HomeMy WebLinkAboutBRACING CALCS - 17-00184 & 17-00185 - 359 W 4th S - The LandingProject: Contractor:
Address: Address:
Telephone:
769
Structure attachment fitting or tension-only bracing system:
Type of brace:1007.5
Angle of brace:Sway brace (pipe attachment) fitting:
Least radius of gyration:*
L/R value:*1007.5
Maximum horizontal load:
Orientation of connecting surface: F
Fastener:
Type:
Diameter:
Length:
Adjusted load rating per 9.3.5.2.3:
Adjusted load rating per 9.3.5.2.3:
BRACING DISTANCE 40'=
Schedule 40
1/2"
Seismic Brace Assembly Detail
45-60 DEG
0.42
300
LAG SCREW
582
Fastener Information
Model: "E"
Listed load rating: 2015
Sheet __1__ of __2__
Seismic Brace Attachments
Laterial Seismic Bracing Calculations
Phoenix Fire Protection
4130 Airport Road
Nampa, Idaho 83687
(208) 461-9117
THE LANDING APARTMENTS
359 WEST 4TH SOUTH
4" SCH 10 TABLE 9.3.5.5.2(A)
Brace Information
(208) 468-9115
Model: #077Make: Afcon
REXBURG, IDAHO
Length of brace:
Diameter of brace:
10'6
1 in.
Make: Afcon
Listed load rating: 2015
(Provide detail on plans)
6-1/2" Length:
Maximum load:
Diameter Type Wp Total Weight
1 in. Sch 40 0.00 ft 2.05 lb/ft 0.35 0.00 lb
1 1/4 in. Sch 40 0.00 ft 2.92 lb/ft 0.35 0.00 lb
1 1/2 in. Sch 40 0.00 ft 3.61 lb/ft 0.35 0.00 lb
2 in. Sch 10 0.00 ft 4.22 lb/ft 0.35 0.00 lb
2 1/2 in. Sch 10 0.00 ft 5.89 lb/ft 0.35 0.00 lb
3 in. Sch 10 0.00 0 7.94 lb/ft 0.35 0.00 lb
4 in. Sch 10 40.00 ft 11.79 lb/ft 0.35 165.06 lb
6 in. Sch 10 0.00 ft 23.03 lb/ft 0.35 0.00 lb
8 in. Sch 10 0.00 ft 40.08 lb/ft 0.35 0.00 lb
Total weight 165.06 lb
189.82 lb
*Excludes tension-only bracing systems
c 2006 National Fire Protection Association
FIGURE A. 9.3.5(a) Seismic Bracing Calculation Form
Fp x 1.15
Total (ft)
NFPA 13 (p. 1 of 1)
Weight per ft Length (ft)
6-1/2"
380
SEE CALCULATIONS FOR DEGREE FROM VERTICAL
40'
Sprinkler System Load Calculation [Fp= __.35____ Wp (default is 0.5)]
Project: Contractor:
Address: Address:
Telephone:
Fax:
Structure attachment fitting or tension-only bracing system:
Type of brace:1007.5
Angle of brace:Sway brace (pipe attachment) fitting:
Least radius of gyration:*
L/R value:*1007.5
Maximum horizontal load:
Orientation of connecting surface: F
Fastener:
Type:
Diameter:
Longitudinal Seismic Bracing Calculations Sheet __2__ of __2__
THE LANDING APARTMENTS Phoenix Fire Protection
359 WEST 4TH SOUTH 4130 Airport Road
REXBURG, IDAHO Nampa, Idaho 83687
4" SCH 10 (208) 468-9115
769 (208) 461-9117
Brace Information Seismic Brace Attachments
Length of brace: 10'-6"
Diameter of brace: 1 in. Make: Afcon Model: #077
Fastener Information Seismic Brace Assembly Detail
Schedule 40 Listed load rating: 2015 Adjusted load rating per 9.3.5.2.3:
60 DEG MIN
0.42 Make: Afcon Model: #410
300 Listed load rating: 1000 Adjusted load rating per 9.3.5.10.3:
713
(Provide detail on plans)
LAG SCREW
1/2" Diameter:
Length:
Maximum load:
Diameter Type Wp Total Weight
1 in. Sch 40 0.00 ft 2.05 lb/ft 0.35 0.00 lb
1 1/4 in. Sch 40 0.00 ft 2.93 lb/ft 0.35 0.00 lb
1 1/2 in. Sch 40 0.00 ft 3.61 lb/ft 0.35 0.00 lb
2 in. Sch 40 0.00 ft 5.11 lb/ft 0.35 0.00 lb
2 1/2 in. Sch 10 0.00 ft 5.89 lb/ft 0.35 0.00 lb
3 in. Sch 10 0.00 ft 7.94 lb/ft 0.35 0.00 lb
4 in. Sch 10 80.00 ft 11.79 lb/ft 0.35 330.12 lb
6 in. Sch 10 0.00 ft 23.03 lb/ft 0.35 0.00 lb
8 in. Sch 10 0.00 ft 40.08 lb/ft 0.35 0.00 lb
Total weight 330.12 lb
379.64 lb
*Excludes tension-only bracing systems
c 2006 National Fire Protection Association FIGURE A. 9.3.5(a) Seismic Bracing Calculation Form
Length (ft) Total (ft) Weight per ft
1/2"
6-1/2"
380
SEE CALCULATIONS FOR DEGREE FROM VERTICAL
Sprinkler System Load Calculation [Fp= ______ Wp (default is 0.5)]
NFPA 13 (p. 1 of 1)
80
Fp x 1.15