NOTES:
1. SMOKE DETECTORS SHALL BE NO MORE THAN 30 LINEAR
FEET APART IN HALLWAYS
2. SMOKE DETECTORS SHALL BE LOCATED MORE THAN 3' FROM
ANY HVAC RETURN OR SUPPLY
3. SMOKE DETECTORS SHALL BE LOCATED NO MORE THAN 5'
FROM MAGNETIC DOOR HOLDERS
4. SMOKE DETECTORS SHALL BE LOCATED NO MORE THAN 15
LINEAR FEET FROM THE END/BEGINNING OF A HALLWAY
5. SMOKE DETECTORS SHALL BE PLACED A MINIMUM OF 3'
FROM CEILING FANS
6.CANDELA SETTINGS OFHORN/STROBE AND STROBE DEVICES
SHALL ADHERE TO 2013 NFPA-72 18.5.5.4 FOR ADEQUATE
INTENSITY
7. STROBES AND HORN/STROBES IN HALLWAYS SHALL BE
LOCATED NO MORE THAN 15' FROM THE BEGINNING/END OF A
HALLWAY AND BE SPACED NO MORE THAN 100' FROM EACH
OTHER
8. ADDRESSABLE DETECTORS AND MODULES HAVE
ADDRESSES NOTED
9. ALL HORN/STROBES SHALL BE PLACED ON HIGH VOLUME
SETTING UNLESS NOTED OTHERWISE
10. VERIFY THAT VERIZON CELLULAR COVERAGE IS ADEQUATE
AT FACP LOCATION. IF IT IS NOT WIRE 18 AWG 4 COND FROM
FACP TO LOCATION WHERE VERISON CELLULAR SERVICE IS
ADEQUATE
11. DUCT SMOKE DETECTORS WITH AUTOMATIC UNIT
SHUTDOWN SHALL BE INSTALLED IN ANY UNIT, OR AGGREGATE
OF UNITS THAT SUPPLY AIR TO THE SAME AREA, FOR A TOTAL
AMOUNT OF AIR FLOW EQUAL TO OR EXCEEDING 2000 CFM.
COORDINATE WITH HVAC CONTRACTOR FOR CLARIFICATION
12. ALL CIRCUITS ARE CLASSIFIED AS CLASS B WITH A
SURVIVABILITY LEVEL OF 1. FPL IS ACCEPTABLE WHERE
PERMITTED BY NFPA-70 AND ABOVE 10' AFF. ALL WIRING
BELOW 10' AFF SHALL BE IN CONDUIT OR CONCEALED
13. ALL WIRING IS NOTED WITH HASH MARKS TO INDICATE THE
NUMBER OF CONDUCTORS REQUIRED
PINNACLE TECHNOLOGIES FIRE ALARM MATRIX
GENERAL CAUSE EFFECT SOUND GENERAL
BUILDING ALARM
NOTIFY FIRE
DEPARTMENT
INITIATE
SUPERVISORY
SIGNAL TO
MAINTENANCE
DISPLAY EVENT
ON FACP DISPLAY
DISPLAY EVENT
ON REMOTE
ANNUNCIATOR
DISPLAY
RECALL ELEVATOR
TO FIRST LOOR
RECALL ELEVATOR
TO SECOND
FLOOR
SHUT DOWN
POWER TO
ELEVATOR
FIRE HAT FLASH IN
AND ON ELEVATOR
MANUAL PULL STATION X X X X
SMOKE DETECTOR X X X X
HAT DETECTOR X X X X
SPRINKLER WATERFLOW X X X X
SPRINKLER TAMPER X X X
A/C POWER LOSS X X X
LOSS OF BATTERY
INTEGRITY X X X
GROUND FAULT X X X
OPEN NAC CIRCUIT X X X
OPEN INITIATING CIRCUIT X X X
SMOKE DETECOR FIRST
FLOOR ELEVATOR DOOR X X X X X
SMOKE DETECTOR SECOND
FLOOR ELEVATOR DOOR X X X X X
SMOKE/HEAT DETECTOR
ELEVATOR CONTROL ROOM
OR IN TOP/BOTTOM OF
ELEVATOR SHAFT
X X X X X X X
FACP SLC
ANN
APU
S
D
FACP
F
H
M
M
F
S
T
FIRE ALARM CONTROL PANEL
REMOTE ANNUNCIATOR
NAC POWER SUPPLY
FIRE ALARM BELL
DUCT SMOKE DETECTOR
SMOKE DETECTOR
HORN STROBE
RELAY MODULE
MANUAL PULL STATION
SPRINKLER TAMPER
HEAT DETECTOR
MAGNETIC DOOR HOLDER
MONITOR MODULE
SPRINKLER FLOW
2-#18
3-#12 120VAC
2-#14
(ALL NACS)
POTTER
PFC-6030
LEGEND OF SYMBOLS
ONE
LINE
DRAWING
S
R
5.1K EOL
NAC 1
S
S
S
M
EXISTING
FACP
ALARM
DRY
CONTACTS
C
NO
5.1K EOL
FACP
S
S
S
S
M