotal (lines 6 to 13) 28967 9901 19606 3873 Less e,lemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -0 0 0 0 14 Subtotal 28967 9901 19606 3873 15 Duct loads 0% 0% 0 0 0% 0% 0 0 286667 96601 766006 36873 Airlreq retl (adcfm) I I 01 I I 1 601 Printout certified by ACCA to meet all requirements of Manual 8th Ed. -�{+ wrr^iolscroR• Right Suite® Univema17.1.03 RSU06972 2012 -Nov .16 08:23:18 C:\Documents and Settings \ROBERT HALL\My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page Right -JO Worksheet UNIT A FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR G PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name UNIT A FURNACE UNIT 2 Exposed wall 200.8 ft 200.8 It 3 Ceiling height 9.0 It d 9.0 It p 4 Room dimensions 5 Room area 1253.0 ft2 1253.0 ft2 Ty Construction Or I HTM I Area (ft') I Load I Area (ft') I Load number I (BtU-value uh/ft;'F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VL12E-0sw 0.068 n 5.03 0.64 376 270 1357 172 376 2701357 172 61C 0:350 n 25.90 11.55 71 0 1839 820 71 0 1839 820 11D0 0.000 n .0.00 0.00 35 35 0 0 35 35 0 0 W 12E-0.0.068 a 5.03 0.64 326 326 1642 209 326 326 1642 209 11VL12E-0sw 0.068 s 5.03 0.64 378 325 1635 208 378 325 1635 208 61C 0.350 s .25.90 20.65 32 0 829. 661 32 0 829 661 11D0 0.000 s 0.00 0.00 21 21 0 0 21 21 0 0 t 12E-0sw 0.068 w 5.03 0.64 727 702 3531 449 727 702 3531 449 -361C 0.350 w 25.90 37.65 25 0 647 941 25 0 647 941 C 168-38ad 0.026 - 1.92 1.09 625 825 1202 682 625 625 1202 682 C OftPartCeil 0.221 - 16.37 9.29 16 16 260 147 16 16 260 147 F 19A-0bscp 0.295 8.20 1.55 22 22 177 33 22 22 177 33 F 22Avpl 0.989 - 73.19 0.00 628 114 8325 0 628 114 8325 0 6 c) AEDexcursion 218 1238 Envelope bss /gain 21445 4540 21445 5560 12 a) Infiltration 7522 761 7522 761 J) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 4 1000 4 1000 Appliances @ 1800 2 3600 2 3600 Subtotal (lines Etc 13) 28967 9901 28967 10921 ess e#emal load 0 0 0 0 estransfer 0 0 0 0 J edithbution -0 0 -0 -0 ubtotal 28967 9901 28967 10921 uct loads 0% 0% 0 0 0% 0% 0 0 286601 96601 28660I 10921 AotaVomdl l m) I I I I Printout certified by ACCA to meet all requirements of Manual 8th Ed Right Suite® U rivers.17.1.03 RSU 06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \ My Documents \Wrightsoft HVAC \2 -CAR 6-PLE%UNITS 1-3.rup Cal Page Right -J@ Worksheet UNIT B FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL 1 1 Room name UNIT B FURNACE UNIT B 2 Exposed wall 103.3 It 103.3 ft 3 Ceiling height 9.0 ft d 9.0 It p 4 Room dimensions 5 Room area 1252.7 W 1252.7 ft' Ty Constmction U -value Or HTM I Area (ft') I Load I Area (ft') I Load number (Stuh/ft'-°F)O (Btuh/ft') or penmeler (ft) (Btuh) or penmeter (ft) (Btuh) Heat Cool Gross N/PIS Heat Cool Gross N/P/S Heat Cool 6 T 0.068 n 5.03 351 256 1288 164 357 256 1288 164 � 61C 0.350 n 25.90 11.55 1.55 60 5 1554 693 60 0 1554 693 11C i1D0 0.000 n 0.00 0.00 35 35 0 0 35 35 0 0 W 12E-0sw 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 11 12E-0sw 0.068 s 5.03 0.64 351 284 1430 182 351 284 1430 182 61C 0.350 s 25.90 20.65 46 0 1188 947 46 0 1188 947 11DO 0.000 s 0.00 0.00 21 21 0 0 21 21 0 0 12E-0.0.068 w 5.03 0.64 227 227 1144 145 227 227 1144 145 t -G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 166-38ad 0.026 1.92 1.09 625 625 1202 682 625 625 1202. 682 C DftPartCeil 0.221 16.37 9.29 11 11 184 105 11 11 184 105 F 19A-0bscp 0.295 - 8.20 1.55 8 8 69 13 8 8 69 13 F 22A+pl 0.989 - 73.19 0.00 628 52 3769 0 628 52 3769 0 6c)AED excursion 283 1498 Envelope lass /gain 11828 3213 17828 4428 12 a) Infiltration 3869 392 3869 392 b) Room ventilation 0 0 0 0 13 Internal gains : Occupants @ 250 0 0 0 0 Appliances @ 1800 2 3600 2 3600 Subtotal (lines 6 to 13) 15697 72051 15697 8419 Lessexternal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 -0 0 0 14 Subtotal 15697 7205 15697 8419 15 Duct loads 0% % 0 0 0% 0% 0 0 oad 156601 7�0I I I i5697 87791 Airt'equvedl (ohm ) I 6601 Printout certified by ACCA to meet all reauirements of Manual 8th Ed -/�+ wriOhc�o1R- Right-SuileOUnivemal7.1.03 RSU06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page Right -J@ Worksheet UNIT C FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name UNIT C FURNACE UNIT 2 Exposed wall 138.3 It 138.3 ft 3 Ceiling height 9.0 It d 9.0 ft p 4 Room dimensions 5 Room area 1251.2 fl' 1251.2 ft' Ty Construction U -value OrHTM Area (ftp I Load I Area (ft') I Load number (Btuh/ft?°F) I Stuh/ft') I or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 T O.B n 5.03 064 405 299 1505 191 405 299 1505 191 YL0.06812E.Om 61C 9.350 n 25.90 11.55 71 0 1839 820 71 0 1839 820 I�—__—_DG 11 D0 0.000 n 0.00 0.00 35 35 0 0 35 35 0 0 W 12E4)sw 0.068 a 5.03 0.64 430 430 2163 275 430 430 2163 275 11 12E-0sw 0.068 s 5.03 0.64 405 345 1736 221 405 345 1736 221 61C 0.350 s 2590 2065. 39 0 1008 806 39 0 1008 am 11 D0 0.000 s. 0.00 000 21 21 0 0 21 21 0. 0 4y 12E-0aw 0.068 w 5.03 0.64 5 5 23 3 5 5 23 3 `G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 168-38ad 0.026 - 1:92 1109 625 625 1202 682 625 625 1202 682 C DBPartceil 0.221 - 16.37 9.29 11 11 184 105 11 11 184 105 F 19A-Obscp 0.295 - 8.20 1.55 10 10 81 15 10 10 81 15 F 22Avpl 0.989 - 73.19 0.00 626 64 4684 0 626 64 4684 0 6 c) AED excursion 23 3 1362 Envelope loss /gain 14425 3348 14425 44 77 12 a) Infiltration 5180 524 5180 524 J) Roomventilatiion 0 0 0 0 13 Internal gains: Occupants @ 2500 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 19606 3873 1 19606 5002 Less external load 0 0 0 0 Leas transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19606 3873 19606 5002 15 Duct loads 0% 0%0 0 0% 0% 0 0 drn 19�0I 852 1660 AotaeQuom�l ( ) I 66701 I I I 1 Printout certified by ACCA to meet all requirements of Manual 8th Ed Right-Suite®Univereal7.1.03 RSU06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 5 - Right -J@ Worksheet Job: 2 -CAR 6-PLEX UNIT A Date: NOV,12,2012 By: ROBERT HALL KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8466 1 Room name UNITA STORAGE 2 Exposed wall 200.8 ft 9.0 ft 3 Ceiling height 9.0 ft p 9.0 ft heat/cool 4 Room dimensions 3.8 x 4.5 ft 5 Room area 1253.0 ft2 16.9 ft2 Ty Construc8on U-valueOr I HTM I Area (ft2) I LoadI Area (ft2 I Load) number (Btuh/ft'F) ( Stub/ft2) ft) or perimeter (ft) pe (Btuh) or perimeter (ft) (Btuh Heat I Cool Gross N/P/S Heat Cool Grass N/P/S Heat Cool f-1 6 4y 12E-0sw 0.068 n 5.03 0.64 376 270 1357 172 0 0 0 0 {LSD 61C 0.350 n 25.90 11.55 71 0 1839 820 0 0 0 0 11DO 0.000 n 0.00 0.00 35 35 0 0 0 0 0 0 W 12E-0sw 0.068 a 5.03 0.64 326 326 1642 209 38 38 192 24 N w 12E-0sw 0.068 s 5.03 0.64 376 325 1635 208 2 2 11 1 (--G 61C 0.350 s 25.90 20.65 32 0 829 661 0 0 0 0 III --DDD 11D0. 0.000 s 0.00 .0.00 21 21 0 0 0 0 0 0 12E 0sw 0.068 w 5.03 0.64 727 702 3531 449 41 41 204 26 T ---G --G 61C 0.350 w 25.90 37.65 25 0 647 941 0 0 0 0 C 16B -38&d 0.026 - 1.92 1.09 625 625 1202 682 0 0 0 0 C DftPartCeil 0.221 16.37 9.29 16 16 260 147 1 1 18 10 F 19A-Obscp 0.295 - 8.20 1.55 22 22 177 33 0 0 0 0 F 22Avpl 0.989 - 73.19 0.00 628 114 8325 0 17 9 659 0 61c' AED excursion 1238 -4 Envelope loss /gain 21445 5560 1085 58 12 a) Infiltration 7522 761 337 34 b) Room ventilation 1 0 0 0 0 13 Internal gains: Occupants @ 250 4 1000 0 0 Appliances @ 1800 2 3600 0 0 SubW11al (lines 6 t 13) 28967 10921 1422 93 Leas exlemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -0 -0 -1422 -93 14 Subtotal 28967 10921 0 0 15 Duct loads 0% 0% 0 0 0% 0% 0 0 oad(dm) 28M70 107281 0 01O Alrtal�uved I I I I I 0I921 Printout Certified by ACCA to meet all reauirements of Manual 8th Ed. -� wesotilt�oR- Right -Suite® Universal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 CADocuments and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 6 RightM Worksheet UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , 10 834442 Phone: 745-5468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name MUD STAIRS 2 Exposed all 4.5 ft 3.0 ft 3 Ceiling height 9.0 ft heat/mot 9.0 ft heat/cool 4 Room dimensions 3.0 x 4.5 ft 1.0 x 33.8 ft 5 Room area 13.5 ft' 33.8 ft' Ty Construction U -value Or I HTM I Area (ft 2) I Load I Area (ft') I Load number (Bluh/ft°%° (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Stuh) Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12E-0sw 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 �G 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 I -D 11D0 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E -05w 0.068 a 5.03 0.64 2 2 11 1 0 0 0 0 11 12E -0m 0.068 s 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 11DO 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 W 12EOsw 0.068 w 5.03 0.64 38 38 192 24 27 27 136 17 `G 61C 0.350 w 25.90 37.65 0 0 0 0 0 0 0 0 C 16S-38ad 0.026 - 1.92 1.09 0 0 0 0 0 0 0 0 C DftPanceil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-06scp 0.295 8.20 1.55 0 0 0 0 0 0 0 0 F 22A�pl 0.989 - 73.19 0.00 14 5 329 0 34 3 220 0 6 c) AED excursion -2 -1 Envelopeloss /gain 533 24 1 1 355 16 12 a) Infiltration 16917 1 1 112 11 J) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 0 0 0 Appliances @ 1800 0 1 0 0 0 Subtotal (lines 6 t 13) 1 1 702 41 1 1 468 27 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -702 41 -468 -27 14 Subtotal 0 0 0 0 15 Duct loads 0% 0% 0 0 0% 0% 0 0 I At oZl(fm I 0 OI I I 01 OI Printout certified by ACCA to meet all requirements of Manual 8th Ed. ,gig -f{�- w.ao`rtsoet- Right Suite® Universal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 AGO. C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 7 Right -J® Worksheet UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name POWDER KIT/DINE/FAM 2 Exposed wall 4.3 ft 47.3 It 3 Ceiling height 9.0 It heat/cool 9.0 R heat/coot 4 Room dimensions 3.8 x 4.5 It 1.0 x 299.0 ft 5 Room area 16.9 ft' 299.0 V Ty Construction U -value Or I HTM I Area (fl0 I Load I Aa (ft 2) re I Load number (Btuhffi--F) (Btuh/ftp or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Grass N/P/S Heat Cool 612E0sw 0.068 n 5.03 0.64 0 0 0 0 178 113 567 72 Bic 0.350 n 25.90 11.55 0 0 0 0 30 0 T/7 346 11DO 0.000 n 0.00 0.00 0 0 0 0 35 35 0 0 W 12E0sw 0.068 a 5.03 0.64 0 0 0 0 63 63 317 40 11 W 12E-0sw 0.068 s 5.03 0.64 0 0 0 0 59 38 189 24 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 L�-p0 11DO 0.000 s 0.00 0.00 0 0 0 0 21 21 0 0 12E.0sw 0.068 w 5.03 0.64 38 38 192 24 126 126 634 81 t -G 61C 0.350 w 25.90 37.65 0 0 0 0 0 0 0 0 C 168-38ad 0.026 1.92 1.09 0 0 0 0 0 0 0 0 C DftPartCeil 0.221 16.37 9.29 0 0 0 0 4 4 57 33 F 19A-0bscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F 22Avpl 0.989 - 73.19 0.00 17 4 311 0 299 47 3458 0 6 c) AED excursion -2 39 Envelope loss /gain 504 23 5999 557 12 a) Infiltration 159 1 16 1771 179 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 2500 0 0 0 Appliances @ 1800 0 0 2 3600 Subtotal (lines 6 to 13) 1 663 39 1 1 77]0 4336 Less external bad 0 0 0 0 Less transfer 0 0 0 0 Redistribution -663 -39 10573 720 14 Subtotal 0 0 18343 5056 15 Duct loads 0% 0% 0 0 0% 0% 0 0 I room 184 53371 T A,r'neq redl (cfm) I I I 01 01 I I 8I Printout certified by ACCA to meet all reauirements of Manual 8th Ed. y{►wrrbbt�oR- Right SWWDUnivers.17.1.03 RSUG6972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Documents \Wdghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 8 Right -SR) Worksheet UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR f. PLEX Date: NOV,12,2012 By: ROBERT HALL 7 Room name MASTER BATH MASTERWIC 2 Exposed all 6.0 It 0 ft 3 Ceiling height 9.0 ft heat/cool 9.0 It heat/cool 4 Room dimensions 1.0 x 48.4 ft 1.0 x 33.2 ft 5 Room area 48.4 11233.2 ft2 Ty Construction U -value Or I HTM) I Area (ftp I Load) I Area (ft2) I Load number (Stuh/ft?°F ) ( Btuh/ft' or perimeter (ft) (Btuh or pedmeter ft ( ) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool r1 612E-0sw 0.068 n 5.03 0.64 54 38 191 24 0 0 0 0 )--G 61C 0.350 n 25.90 11.55 16 0 414 185 0 0 0 0 �D 11D0 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a 5.03 0.64 0 0 0 0 0 0 0 0 71 12E-0sw 0.068 s 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 s :25.90 20.65 0 0 0 0 0 0 0 0 71D0 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 t 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 -G 61C 0.350 w 25.90 37.65 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 1.92 1.09 48 48 93 53 33 33 64 36 C DRPartCeil 0.221 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - 8.20 1.55 - 3 3 25 5 0 0 0 0 F 22A+pl 0.989 - 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 61 -11 1 Envelope loss /gain 723 327 64 35 12 a) Infiltration 225 23 1 0 0 b) Room ventilation 0 0 1 0 0 13 Internal gains: Occupants @ 2500 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 948 350 64 35 ssexternalload 0000transfer0 0 0 0 TR':- distribution 0 0 226 56 ubtotal 948 350 290 91 uct loads 0% 0% 0 0 0% 0% 0 0 Aotal�ruired 3231 2901 961 (cfm) 1 X21 I 1 Printout certified by ACCA to meet all requirements of Manual 8th Ed. Right -Suite® Universal 7.1.03 RSU 06972 2012 -Nov -1608:2348 C:\Documents and Settings \ROBERT HALL \My Documents \Wdghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 9 Right -J® Worksheet UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name LAUNDRY MASTER BED 2 Exposed all 0 R 26.3 It 3 Ceiling height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 3.8 x 4.5 It 1.0 x 151.3 It 5 Room area 16.9 ft' 151.3 ft' Ty Construction�BU -value Or I HTM I Area (ft') I Lo atlI Area (ft') I Load number tuh/fta°F) (Btuh/ft') or perimeter (ft) (Bwh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool GrossN/P/S Heat Cool 6 T VL 12E-0sw 0.068 n 5.03 0.64 0 0 0 0 122 97 486 62 _L(D' 61C 0.350 n 25.90 11.55 0 0 0 0 25 0 647 289 11D0 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 ww 12E-0sw 0.068 a 5.03 0.64 0 0 0 0 7 7 34 4 71 12E-0sw 0.068 s 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 I� 11DO 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 108 83 418 53 LG 61C 0.350 w 25.90 3765 0 0 0 0 25 0 647 941 C 16B -Mad 0.026 - 1.92 1.09 17 17 32 18 151 151 291 765 C DftPartCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 8.20 1.55 0 0 0 0 15 15 125 24 F 22AVPI 0.989 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -7 509 Envelcpeloss /gain 32 18 2648 2047 12 a) Infiltration 0 0 984 100 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 0 2 500 Appliances @ 1800 0 0 0 0 Sublotal (lines filo 13) 32 18 3632 2646 Less eMemal load 0 0 0 Less transfer 0 0 0 Redistribution 32 -18 am 25 14 Subtotal 0 0 671 15 Ductloads 0% 0% 0 0 0% 0 oadI 26 d (cfm I I OI 0 Ir I 78Arqure1 1 Printout certified by ACCA to meet all reauirements of Manual a[h Ed. -�{+- wraatio-or't- Right -Suite® Universal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Documents \wdghtsoft HVAC \2 -CAR 6-PLEX UNITS 13.rup Cal Page 10 Right -J@ Worksheet UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , 10 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name UPPER STAIRS OPEN FROM ABOVE 2 Exposed all 0 ft 3.8 ft 3 Ceiling height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 1.0 x 31.5 ft 3.8 x 10.5 ft 5 Room area 31.5 ft' 39.4 ft2 Ty Construction U -value Or HTM Area (ft') I Load I Area (ft 2) I Load number (Btuh/t;'F) I Btuh /ft I or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross NIP/S Heat Cool 6 12E-0sw 0.068 _r n 5.03 0.64 0 0 0 0 0 0 0 0 SIC 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a 5.03 0.64 0 0 0 0 0 0 0 0 11VL212E-0w0.068 s 5.03 0.64 0 0 0 0 34 34 170 22 61C 0:350 s 25.90 20.65 0 0 0 0 0 0 0 0 Y1D0 0.000 s 0.00 0:00 0 0 0 0 0 0 0 0 W 1215 s 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 �G 61C 0.350 w 25.90 37.65 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 32 32 61 34 39 39 76 43 C DftPanCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F 22A+pl 0.989 - 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AEG excursion Envelope loss /gain 61 33 246 61 12 a) Infiltration 0 0 141 14 b) Roomventilation 0 0 01 0 13 Internal gains: Occupants @ 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 61 33 386 76 s external load 0 0 0 0 s transfer 0 0 0 0 [ER.dIsIn bution -61 -33 -386 -76 total0 0 0 0 tloads 0% 0% 0 0 0% 0% 0 0 Av relquved (dm) I I I OI 001 I I OI 0 Printout certified by ACCA to meet all recuirements of Manual 8th Ed. ^`�- -►{+- wriptif�of'c Right -Suite® Universa17.1.03 RSU06972 2012 -Nov -1608:23:18 AC -L9. CADocuments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 11 Right -J@ Worksheet UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD . RIGBY, ID 834442 Phone: 745-8488 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name UPPER BATH MECH 2 Exposed wall 7.5 It 4.5 It 3 Ceiling height 9.0 It heat/cool 9.0 It heat/cool 4 Room dimensions 4.5 x 7.5 It 4.5 x 4.5 ft 5 Room area 33.8 ft' 20.3 ft' Ty Construction U -value Or HTM I Area (ft) I Load I Area (ftp I Load I number (BNhM 'F) (Buh /ft ') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cool 612E-0sw 0.068 n I r 5.03 0.64 0 0 0 0 I 0 I 0 0 0 I --G 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 L -D 1100 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a 5.03 0.64 0 0 0 0 0 0 0 0 114y 12E-0sw 0.068 a 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 I� 1100 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 t 12E -0w 0.068 w 5.03 0.64 68 68 340 43 41 41 204 26 -C 61C 0.350 w 25.90 37.65 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 1.92 1.09 34 34 65 37 20 20 39 22 C DftPartCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 8.20 1.55 1 1 9 2 0 0 0 0 F 22Avpl 0.989 73.19 0.00 0 0 0 0 0 0 0 0 61 c) AED excursion 4 -3 Envelope loss /gain 413 77 1 243 45 12 a) Infiltration 281 28 1 1 169 17 J) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 01 ( 1 0 Appliances @ 1800 0 0 0 Subtotal (lines 6 to 13) 694 1 1061 1 1 411 62 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 251 54 -411 62 14 Subtotal 945 159 0 0 15 Dud loads 0% 0% 0 0 0% 0% 0 0 9221 1591 Air%cuo of. 1 I 1 1 1 O O Printout Certified bV ACCA to meet all requirements of Manual 8th Ed. Right Suite® UnNersal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 C:1Documents and Settings \ROBERT HALL \My Documents \Wdghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 12 Right -J@ Worksheet UNIT A KARTCHNER HOMES 797 CTnr.KMAN BLVD _ RIGBY. ID 834442 Phone: 745-8468 Job: 2- CAR G PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name BED 1 BED 2 2 Exposed wall 21.0 ft 18.0 ft 3 Ceiling height 9.0 R heat/cool 9.0 R heat/cool 4 Room dimensions 8.3 x 11.3 It 1.0 x 96.8 ft 5 Room area 82.8 R' 96.8 It Ty Construction U -value Or HTM I Area (ft') I Load I Area (R 2) I Load number (Btuh /ftx'F) I (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Bluh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6VL12E-0sw T 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 0 0 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12EOsw 0.068 a 5.03 0.64 14 14 68 9 95 95 476 60 71 12EOsw 0.068 a 5.03 0.64 74 58 293 37 68 52 259 33 61C 0.350. s 25.90 20.65 16 0 414 330 16 0 414 330 11DO 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 12EOsw 0.068 w 5.03 0.64 101 101 509 65 0 0 0 0 61C 0.350 w 25.90 37.65 0 0 0 0 0 0 0 0 C. 16B-38ad 0.026 - 7:92 1.09 93 93 179 101 97 97 186 W6 C DtPartCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 0 0 F 19A-0bsop 0.295 - 8.20 1.55 0 0 0 0 0 0 0 F 22AIpl 0.989 - 73.19 0.00 0 0 0 0 0 0 0 6 c) AED excursion 376 377 Emdopeloss/gain id64 978 1335 906 12 a) Infftration 787 80 1 1 67468 J) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 1 250 1 1 1 1 250 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 2250 1248 1 1 2010 1224 Leas external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 228 42 272 79 14 Subtotal 2479 1290 2282 1303 15 Duct loads 0% 06 0 0 0% 0% 0 0 TAotau-am load 241 12861 I M2 13!03 13831 ed (clm) I I I Printout Certified by ACCA to meet all reauirements of Manual 8th Ed. -�'{+• ., Iil Right -Suite® U rivers al 7.1.03 RSU 06972 2012 -Nov -1608:23:18 CADocuments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.wp Cal Page 13 Right -J@ Worksheet UNIT A KARTCHNER HOMES 197 STOCKMAN BLVD RIGBY , 10 834442 Phone: 745-8468 Job: 2- CAR G PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name HALLWAY GARAGE 2 Exposed wall 0 ft 45.8 ft 3 Ceiling height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 1.0 x 60.8 ft 15.8 z 15.8 fl 5 Room area 60.8 V 248.1 ft2 T Ty Construction U -value Or HTM I Area (ft I Laatl I Area (ft') Load number (Btuh/ft'-°F) (BWh/fi 2) or Perimeter (ft) (BWh) or perimeter (ft) (BNh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool t-1 6 1212-0sw 0.068 n 5.03 0.64 0 0 0 0 23 23 113 14 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a 5.03 0.64 0 0 0 0 108 108 543 69 11 12E -0s. 0.068 s 5.03 0.64 0 0 0 0 142 142 713 91 I -G 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 II --OD 11 D0 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 140 140 702 89 61C 0.350 w 25.90 37.65 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 61 61 117 66 0 0 0 0 C DftPartCeil 0.221 16.37 9.29 0 0 0 0 11 11 184 105 F 19A-0bscp 0.295 - 8.20 1.55 2 2 19 4 0 0 0 0 F 22Avpl 0.989 - 73.19 0.00 0 0 0 0 248 46 3348 0 6 j c) AED excursion -3 -22 Envelope loss /gain 136 67 5604 346 12 a) Infiltration0 0 1714 173 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 2500 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 1 136 67 1 1 7319 520 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -136 S7 -7319 S20 14 Subtotal 0 0 0 0 15 Duct loads 0% 0% 0 0 0% 0% 0 0 irrTotal=(cm) I I 0 01 I I O I O Printout certified by ACCA to meet all requirements of Manual 8th Ed. -Pllf w'a:onaroec- Right Suite® Universal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 . C:\Documents and Settings \ROBERT HALL \My Documents \Wdghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 14 Right -J@ Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR 5- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name UNIT B KIT/DIN /FAM B 2 Exposed wall 103.3 ft 23.8 ft 3 Ceiling height 9.0 ft p 9.0 It heat/cool 4 Room dimensions 1.0 x 298.7 ft 5 Room area 1252.7 112 298.7 ft' Ty Corvsbuction U -value Or I HTM I Area (fl 2) I Load I Area (ft=) I Load number (Btuh W2 F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Stuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 4y 12E-0sw 0.068 n 5.03 0.64 351 256 1288 164 176 417 586 74 �L-DO 61C 0.350. n 25.90 11.55 60 0 1554 693 24 0 622 277 11DO 0.000 n 0.00 0.00 35 35 0 0 35 35 0 0 W 12E-0sw 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 12E-05. 0.068 s 5.03 0.64 351 284 1430 182 34 13 64 8 61C 0.350 s 25.90 20.65 46 0 1188 947 00 0 0 11 D0 0.000 s 0.00 0.00 21 21 0 0 21 21 0 0 W 12E Osw 0.068 w 5.03 0.64 227 227 1144 145 5 5 23 3 L ---G 61 C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 625 625 1202 682 0 0 0 0. C DftPanceil 0.221 16.37 9.29 11 11 184 105 0 0 0 0 F 19A-Obscp 0.295 - 8.20 1.55 8 8 69 13 0 0 0 0 F 22Avpl 0.989 - 73.19 0.00 628 52 3769 0 299 24 1738 0 61 c) AED excursion 1498 108 Envelope loss /gain 11828 4428 3033 470 12 a) Infftration 3869 3921 890 90 b) Room vent lation 0 0 0 0 13 Internal gains: Occupants @ 250 0 0 0 0 Appliances @ 1800 2 3600 2 3600 Subtotal (lines 6 t 13) 15697 8419 3923 4160 00000 0 0 0 =1.11,b 0 0 4512 369 15697 8419 8434 4529 0% 0% 0 0 0% 0% 0 0 6971 15660 114NrtaeQuo 8355 44151 aI (dm) I I I n19I I I 1 Printout certified by ACCA to meet all requirements of Manual 8th Ed. Right Suite® U niversal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 CADocuments and Settings \ROBERT HALL \ My Documents\Wrightsoft HVAC \2 -CAR 6-PLEX UNITS I-3.mp Cal Page 15 Right -JO Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834042 Phone: 745-0468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name HALLWAY B GARAGE S 2 Exposed wall 0 ft 27.8 It 31 Ceiling height 9.0 It heat/cool 9.0 ft heat/cool 4 Room dimensions 1.0 x 60.8 It 15.8 x 15.8 ft 5i Room area 60.8 ft' 248.1 ft' Ty Construction U-valuerea Or HTM A(ft') I Lo ad I Aea r(ft') I Load number �Stuh/ft"F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Stem) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12E-0sw 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E -0s. 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 11 12E -0s. 0.068 s 5.03 0.64 0 0 0 0 142 142 713 91 61C 0.350 's 25.90 20.65 0 0 0 0 0 0 0 0 11DO 0000 s 0.00 0,00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 108 108 543 69 `G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 '1.09 61 61 117 66 0 0 0 0 C DftPartCeil 0.221 - 16.37 9.29 0 0 0 0 11 11 184 105 F F 19A-0bscp 22Avp1 0.295 0.989 - - 8.20 73.19 1.55 0.00 0 0 0 0 0 0 0 0 0 248 0 28 0 2031 0 0 6 c) AED excursion -0 -0 Envelope less /gain 117 66 3472 264 12 a) Infiltration 0 01 10401 105 b) Room ventilation 0 01 0 0 13 Internal gains: Occupants @ 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6to 13) 117 66 4512 369 Less external bad 0 0 0 0 Less transfer 0 0 0 0 Redistribution -117 -66 -4512 -369 14 Subtotal 0 0 0 0 15 Duct loads 0% 0% 0 0 0% 0% 0 0 md Ar`nsq.rem (chn) I I 1 0ad 01 1 1 el 61 Printout Certified by ACCA to meet all requirements of Manual 8th Ed. Right Suite® Universal 7.1.03 RSU06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 16 Right -J@ Worksheet UNIT 8 KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 Job: 2- CAR & PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name BED 2 B BED 1 B 2 Exposed all 18.0 ft 9.8 ft 3 Ceiling height 9.0 It heat/cool 9.0 It heat/cool 4 Room dimensions 1.0 x 96.8 it 8.3 x 11.3 ft 5 Room area 96.8 ft2 92.8 ft2 Ty Construcgon U -value Or I HTM I A. A(ft2) I Load I Area (ft2) I Load number (Blah/ft2-"F) (Blum/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool i1 6VL12E-0sw 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a0.00 0.00 0 0 0 0 0 0 0 0 11 w 12E-0sw 0068 s 5.03 0,64 68 52 259 33 74 58 293 37 I --G 61C 0.350 a 25.90 20.65 16 0 414 330 16 0 414 330 III 11DO 0.000 a 0.00 0.00 0 0 0 0 0 0 0 0 --DDD t 12E-0.0.068 w 5.03 0.64 95 95 476 60 14 14 68 9 -G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B38ad 0.026 - 1.92 1.09 97 97 186 106 93 93 179 101 C DftParlCeil 0.221 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 8.20 1.55 0 0 0 0 0 0 0 0 F 22Avpl 0.989 - 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 426 426 Envelope loss /gain 1335 956 954 904 12 a) Infiltration 674 68 365 37 b) Room ventilation 0 0 0 0 13 Internal gains : Occupants @ 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 2010 1024 1319 941 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 411 405 39 22 14 Subtotal 2421 1429 1358 963 15 Duo loads 0% 0% 0 0 0% 0% 0 0 2 18 135 9 Avrecfm v( I 1021 131 I I 1� Printout certified by ACCA to meet all requirements of Manual 8th Ed �y -M+- wrrsowtwotic- Right -Suite® Universal 7.1.03 R5U 06972 2012 -Nov -1608:23:18 2C -Q CADocuments and Settings \ROBERT HALL \My Documents \Whghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 17 Right M Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name MECH B UPER BATH B 2 Exposed wall O ft O ft 3 Ceiling height 9.0 It heat/cool 9.0 R heat/cool 4 Room dimensions 4.5 x 4.5 It 4.5 x 7.5 It 5 Room area 20.3 W 33.8 W T Y Construction U -value Or HTM I Area ft I Load I Area ft I Load I number (Btuh/ft"F) (BWh/ftl or perimeter (ft) (BWh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool r1 6 12E-0sw 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 w 12E0sw 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 1112E-0sw 0.068 s 5.03 0.64 0 0 0 0 0 0 0 0 61C 0:350 s 25.90 20.65 0 0 0 0 0 0 0 0 11 D0 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 V� 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 t -G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 20 20 39 22 34 34 65 37 C DftParlCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F 22Avpl 0.989 - 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AMexcursion -0 -0 Envelope loss /gain 39 22 65 37 12 a) Infiltration 0 0 0 0 b) Room ventilation 1 0 0 0 0 13 Internal gains: Occupants (03 250 0 0 0 0 Appliances Q 1800 0 0 0 0 Subtotal (lines 6 to 13) 39 22 65 37 Less a#emel load 0 0 0A700 Less trensfer 0 0 0Redistribution -39 -22 5814 Subtotal 0 0 12315 Dud loads 0% 0% 0 0 0% 0% 0 cad amu 0( 251 761 1 1 Ao red n 1 1 01 01 1 1 Printout certified by ACCA to meet all requirements of Manual 8th Ed. .i.wr4onc�o�e' Right-S.Re©Universa17.1.03RSU06972 2012 -Nov -1608:23:18 ,llaC:\Documents and Settings \ROBERT HALL \My Documents \wrightsoft HVAC \2 -CAR 6-PLEX UNITS 13.mp Cal Page 18 Right M Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-6468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Roan name MASTER BED B UPPER STAIR B 2 Exposed all 14.3 1t 0 It 3 Ceiling height 9.0 ft heat/cool 9.0 It heauc l 41 Room dimensions 1.0 x 151.3 ft 1.0 x 31.5 ft 5 Room area 151.3 ft' 31.5 ft' Ty ConstructionU-value Or HTM Area (ft') I Load I Area (ft') Load number (But h/ft;°F) I (Btuh/ft') I or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 612E4sw 0.068 n 5.03 0.64 122 102 511 65 0 0 0 0 �-G 61C 0.350 n 25.90 11.55 20 0 .518 231 0 0 0 0 I -D 1100 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 7112E -0s. 0.068 s 5.03 0.64 0 '0 0 0 0 0 0 0 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 11DO 0.000 s. 0.00 0.00 0 0 0 0 0 0 0 0 VL 12E-0sw 0.068 w 5.03 0.64 7 7 34 4 0 0 0 0 I --f' 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 188S8ad 0.026 - 1.92 1.09 151 151 291. 165 32 32 61 34 C DOPartCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - 8.20 1.55 8 8 69 13 0 0 0 0 F 22A+ pl 0.989 - 73.19 0.00 0 0 0 0 0 0 0 0 61 AED exwrsion 93 -0 Envelope loss /gain 1423 572 61 34 12 a) Infiltration 1 534 54 0 0 b) Room ventilation 1 0 0 1 0 0 13 Internal gains: Occupants ® 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 t 13) 1957 626 61 34 '09'0000 0 0 0 ER�,el.nb.l.n 45 26 -61 -34 2002 651 0 0 0% 0% 0 0 0% 0% 0 0 20841 6601 1 1 Ar elgued Wim) 1 1 1 I 1 01 O1 Printout certified by ACCA to meet all requirements of Manual 8th Ed. ♦�we+folt+ltwotR- Right Suite® Universa17.1.03 RSU 06972 2012 -Nov -1608:23:18 ' C:\Documents and Settings \ROBERT HALL \MyDocuments \Wrightsoft HVAC \2 -CAR 6-PLE%UNITS 1-3.mp Cal Page 19 Right -JO Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Plane: 745-8468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL I Room name OPEN TO ABOVE LAUNDRY 2 Exposed wall 3.8 R 0 R 3 Ceiling height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 3.8 x 10.5 It 3.8 x 4.5 R 5 Room area 39.4 ft2 16.9 ft2 T Ty Constmction U -value Or HTM Area ft2) Load Area itI I Load number (Btuh/ft2-°F) (Btuh/ft') I or perimeter (R) I (Blah) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 T 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 1 6C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11D 17D0 0.000 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0 .068 a a 0.00 0.00 0 0 0 0 0 0 0 0 11 61C 0.068 s 5.03 0.64 4 20 700 13 0 0 0 0 �C 61C 0.350 s 25.90 20:65 1 14 0 359 286 0 0 0 0 I--0 11D0 0.000 s 0:00 0:00 0 0 0 0 0 0 0 0 t 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 -G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 168-08ad 0.026 - 1.92 1.09 39 39 76 43 17 17 32 18 C DRPartCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F 22AIIN 0.989 73.19 0.00 0 0 0 0 0 0 0 0 6c) AED excursion 370 -0 Envelope loss /gain 535 712 32 78 12 a) Infiltration 141 14 0 0 N Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines filo 13) 675 726 32 18 Lass external load0 0 0 Less transfer 0 0 0 Redistribution -675 -72 LO00% -32 -1814 Subtotal 0 0 0 15 Duct loads 0%0% 0 0% 0 0 regu -O Alr (.f.) I I I 0I OI OI O Printout certified by ACCA to meet all requirements of Manual 8th Ed. -lir w�towe�ofc Right -Suite® Universa17.1.03 RSU 06972 2012 -Nov -1608:23:18 CADocuments and Settings \ROBERT HALL \My Documents \Wrtghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 20 Right M Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR & PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name MASTER WIC B MASTER BATH B 2 Exposed well 0 1t 6.0 It 3 Ceiling Might 9.0 R heat/cool 9.0 ft heat/cool 4 Room dimensions 1.0 x 33.2 ft 1.0 x 48.4 It 5 Room area 33.2 ft- 48.4 ft' Ty I Construction U -value Or HTM I Area (ftp I Load I Area (ft 0 I Load number (BNh/ft'-F) I (Blah /ft=) or perimeter (ft) (Btuh) or perimeter (ft) (BNh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool r1 612E-0sw 11111 0.068 n 5.03 0.64 0 0 0 0 54 38 191 24 I -G 61C 0.350 n 25.90 11.55 0 0 0 0 16 0 414 185 �D 11D0 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 1112E-0sw VL 0.068 s 5.03 0.64 0 0 0 O 0 0 0'. 0 I --G 61C 0:350 s .25.90 20.65 0 0 0 0 0 0 0 0 11 D0 0.000 a 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0.0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 �G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 33 33 64 36 48 48 93 53 C DftPanCeil 0.221 - 16.37 929 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F 22A+ pl 0.989 73.19 0.00 0 0 0 0 0 0 0 0 61 c) AED exwrsion -0 75 Envelope loss /gain 64 36 699 337 12 a) Infiftration 0 0 225 23 J) Roomventilation 0 0 1 0 0 13 Intemalgains: Occupants @ 250 0 0 0 0 Appliances @ 1800 00 0 0 Subtotal (lines 6 to 13) 64 36 924 359 Less transfer load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 371 382 0 0 14 Subtotal 434 418 924 359 is Of loads 0% 0% 0 0 0% 0% 0 0 raomdl 434 4381 9391 359 1 1 Aofrel ( m) 1 1 331 Printout certified by ACCA to meet all requirements of Manual 8th Ed -rW wr ftcw Right -Suite® Univemal7.1.03 RSU 06972 2012 -Nov -1608:23:18 CADocuments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 21 Right -J® Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name MAIN STAIR POWDERS 2 Exposed wall O ft O ft 3 Ceiling height 9.0 It heat/cool 9.0 It heat/cool 4 Room dimensions 1.0 x 33.8 ft 3.8 x 4.5 ft 5 Room area fl 33.8 ' 16.9 ft' Ty Construction U-valu Or HTM I Area (ftp Load Area (it Load number (Btuh IV%F) (Btuh)ftp or perimeter (1t) (Btuh) or perimeter (ft) (Stuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool rl 612E -Om 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 {-G 61C 0.350 n 25.90 11.55 0 O 0 0 0 0 0 0 LL --DD 11Do 0.001) n 0.00 0.00 0 0 0 0 0 0 0 0 .. W 12E-0sw 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 11 12E-0sw 0.068 s 5.03 .0.64 0 0 0 0 0 0 0 0 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 11DO 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 t 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 --G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 166-08ad .0.026 1.92 1.09 0 0 0 0 0 0 0 0 C DftParlCeil 0.227 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - '8.20 1.55 0 0 0 0 0 0 0 0 F 22Avpl 0.989 73.19 0.00 34 0 0 0 17 0 0 0 6i c) AED excursion 0 0 Envelope loss /gain 0 0 0 0 12 a) Infiltration0 0 0 0 J) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 00 0 0 Appliances @ 7800 0 . 0 0 0 Subtotal (lines 6 to 13) 0 0 1 1 0 0 Less eMemal bad 0 0 0 0 Less transfer 0 0 0 0 Redistnbution 0 0 0 0 14 Subtotal 0 0 0 0 15 Dud loads 0% 0% 0 0 0 % 0% 0 0 T0131Air I 01 reQuired (e I I OI OI I OI Printout certified by ACCA to meet all requirements of Manual 8th Ed. ^y -+}+- wrsotitroR- Right SuiteO U rivers a[ 7.1.03 RSU 06972 2012 -Nov -1608:23:18 AC.Q CADowments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 22 Right -J® Worksheet UNIT B KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR 6. PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name STOAGE B MUD B 2 Exposed all O ft 0 It 3 Ceiling height 9.0 It heat/cool 9.0 It heat/cool 4 Room dimensions 3.8 x 4.5 It 3.0 x 4.5 It 5 Room area 16.9 ft' 13.5 ft' Ty Constnwdon U-valuOr HTM Area (ft') I Load I Area (fit Load number �(Btuhlft�Fjlp I (Stuh/k') I or perimeter (ft) Slut, or perimeter (ft) (Btuh) Heat Coal Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VLt12E -Ow }II 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 n25.90 11- 55 0 0 0 0 0 0 0 0 11DO 0:000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12&06 v 0.068 a 0.00 0.00 0 0 0 0 0 0 0 0 11 12E-0sw 0.068 s 5.03 0.64 0 0 0 0 0 0 0 0 61C .0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 11 D0 0000 s 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 `f 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 0 0 0 0 0 0 0 0 C DftPadCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A.Obscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F 22A+ l 0.989 - 73.19 0.00 17 0 0 0 14 0 0 0 6c)AED exwmion 0 0 Envelope loss /gain 0 0 0 0 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains : Occupants @ 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 0 0 1 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 15 Dud loads 0% 0% 0 0 0% 0% 0 0 I Aomrsqu'roired (chn ) I OI O I I 0I 01 Printout certified by ACCA to meet all reauirements of Manual ath Ed. - - w�so,st�o�t Right Suite® Universa17.1.03 RSU06972 2072 -Nov -1-608:23:1-8 C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS iJ.rup Cal Page 23 Right -J@ Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL I Room name UNIT C OPEN TO ABOVE C 2 Exposed wall 138.3 R 14.3 it 3 Ceiling height 9.0 it p 9.0 it heat/cool 4 Room dimensions 3.8 x 10.5 R 5 Room area 1251.2 ft' 39.4 ft' Ty Construction U -value Or HTMArea (ft') I Load I Area (ft') I Load number (Btuh/ft?°F) (Btuh/ft') or perimeter (ft) (Stuh) or perimeter (ft) (Btuh) Heat Coal Gross N/P/S Heat Cool Gross N/P/S Heat Cool r1 6 T��I 0.058 n 5.03 0.64 I 4 I 299 I 1505 f 191 0 0 0 0 6 1C 0.350 n 25.90 17.55 77 71 0 1839 820 0 0 0 0 111C 1D0 0.000 0.00 0.00 35 35 0 0 0 0 0 0 W 12E -Os. 0.08 a a 5.03 0.64 430 430 2163 275 95 95 476 60 11 12E-0sw 00668. s 5.03 0:64 405 345 1736 227 34 27 135. 17 61C 0.350 5 25.90 20.65 39 0 1008 804 7 0 180 143 11D0 0.000 s 0.00 0-W 21 21 0 0 0 0 0 0 V� 12E-0sw 0.068 w 5.03 0.64 5 5 23 3 0 0 0 0 �G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16BJ8ad 9.026 1.92 1.09 625 625 1202 682 39 39 76 43 C DftPanCeil 0.221 16.37 9.29 11 11 184 105 0 0 0 0 F 19A-0bscp 0.295 8.20 1.55 10 10 81 15 0 0 0 0 F 22Acpl 0.989 73.19 0.00 626 64 4684 0 0 0 0 0 6 c) AED exwrsion 1362 184 Envelope loss /gain 14425 4477 1 1 866 448 12 a) Infiltration 5180 524 534 54 b) Room ventilation 0 0 0 0 13 Internal gains : Oupants @ 250 cc 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 1 19606 5002 1 1 1400 502 Less external bad 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -1400 -502 14 Subtotal 19606 5002 0 0 15 Duct loads 0% 0% 0 0 0% 0 % 0Tota 0 196601 58521 Air reguved (ctm) I I I I I 01 0I Printout certified by ACCA to meet all requirements of Manual 8th Ed. wrrsol lt- Right-SuiteOUniversa17.1.03 RSU06972 2012 -Nov -1608:23:18 CADowments and Settings \ROBERT HALL \My Documents \Wdghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 24 Right -JO Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY. ID 834442 Phone: 745-8468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name HALLWAY C BED 2 C 2 Exposed all 0 ft 18.0 ft 3 Ceiling height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 1.0 x 60.8 fl 1.0 x 96.8 It 5 Room area 60.8 ft' 96.8 W Ty ConstructionU-value number ( Btuh/ft?-F) Or HTM (Btuhnt I Area (ft') ( I or perimeter ft) Load I (Btuh) Area (ft-) I or perimeter (ft) Load) (Brun Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1212-0sw 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0. 0 W12E-0sw 0.068 a 5.03 0.64 0 0 0 0 95 95 476 60 11 w 12E-06+ 0.068 s 5.03 064 0 0 0 0 fib 52 259 33 I --G 61C 0.350 s 25.90 20.65 0 0 0 0 16 0 414 330 III--DDD11DO 0.000 a 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0.0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 `(' 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 1.92 1.09 61 61 117 66 97 97 186 106 C DRPanreil 0.221 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 8.20 1.55 1 1 9 2 0 0 0 0 F 22Avpl 0.989 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AED ezwrsion -0 425 Envelope loss /gain 126 68 1 1 1335 954 12 a) Infiltration 0 0 674 68 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 00 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 t 13) 1 126 68 1 1 2010 1023 Less eMemal load 0 00 0 Less transfer 0 0 0 0 Redistribution -126 -68 776 293 14 Subtotal 0 0 2786 1316 15 Dud loads 0% 0% 0 0 0% 0% 0 0 27941 12241 Ar requ ed lot I I I 0I OI Printout certified by ACCA to meet all requirements of Manual ath Ed. -�{+- wrsoestcw�c- Right Suite® U niversal 7.1.03 RSU 06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL\My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 25 Right -J® Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY . ID 834442 Phone: 7454468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name BED 1 C UPPER STAIR C 2 Exposed all 9.8 ft 0 ft 3 Ceiling height 9.0 ft heat/cool 9.0 It heat/cool 4 Room dimensions 8.3 x 11.3 ft 1.0 x 31.5 ft 5 Room area 92.8 ft' 31.5 ft' Ty ConstruclionU-value Or HTM I Area (ft 2) I Load I Area (ft 2) I Load I number (But h/ft;'F) (BWh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gress N/P/S Heat Cool Gross N/P/S Heat Cool 6 4y 12E-0sw 0.068 n 5.03 0.64 0 0 0 0 0 0 0 0 I��D 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11 D0 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12&0s 0.068 a 5.03 0.64 14 14 68 9 0 0 0 0 11 12E-0sw 0.068 s 5.03 0.64 74 58 293 37 0 0 0 0 61C 0.350 s 25.90 20.65 16 0 414 330 0 0 0 0 11DO 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 t12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 -- 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16838ad 0.026 - 1.92 1.09 93 93 179 101 32 32 61 34 C DftPartCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F mAapl 0.989 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 425 -0 Envelope loss /gain 954 903 61 34 12 a) Infll2tion 365 37 1 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines fi to 13) 1 1 1319 940 1 1 61 34 Less external load 0 0 0 0 ,.astransfer 0 0 0 0 Redistribution 40 22 -61 34 14 Subtotal 1360 962 0 0 15 Duct loads 0% 0% 0 0 0% 0% 0 0 mom ad 13461 0 Aotal �uiredl (cfm) I I �2I I I 0I Printout certified by ACCA to meet all requirements of Manual 8th Ed. may--4'i+-w t�oR Right SuiteaO U niv ere at 7.1.03 RSU 06972 2012 -Nov -1608:23:18 .iGC�� CADocuments and Settings \ROBERT HALL\My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 26 Right -J@ Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD . RIGBY . ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name MECH C UPPER BATH C 2 Exposed wall O ft O ft 3 Ceiling height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 4.5 x 4.5 It 4.5 x 7.5 It 5 Room area 20.3 ft2 33.8 ft' Ty Construction U -value I HTM I M') Area (ft 2) I Load I Area (ft 2) I Load number IOr (BUh/ft'-°F) (Btuh or perimeter (ft) (Bwh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Hea[ Cool Gross N/P/S Heat Cool r1 612E-0sw 0.068 �1 n 5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 n 25.90 11,55 0 0 0 0 0 0 0 0 1100 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E4sw 0.068 a 5.03 0.64 0 0 0 0 0 0 0 0 11 v 12E-0sw 0.068 s5.03 0.64 0 0 0 0 0 0 0 0 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 11130 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 1r�r 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 L -G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 1.92 1.09 20 20 39 22 34 34 65 37 C OftPanCeil 0.221 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.20. 1.55 0 0 0 0 0 0 3 1 F 22Aapl 0.989 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -0 -0 Envelope loss /gain 39 22 68 37 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 01 0 0 13 Internal gains : Occupants @ 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 39 22 68 37 Less extemal lead 0 0 0 0 Less transfer 0 0 0 0 Redistnbution -39 -22 62 34 14 Subtotal 0 0 130 71 15 Duct loads 0% 0% 0 0 0% 0% 0 0 I I t34I Ao,`mquiretll (of. I I of OI 12I Printout certified by ACCA to meet all requirements of Manual 8th Ed -�+- wrsolsc�roR- Right-Suite®Universal7.1.03 RSU06972 2012 -Nov -1608:23:18 CADoouments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 27 Right J® Worksheet UNIT C KARTCHNER HOMES 187 STOCKMAN BLVD , RIGBY , ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name LAUNDRYC MASTER WIC 2 Exposed wall 0 ft 4.5 it 3 Ceiling height 9.0 ft heat/cool 9.0 It heat/coot 4 Room dimensions 3.8 x 4.5 ft 1.0 x 33.2 ft 5 Room area 16.9 ft' 33.2 ft' Ty Construction U -value Or I HTM I Area (ft') Load I Area (ft2) I Load number (Stuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (BWh) Heat Cool Gross N/P/S Hea[ Cool Gross N/P/S Heat Cool Ilr �tuhalu!F)I r1 6VL12E-0sw 0.068 n STI 5.03 0.64 0 �� 0 I 0 I 0 I 0 0 0 0 61C 0.350 n 25.90 11.55 0 0 0 0 0 0 0 0 11 D0 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 a 5.03 0.64 0 0 0 0 41 41 204 26 11 w 12E-0sw 0.068 's 5.03 0.64 0 0 0 0 0 0 0 0 I ---G 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 II-- 2 11 D0 0.000 s 0.00 0.00 0 0 0 0 0 0 0. 0 VL 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 LG 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 - 1.92 1.09 17 17 32 18 33 33 64 36 C DftloartCeil 0.221 16.37 929 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 8.20 1.55 0 0 0 0 0 0 0 0 F 22Api 0.989 73.19 0.00 0 0 0 0 0 0 0 0 6 c) All excursion -0 Envelope lass /gain 32 18 268 0 62 12 a) Infiltration 0 0 169 17 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants ® 250 0 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 32 18 436 79 Less ememal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -32 -18 733 269 14 Subtotal 0 0 1169 348 15 Duct loads 0% 0% 0 0 0% 0% 0 0 � 1 1 Nr�egedl ( fm) 1 1 0I 0I 1 1 391 1 Printout certified by ACCA to meet all requirements of Manual 8th Ed. -�'i+-w�btivwR- Right SuiteNJ Univers a17.1.03 RSU 06972 2012 -Nov -16 W:23:18 C:\Documents and Settings \ROBERT HALL\My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 28 Right -M) Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 7454468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name MASTER BATH C MASTER BED C 2 Exposed all 13.5 R 14.3 R 3 Ceiling height 9.0 R heat/mol 9.0 R heat/cool 41 Room dimensions 1.0 x 48.4 ft 1.0 x 151.3 R 5 Room area 48.4 R' 151.3 ft' Ty Construction -value Or I HTM I Area (R') Load I Area (ft') I Load number Btuh/R?°F) (U (Btuh/ft') or perimeter R ( ) (Btuh) or perimeter (ft) ( (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool r1- 6 12E-0sw 0.068 n 5.03 0.64 54 38 191 24 122 97 486 62 fi1C 0.350 n 25.90 11.55 16 0 414 185 25 0 647 289 11DO 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 w12E-0sw 0.068 a 5.03 0.64 68 68 340 43 7 7 34 4 11 12E-0sw 0.068 s 5.03 0.64 0 0 0 0 0 0 0 0 6 C 0.350 s 25:90 20.65 0 0 0 0 0 0 0 0 II ----DD 11D0 .0.000 s 0.00 0:00 0 0 0 0 0 0 0 0 W 12E-0.0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 �G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 1613-38ad 0.026 1.92 1.09 48 48 93 53 151 151 291 165 C DRPadCeil 0.221 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 - 8.20 1.55 0 0 0 0 8 8 69 13 F 22A-vpl 0.989 73.19 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 74 116 Envelope loss /gain 1038 379 1527 649 12 a) Infiltration 506 51 534 54 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 1 0 0 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 1 1 1544 430 1 2061 703 Less exlemal lead 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 47 26 14 Subtotal 1544 430 2108 729 15 Duct loads 0% 0% 0 0 0% 0% 0 0 m load 15 4 30 218 7291 Air (cfm uir I 21 731 I I 71 1 Printout certified by ACCA to meet all reouirements of Manual 8th Ed wrspii- Right-Suile®Universa17.1.03 RSU06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 29 Right -JO Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 7455468 Job: 2- CAR 6 PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name KIT/DIN /FAM C POWDER C 2 Exposed wall 26.8 ft 0 It 3 Ceiling height 9.0 ft heat/cool 9.0 it heat/cool 4 Room dimensions 1.0 x 304.3 ft 3.0 x 4.5 It 5 Room area 304.3 ft' 13.5 ft' Ty Construction U -value Or I HTM I Area (ft) I Load Area (ftp I Load number (Stuh/8;°F)I (Stuh/fi or perimeter (ft) (Btuh)I or perimeter (ft) (Btuh) Heat Cool Grew NIP/S Heat Cool Gross NIP/S Heat Cool r-1 612E-0sw {II 0.068 n 5.03 0.64 176 111 556 71 0 0 0 0 I -G 61C 0:350 n 25.90 11.55 30 0 777 346 0 0 0 0 LL -DD 11DO 0.000 n - 0.00 0.00 35 35 0 0 0 0 0 0 W 12E-0.0.068 a 5.03 0.64 0 0 0 0 0 0 0 0 11 12E-0sw 0.068 s 5.03 0.64 61 40 200 25 0 0 0 0 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 11DO 0.000 s 0.00 0.00 21 21 0 0 0 0 0 0 W 12E-0sw 0.068 w 5.03 0.64 5 5 23 3 0 0 0 0 1-G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 168-38ad 0.026 - 1.92 1.09 0 0 0 0 0 0 0 0 C DftPartCeil (1221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-Obscp 0.295 - 8.20 1.55 0 0 0 0 0 0 0 0 F 22Avpl 0.989 73.19 0.00 304 27 1958 0 14 0 0 0 61c c) AED excursion ' 140 0 Envelope loss /gain 3513 585 0 0 12 a) Infiltration 1002 j 101 0 0 J) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 0 0 0 1 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 t 13) 4516 686 1 1 0 0 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 5993 459 0 0 14 Subtotal 10509 1145 0 0 15 Dud loads G% 0% 0 0 0% 0% 0 0 1 I I I31 II 4 19%l(Nuom 51 O OI Printout certified by ACCA to meet all reauirements of Manual 8th Ed. +y 't{+- wrsowcwfc- Right Suite®Univemal7.1.03 RSU06972 2012 -Nov -1608:23:18 .GG C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 30 Right -JO Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBY, ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 11 Room name MAIN STAIR C MUD C 2 3 Exposed all Ceiling height 0 ft 9.0 ft heat/cool 6.0 ft 9.0 ft ::-1 4 Room dimensions 1.0 x 31.5 ft 3.0 x 4.0 5 Room area 31.5 fl' 12.0 ft2 Ty Construction U -value Or HTMI Area (ft') I Load I Area (ftp I Load number /ft I (Btuh /ft 2 or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool I(Stuh"F)I IfF r1 6 0.068 n 5.03 0.54 0 0 0 0 27 27 136 17 6 1C 0.350 n 25.90 11:55 0 0 0 0 0 0 0 0 111C 700 0:000 n 0.00 0.00 0 0 0 0 0 0 0. II W12E-0sw 0.068 a 5.03 0.640 0 0 0 0 0 0 0 11 12E-0Os. 0.068 s 5.03 .0.64 0 0 0 0 27 27 136. 17 61C 0.350 s 25.90 20.65 0 0 0 0 0 0 0 0 1100 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-0sw 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 T -G 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 1.92 1.09 0 0 0 0 0 0 0 0 C DftPartCeil 0.221 - 16.37 9.29 0 0 0 0 0 0 0 0 F 19A-0bscp 0.295 8.20 1.55 0 0 0 0 0 0 0 0 F 22"pl 0.989 73.19 0.00 32 0 0 0 12 6 439 0 6 c)AED excursion 0 -0 Envelope bes /gain 0 0 711 34 12 a) Infiltration 0 0 225 b) Room ventilation 0 0 0 13 Internal gains: Occupants @ 250 0 0 0 157 Appliances @ 1800 0 0 0 Subtotal (lines 6 t 13) 0 0 936 Less eEel load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -936 57 14 Subtotal 0 0 0 0 15 Duct loads 0% 0% 0 0 0% 0% 0 0 1 61 01 1 61 D Printout certified by ACCA to meet all reauirements of Manual 8th Ed. -�{+- wrrspkara/c- Right Suite® U niversal 7.1.03 RSU06972 2012 -Nov -1608:23:18 C:\Documents and Settings \ROBERT HALL \ My Documents \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 31 Right -JO Worksheet UNIT C KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 1 Room name STORAGE C GARAGE C 2 Exposed wall 0.5 It 30.8 R 3 Ceiling height 9.0 It heat/mol 9.0 R heat/cool 4 Roomdimensions 3.8 x 4.5 ft 15.8 x 15.8 ft 5 Roomarea 16.9 ft2 248.1 ft2 Ty Constwalon U -value Or HTM I Area (ft2) I Load I Area (ft2) I Load number (Btuh/ft;°F) (Btuh/R 2) or perimeter (ft) (Btuh) or perimeter (R) (8tuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 T W 0.068 n 5.03 0.64 0 0 0 0 27 27 136 77 {�1D` 1 6C 0.350 n 25.90 1155 0 0 0 0 0 0 0 0 11 17DD 0 0.000 n 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-Om0.068 a 5.03 4 5 5 23 3 108 108 543 69 11 12E-0sw 0.068 s 5.03 0.64 0-6 0 0 0 0 142 742 713 91 61C 9.350 s 25.90 2065. 0 0 0 0 0 0 0 0 71 D0 0.000 s 0.00 0.00 0 0 0 0 0 0 0 0 l/� 12E-0. 0.068 w 5.03 0.64 0 0 0 0 0 0 0 0 LG 61C 0.350 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16B-38ad 0.026 1.92 1.09 0 0 0 0 0 0 0 0 C DRPartCeil 0.221 16.37 9.29 0 0 0 0 1111 184 105 F 19A-0bscp 0.295 8.20 1.55 0 0 0 0 0 0 0 0 F 22A+pl 0.989 73.19 0.00 17 1 37 0 248 31 2250 0 6 LAE"excursion -0 -1 Envelope loss /gain 59 3 1 1 3827 1 280 12 a) Infiltration 19 2 1152 117 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 250 0 0 1 0 1 0 Appliances @ 1800 0 0 0 0 Subtotal (lines 6 to 13) 1 1 78 5 1 1 4979 397 Less exlemal load 0a 0 0 Less transfer 0 0 0 0 Redistribution -78 -5 -4979 -397 14 Subtotal 0 0 0 0 15 Dud loads 0% 0% 0 0 0% 0% 0 0 01 i(Avechn I 0I 0I I I I Printout certified by ACCA to meet all requirements of Manual 8th Ed „�- -4"{+- wrsoeslcr oft- Right-SuileO Universal 7.1.03 RSU 06972 2012 -Nov -1608:23:78 CADocuments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS iJ.rup Cal Page 32 MAIN Le}& �1A?n ti1196in i '.... .IT IOWE /FMI IQr 1.1. /FNAB KR I."I IFAMC qr /FAY /OWO '�T19?n !�"]9 cM "15stTe �r R POKDERB _ FERC O JT IF-T- _ I .1srua� Ryc YUN srNRSo sn� Yuo Yuoe GE rsroRACEc Ywc Ywo oEo STNRS J GaRAGEA G Ea GARAGE CdRhC£0 Job #: 2- CAR 6- PLEX Scale:1 : 130 KARTCHNER HOMES Performed by ROBERT HALL for Pae 1 g 2-CAR6 PLEX 197 STOCKMAN BLVD Right -Suite® Universal RIGBY, ID 834442 7.1 .03 RSLI06972 REXBURG Phone: 745-8468 2012 -Nov -16 08:24:16 C:\Documents and Settings\ROBER.. UPPER FLO Job #: 2- CAR6- PLEX Performed by ROBERT HALL for 2-CAR6 FLEX REXBURG KARTCHNER HOMES 197 STOCKMAN BLVD RIGBY, ID 834442 Phone: 745-8468 Scale: 1 : 130 Page 2 Right i[e® Universal 7.1.03 RS W6972 2012 -Nov -16 08:24:17 Duct System Summary UNIT A FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 Project• • For. 2-CAR6 FLEX KARTCHNER HOMES REXBURG External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest friction rate Actual airflow Total effective lengtNTEL) Heating 0.70 in H2O 0.36 in H2O 0.34 in H2O 0.18/0.16 in H2O 0.079 in/100ft 660 cfm 431 ft Supply Branch Detail Table Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Cooling 0.70 in H2O 0.36 in H2O 0.34 in H2O 0.18/0.16 in H2O 0.079 in/100ft 660 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (n) H x W (in) Duct Mat] Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BED 1 C 1290 56 86 0.124 6.0 OX 0 ShMt 15.0 130.0 st3 BED C 1303 52 87 0.087 6.0 Oxo ShMt 21.0 185.0 st3A KIT/DINE/FAM h 6114 139 112 0.112 6.0 0x0 ShMt 20.0 140.0 st3 KIT/DINE/FAM-A h 6114 139 112 0.087 6.0 0X0 ShMt 31.0 175.0 st3A KIT/DINE /FAM -C h 6114 139 112 0.089 6.0 OX 0 ShMt 16.0 185.0 st3B MASTER BATH c 350 22 23 0.081 6.0 Ox 0 ShMt 28.0 195.0 st3B MASTER BED C 2671 84 178 0.118 6.0 Ox 0 ShMt 22.0 130.0 st3 MASTER WIC h 290 7 6 0.079 6.0 Ox 0 ShMt 23.0 205.0 st3B UPPER BATH h 159 22 11 Q Q QX 0 ShMt 0 0 Supply Trunk Detail Table Boid Irtallo values have been manually overriCCen ti 'Pi -l' WIighiSOT[• Right-SuRe®Univema17.1.03 RSU06972 /IRAXJ� CADo menta and Settings \ROBERT HALL \My Doaments \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 13.mp Cal 2012 -Nov -16 08:23:27 Page 1 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (dm) (cfm) FR (fpm) (in) (in) Material Trunk st3B Peak AVF 168 142 0.079 503 7.4 8 x 6 ShtMetl st3A st3A Peak AVF 359 341 0.079 646 9.8 8 x 10 ShtMetl st3 st3 Peak AVF 638 717 0.079 760 12.8 8 x 17 ShtMetl Boid Irtallo values have been manually overriCCen ti 'Pi -l' WIighiSOT[• Right-SuRe®Univema17.1.03 RSU06972 /IRAXJ� CADo menta and Settings \ROBERT HALL \My Doaments \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS 13.mp Cal 2012 -Nov -16 08:23:27 Page 1 Return Branch Detail Table Name Grill Size(in) Htg (dM) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Studdoist Opening (in) Duct Matl Trunk rb3 Ox 0 28 17 203.0 0.079 89 3.8 14X6.25 10x9 SJSp rt3A rb10 Ox 0 52 87 92.0 0.174 275 4.9 14X3.25 10x9 SJSp rt3 rb9 0x0 56 86 101.0 0.159 272 5.0 14X3.25 10x9 SJSp r13 rb2 oxo 139 112 0 0 441 0 14X6.25 10x9 SJSp rb5 oxo 279 225 0 0 882 0 14X6.25 10x9 SJSp rb11 oxo 105 201 0 0 637 0 144.25 10x9 SJSp ti wrigh h. Right SuiteOUniversa17.7.03 RSU 06972 2012 -Nov -7608:23:27 iRL.IY� C:\Documents and Settings \ROBERT HALL \My Dowments \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS iJ.mp Cal Page 2 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt3A Peak AVF 28 17 0.079 127 3.8 8 x 4 ShtMetl rt3 rt3 Peak AVF 137 190 0.079 426 7.8 8 x 8 ShtMetl ti wrigh h. Right SuiteOUniversa17.7.03 RSU 06972 2012 -Nov -7608:23:27 iRL.IY� C:\Documents and Settings \ROBERT HALL \My Dowments \Wnghtsoft HVAC \2 -CAR 6-PLEX UNITS iJ.mp Cal Page 2 Duct System Summary UNIT B FURNACE KARTCHNER HOMES 197 STOCKMAN BLVD , RIGBV , ID 834442 Phone: 745-8468 For. 2-CAR6 PLEX KARTCHNER HOMES REXBURG Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL Name Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0.36 in H2O 0.36 in H2O Available static pressure - 0.34 in H2O 0.34 in H2O Supply/ return available pressure 0.20/0.14 in H2O 0.20/0.14 in H2O Lowest friction rate 0.105 in/100ft 0.105 in/100ft Actual air flow 660 cfm 660 cfm Total effective length(TEL) c 1510 118 323 ft 0.123 Name Design (Btuh) Htg (cfm) Clg (Cfm) Design FR Diam (in) H x W (in) Duct Mat[ Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BED 1 B c 963 57 88 0.115 6.0 0x0 ShMt 14.0 160.0 st2 BED 2 B c 1429 102 131 0.132 6.0 Ox 0 ShMt 22.0 130.0 st2 KIT/DIN iFAM B -A c 1510 118 138 0.123 6.0 Ox 0 ShMt 23.0 140.0 st2 KIT/DIN FAM B -B c 1510 118 138 0.120 6.0 Ox 0 ShMt 16.0 150.0 st2B KIT/DIN /FAM B -C c 1510 118 138 0.110 6.0 Oxo ShMt 31.0 150.0 st2A MASTER BATH B h 924 39 33 0.105 6.0 Ox 0 ShMt 30.0 160.0 st2B MASTER BED R h 651 84 60 0 0 Ox 0 ShMt 0 0 MASTER WIC B c 418 18 38 0.123 6.0 Ox 0 ShMt 22.0 140.0 WA UPER BATH B c 70 5 6 0.127 6.0 Ox 0 ShMt 7.0 150.0 st2 Bold /italic values have been manually overridden t .#}W16qhtS,0f. Right Sui te® U niv em al 7.1.03 RSU 06972 2012 -Nov -1608:23:27 CADowments and Settings \ROBERT HALL \My Documents Wrightson HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 3 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (Cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 576 712 0.105 854 12.0 8 x 15 ShtMetl st2A Peak AVF 294 348 0.105 696 9.2 8 x 9 ShtMetl st2 st2B Peak AVF 157 171 0.105 385 7.0 8 x 8 ShtMetl st2A Bold /italic values have been manually overridden t .#}W16qhtS,0f. Right Sui te® U niv em al 7.1.03 RSU 06972 2012 -Nov -1608:23:27 CADowments and Settings \ROBERT HALL \My Documents Wrightson HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 3 Return Trunk Detail Table Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Type Name Size(in) (cfm) WITI) (ft) FR (fpm) (in) (in) Opening (in) Mat[ Trunk rb13 Oxo 277 357 133.0 0.105 566 9.3 2-14X3.25 2-10x18 SJSp i12A rb12 0x0 142 183 99.0 0.141 579 6.8 14X3.25 10x9 SJSp rt2 rb6 0x0 241 231 93.0 0.151 382 7.5 2-14X3.25 2-10x18 SJSp rt2 Return Trunk Detail Table t .4k. Wriqhtff0t.. Right Suite4D U nNemal 7.1.03 RSU06972 2012 -Nov -1608:23:27 /FG.71+G11 CAcurrents and Settings \ROBERT HALL \My Documents \Wnghisofl HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 4 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt2A Peak AVF 277 357 0.105 643 9.3 8 x 10 ShtMetl rt2 rt2 Peak AVF 660 771 0.105 694 12.4 8 x 20 ShtMetl t .4k. Wriqhtff0t.. Right Suite4D U nNemal 7.1.03 RSU06972 2012 -Nov -1608:23:27 /FG.71+G11 CAcurrents and Settings \ROBERT HALL \My Documents \Wnghisofl HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 4 Duct System Summary UNIT C FURNACE KARTCHNER HOMES Job: 2- CAR 6- PLEX Date: NOV,12,2012 By: ROBERT HALL 197 STOCKMAN BLVD , RIGBY , ID 834442 Phone'. 745-8468 0.36 in H2O 0.34 in H2O 0.21/0.13 in H2O 0.085 in/100ft 660 cfm Project Information 164 For: 2-CAR6 PLEX KARTCHNER HOMES REXBURG External static pressure Pressure losses Available static pressure Supply/return available pressure Lowest friction rate Actual air flow Total effective length(TEL) Heating 0.70 in H2O 0.36 in H2O 0.34 in H2O 0.21/0.13 in H2O 0.085 in/100ft 660 cfm 401 it Supply Branch Detail Table Cooling 0.70 in H2O 0.36 in H2O 0.34 in H2O 0.21/0.13 in H2O 0.085 in/100ft 660 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (M Ftg.Egv Ln (M Trunk BED 1 C C 962 46 164 0.121 6.0 Ox 0 ShMt 14.0 160.0 st1 BED 2C c 1316 94 224 0.097 6.0 Oxo ShMt 21.0 195.0 st1 KIT/DIN /FAMC-A h 3503 118 65 0.085 6.0 0x0 ShMt 33.0 215.0 st1A KIT/DIN/FAM C -B h 3503 118 65 0.091 6.0 0x0 ShMt 16.0 215.0 st1B KR/DIN /FAM C -C h 3503 118 65 0.089 6.0 Ox 0 ShMt 22.0 215.0 st1 MASTER BATH C C 430 52 73 0 0 Ox 0 ShMt 0 0 MASTER BED C C 729 71 124 0.092 6.0 OX 0 ShMt 23.0 205.0 st1 MASTER WIC c 348 39 59 0.092 6.0 0x0 ShMt 24.0 205.0 st1A UPPER BATH C 71 4 12 0.127 6.0 0X0 ShMt 6.0 160.0 st1 Supply Trunk Detail Table BoW /italic values have been manually overridden !mac-Pid-wrightZCd%- Right Sui le® U niv am al 7.1.03 RSU 06972 2012 -Nov -1608:23:27 /1...1.15 C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 5 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (Cfm) (Cfm) FR (fpm) (in) (in) Material Trunk st1 Peak AVF 608 779 0.085 876 13.0 8 x 16 ShtMetl st1A Peak AVF 275 189 0.085 619 8.8 8 x 8 ShtMetl st1 sit Peak AVF 118 65 0.091 265 6.3 8 x 8 ShtMetl st1A BoW /italic values have been manually overridden !mac-Pid-wrightZCd%- Right Sui le® U niv am al 7.1.03 RSU 06972 2012 -Nov -1608:23:27 /1...1.15 C:\Documents and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.mp Cal Page 5 Return Trunk Detail Table Grill Htg Clg TEL Design Veloc Diam H x W Studdoist Duct Type Name Size (in) Win) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Mall Trunk rb8 0x0 354 195 153.0 0.085 373 9.7 3-14X3.25 3-10)Q7 SJSp rt1A rb16 0x0 75 136 93.0 0.139 431 6.1 14X3.25 10x9 SJSp rt1 rb15 0x0 140 388 101.0 0.128 614 9.2 2-14X3.25 2-10x18 SJSp rtl rb14 0x0 91 133 130.0 0.100 420 6.5 14X3.25 10x9 SJSp rt1A Return Trunk Detail Table Q -f* rightsof't. Right -Suite@ Univers a(7.1.03 RSU 06972 2012 -Nov -1608:23:27 Zax CADccuments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 6 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt1 Peak AVF 660 852 0.085 767 13A 8 x 20 ShtMetl rt1A Peak AVF 445 328 0.085 668 10.5 8 x 12 ShtMetl rt1 Q -f* rightsof't. Right -Suite@ Univers a(7.1.03 RSU 06972 2012 -Nov -1608:23:27 Zax CADccuments and Settings \ROBERT HALL \My Documents \Wrightsoft HVAC \2 -CAR 6-PLEX UNITS 1-3.rup Cal Page 6