Loading...
HomeMy WebLinkAboutPLANS FA SYSTEM - 17-00632 - DL Evans Bank - Tenant FinishDATE: SCALE: DRAWN BY: Re m o d e l DL E v a n s B a n k 12 5 V a l l e y R i v e r D r , R e x b u r g , I D 8 3 4 4 0 FI R E A L A R M S Y S T E M 1 NOTES: 1. SMOKE DETECTORS SHALL BE NO MORE THAN 30 LINEAR FEET APART IN HALLWAYS 2. SMOKE DETECTORS SHALL BE LOCATED MORE THAN 3' FROM ANY HVAC RETURN OR SUPPLY 3. SMOKE DETECTORS SHALL BE LOCATED NO MORE THAN 5' FROM MAGNETIC DOOR HOLDERS 4. SMOKE DETECTORS SHALL BE LOCATED NO MORE THAN 15 LINEAR FEET FROM THE END/BEGINNING OF A HALLWAY 5. SMOKE DETECTORS SHALL BE PLACED A MINIMUM OF 3' FROM CEILING FANS 6.CANDELA SETTINGS OFHORN/STROBE AND STROBE DEVICES SHALL ADHERE TO 2013 NFPA-72 18.5.5.4 FOR ADEQUATE INTENSITY 7. STROBES AND HORN/STROBES IN HALLWAYS SHALL BE LOCATED NO MORE THAN 15' FROM THE BEGINNING/END OF A HALLWAY AND BE SPACED NO MORE THAN 100' FROM EACH OTHER 8. ADDRESSABLE DETECTORS AND MODULES HAVE ADDRESSES NOTED 9. ALL HORN/STROBES SHALL BE PLACED ON HIGH VOLUME SETTING UNLESS NOTED OTHERWISE 10. VERIFY THAT VERIZON CELLULAR COVERAGE IS ADEQUATE AT FACP LOCATION. IF IT IS NOT WIRE 18 AWG 4 COND FROM FACP TO LOCATION WHERE VERISON CELLULAR SERVICE IS ADEQUATE 11. DUCT SMOKE DETECTORS WITH AUTOMATIC UNIT SHUTDOWN SHALL BE INSTALLED IN ANY UNIT, OR AGGREGATE OF UNITS THAT SUPPLY AIR TO THE SAME AREA, FOR A TOTAL AMOUNT OF AIR FLOW EQUAL TO OR EXCEEDING 2000 CFM. COORDINATE WITH HVAC CONTRACTOR FOR CLARIFICATION 12. ALL CIRCUITS ARE CLASSIFIED AS CLASS B WITH A SURVIVABILITY LEVEL OF 1. FPL IS ACCEPTABLE WHERE PERMITTED BY NFPA-70 AND ABOVE 10' AFF. ALL WIRING BELOW 10' AFF SHALL BE IN CONDUIT OR CONCEALED 13. ALL WIRING IS NOTED WITH HASH MARKS TO INDICATE THE NUMBER OF CONDUCTORS REQUIRED PINNACLE TECHNOLOGIES FIRE ALARM MATRIX GENERAL CAUSE EFFECT SOUND GENERAL BUILDING ALARM NOTIFY FIRE DEPARTMENT INITIATE SUPERVISORY SIGNAL TO MAINTENANCE DISPLAY EVENT ON FACP DISPLAY DISPLAY EVENT ON REMOTE ANNUNCIATOR DISPLAY RECALL ELEVATOR TO FIRST LOOR RECALL ELEVATOR TO SECOND FLOOR SHUT DOWN POWER TO ELEVATOR FIRE HAT FLASH IN AND ON ELEVATOR MANUAL PULL STATION X X X X SMOKE DETECTOR X X X X HAT DETECTOR X X X X SPRINKLER WATERFLOW X X X X SPRINKLER TAMPER X X X A/C POWER LOSS X X X LOSS OF BATTERY INTEGRITY X X X GROUND FAULT X X X OPEN NAC CIRCUIT X X X OPEN INITIATING CIRCUIT X X X SMOKE DETECOR FIRST FLOOR ELEVATOR DOOR X X X X X SMOKE DETECTOR SECOND FLOOR ELEVATOR DOOR X X X X X SMOKE/HEAT DETECTOR ELEVATOR CONTROL ROOM OR IN TOP/BOTTOM OF ELEVATOR SHAFT X X X X X X X FACP SLC ANN APU S D FACP F H M M F S T FIRE ALARM CONTROL PANEL REMOTE ANNUNCIATOR NAC POWER SUPPLY FIRE ALARM BELL DUCT SMOKE DETECTOR SMOKE DETECTOR HORN STROBE RELAY MODULE MANUAL PULL STATION SPRINKLER TAMPER HEAT DETECTOR MAGNETIC DOOR HOLDER MONITOR MODULE SPRINKLER FLOW 2-#18 3-#12 120VAC 2-#14 (ALL NACS) POTTER PFC-6030 LEGEND OF SYMBOLS ONE LINE DRAWING S R 5.1K EOL NAC 1 S S S M EXISTING FACP ALARM DRY CONTACTS C NO 5.1K EOL FACP S S S S M