HomeMy WebLinkAboutREVIEW REPORT - 17-00184 - 359 W 4th S - The Landing - N Bldg 1 - 26 UnitsReview
Report
Current Fire Alarm Review Status: REVISIONS
Application Number: 17-00184Permit Details
Application Received Date: 04/10/2017
Multi-Family Residential
Application Approved Date:
Application Approved Status: APPROVED
05/08/2017
359 W 4th S
The Landing - North Bldg 1 - 26 Units
Status of Plan Reviews Completed
05/15/2017Electrical Review REVISIONS
05/17/2017Electrical Review COMPLETED
05/17/2017Fire Department Review - Site Plan COMPLETED
05/24/2017Plumbing Review COMPLETED
05/24/2017HVAC Review COMPLETED
06/05/2017Building Review REVISIONS
06/12/2017Building Review REVISIONS
06/15/2017Building Review COMPLETED
07/06/2017Fire Sprinkler Review COMPLETED
08/22/2017Fire Alarm Review REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Fire Alarm Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Fire Alarm: Signalling Devices Placement REVISIONSSee other notes that are part of this review. No
signalling device noted on the exterior on each
building for water flow indication for fire
department-outside of fire riser room.
*Revisions Response :
Fire Alarm: Remote Annunciator Location N/ANot required to have one-nothing noted.
Fire Alarm: ADA Compliant Reviewed for code compliance.COMPLETED
Fire Alarm: Elevator Recall Reviewed for code compliance.COMPLETED
Fire Alarm: Battery Calculations Reviewed for code compliance.COMPLETED
Reviewed By: Bret Stoddard
Review Date: 08/22/2017
Plan Review Details
bret.stoddard@rexburg.org
Fire Alarm Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Fire Alarm Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Fire Alarm: Initiating Devices Placement Reviewed for code compliance. Note: Smoke
detectors in the ADA compliant dwelling units
must alarm only the devices in that unit upon
local alarm and also alarm under water flow or
system alarm. Not noted in the operations
matrix.
COMPLETED
Page 2 of 2
Approval of plans does not constitue approval of variance from code