HomeMy WebLinkAboutRESCHECK - 17-00499 - 796 S 2275 W - New SFRCREScheck Software Version 4.6.2
�J( Compliance Certificate
Project SF5B8 - HARTFORD
Energy Code:
2012 IECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Orientation:
Unspecified
Conditioned Floor Area:
2,320 ft2
Glazing Area
10%
Climate Zone:
6 (8693 HDD)
Permit Date:
0.0
Permit Number:
280
Construction Site: Owner/Agent: Designer/Contractor:
SUMMERFIELD, BLOCK: 8, LOT: 5 Kartchner Homes
REXBURG, ID 83440 Logan, UT
john@kartchnerhomes.com
Compliance: Passes using UA trade-off
Compliance: 0.0% Better Than Cade Maximum UA: 549 Your UA: 549
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Ceiling 1: Flat Ceiling or Scissor Truss
957
Second Wall Front: Wood Frame, 16" o.c.
344
Orientation: Front
Window 10: Wood Frame:Double Pane with Low -E
61
Orientation: Front
0.0
Second Wall Right: Wood Frame, 16" o.c.
209
Orientation: Right side
0.0
Window 10: Vinyl/Fiberglass Frame:Double Pane with Low -E
13
Orientation: Right side
0.0
Second Wall Rear: Wood Frame, 16" o.c.
280
Orientation: Back
0.0
Window 10: Vinyl/Fiberglass Frame:Double Pane with Low -E
40
Orientation: Back
Second Wall Left: Wood Frame, 16" o.c.
209
Orientation: Left side
Floor 1: All -Wood joist/Truss:Over Unconditioned Space
180
Floor 2: All -Wood joist/Truss:Over Outside Air
66
Main Wall Front: Wood Frame, 16" o.c.
383
Orientation: Front
Door 1: Solid
75
Orientation: Front
Main Wall Right: Wood Frame, 16" o.c.
235
Orientation: Right side
Project Title: SF5B8 - HARTFORD
Data filename: C:\Users\j hoe Ilei n.MAI N\Documents\REScheck\SF5B8 - HARTFORD.rck
50.0 0.0 0.026 25
22.0 0.0 0.056 16
0.320 20
22.0 0.0 0.056 11
0.320 4
22.0
0.0
0.056
13
0.320
13
22.0
0.0
0.056
12
30.0
0.0
0.033
6
30.0
0.0
0.033
2
22.0
0.0
0.056
17
0.150 11
22.0 0.0 0.056 13
Report date: 08/09/17
Page 1 of 9
main waii near: Wood Frame, 16" o.c. 315 22.0 0.0 0.056 12
Orientation: Back
Window 5: Vinyl/Fiberglass Frame:Double Pane with Low -E 93 0.320 30
Orientation: Back
Main Wall Left: Wood Frame, 16" o.c. 168 22.0 0.0 0.056 9
Orientation: Left side
Floor 3: Slab -On -Grade: Unheated 490 10.0 0.684 335
Insulation depth: 4,0'
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in
REScheck Version 4.6.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Signature Date
Project Title: SF5B8 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\j hoe Ilein.MAI N\Documents\REScheck\SF5B8 - HARTFORD.rck Page 2 of 9
CREScheck Software Version 4.6.2
�J( Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Pre-Inspection/Plan Review
Plans Verified
Value
Field Verified
Value
Complies? Comments/Assumptions
& Req.ID
103.1,
Construction drawings and
;❑Complies
103.2
(documentation demonstrates,❑Does
Not
[PR3]1
:energy code compliance for the
❑ Not Observable
;building envelope. :
❑Not Applicable
103.1,
'Construction drawings and❑Complies
103.2,
(documentation demonstrate
;❑Does Not
403.7
:energy code compliance for
[PR3]1
;lighting and mechanical systems.
I❑Not Observable
;Systems serving multiple
❑Not Applicable
;dwelling units must demonstrate '..
_
!compliance with the IECC '..
;Commercial Provisions.
302.1,
'Heating and cooling equipment is:
Heating: ! Heating:
I❑Complies
403.6
sized per ACCA Manual S based
Btu/hr_ Btu/hr_
I❑Does Not
(PR2]1-on
loads calculated per ACCA
Cooling: Cooling:❑Not
Observable I
..
Manual J or other methods I
approved by the code official.
Btu/hr Btu/hr_
:❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: SF5B8 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\] hoe lie! n.MAIN\Documents\REScheck\SF5B8 - HARTFORD.rck Page 3 of 9
Section
# Foundation Inspection
I
Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
& Re .ID
402.1.1
(Slab edge insulation R-value.
R-
R-❑Complies
;See the Envelope Assemblies
[FOM
E] Unheated
❑Unheated
❑Does Not (table for values.
❑ Heated
❑ Heated
;❑Not Observable
[]Not Applicable
1❑Complies
303.2,
'Slab edge insulation installed per
402.2.9
'manufacturer's instructions.
�- ❑Does Not
[F02]1
--❑Not Observable
14
•,
-_,❑Not Applicable
402.1.1
(Slab edge insulation
ft
ft
❑Complies ;See the Envelope Assemblies
[F03]'
depth/length.❑Does
Not table for values.
V
I❑Not Observable
j❑Not Applicable
303.2.1
IA protective covering is installed
-_
❑Complies
[F011]2
to protect exposed exterior
A. .,,, ,
" k
❑Does Not
V
insulation and extends a
i minimum of 6 in. below grade.
-?'❑Not
❑Not Observable
Applicable
403.8
�°snow- and ice-melting system
- ❑Complies
[FO12]2
Controls Installed.
- ❑Does Not
e
-'❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) +;. Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: SF5B8 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\SF5B8 - HARTFORD.rck Page 4 of 9
Section
#
Framing /Rough -In Inspection
Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
& Req.ID
402.1.1,
;Door U -factor.
U-
U -❑Complies ; See the Envelope Assemblies
402.3.4❑Does
Not table for values.
[FRl]1
;❑Not Observable
❑Not Applicable
402.1.1,
Glazing U-factor(area-weighted
U-
U- ;❑Complies see the Envelope Assemblies
402.3.1,
average).❑Does
Not ;table for values.
402.3.3,
402.3.6,
'..
;❑Not Observable
402.5❑Not
Applicable
[FR2]1
303.1.3
IU -factors of fenestration products '� ' -, 4"3a'
-..= ❑Complies
[FR4]1
:are determined in accordance
v
❑Does Not
:with the NFRC test procedure or
;taken from the default table.
❑Not Observable
_ ❑Not Applicable
402.4.1.1
;Air barrier and thermal barrier
- ❑Complies
[FR23]1
:installed per manufacturer's
. ❑Does Not
:instructions. 4
-° ❑Not Observable
❑Not Applicable
402.4.3
;Fenestration that is not site built
❑Complies
[FR20]1
its listed and labeled as meeting
❑Does Not
AAMA/WDMA/CSA 101/I.S.2/A440
;or has infiltration rates per NFRC _
,ti ❑Not Observable
400 that do not exceed code
- a
❑Not Applicable
limits.
402.4.4
'.. IC -rated recessed lighting fixtures s
❑Complies
[FR16]2
sealed at housing/interior finish
❑Does Not
,)
and labeled to indicate <_2.0 cfm
❑Not Observable
'.leakage at 75 Pa
❑Not Applicable j
403.2.1
Supply ducts in attics are ;
R-
R -;❑Complies
[FR12]1
;insulated to tR-8. All other ducts I
R-
R_ ❑Does Not
,e,,
in
in unconditioned spaces or
the building envelope are;❑Not
Observable
!insulated to z--R-6.pplicable
A
403.2.2
;AII joints and seams of air ducts,
1' ❑Complies
[FR13]1
:air handlers, and filter boxes areAi:;❑Does
;sealed.
Not
,10
❑Not Observable
- ❑Not Applicable
403.2.3
Building cavities are not used as -
'-
❑Complies
[FR15]3
!ducts or plenums.
-
"• ❑Does Not
Q'
-, ❑Not Observable
-:k:,❑Not Applicable
403.3
! HVAC piping conveying fluids
R-
R -❑Complies
[FR17]'
.above 105 QF or chilled fluids
❑Does Not
V
below 55 QF are insulated to >_R-
'3
:[_]Not Observable
❑Not Applicable
403.3.1
;Protection of insulation on HVAC
-x
-'--. ❑Complies
[FR24]1
!piping.
❑Does Not
❑Not Observable
❑Not Applicable
403.4.2
Hot water pipes are insulated to
R-
R- ❑Complies
[FR18]2
-.>R-3.❑Does
Not
❑Not Observable
❑Not Applicable
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: SF5B8 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF5B8 - HARTFORD.rck Page 5 of 9
Section
#
Plans Verified
Framing /Rough-In Inspection
Value
Field Verified
Value Complies?
Comments/Assumptions
& Req.ID
403.5
Automatic or gravity dampers are;
❑Complies
[FR19]'
installed on all outdoor air❑Does
'..
Not
intakes and exhausts.
-❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: SF588 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\jhoel lei n.MAI N\Documents\REScheck\SF5B8 - HARTFORD.rck Page 6 of 9
Section
#
Insulation Inspection
Plans Verified
Value
Field Verified
Value
Complies? Comments/Assumptions
& Req.ID
303.1 :All
installed insulation is labeled
❑Complies
[IN1312
for the installed R -values
'
"--r
_ 'r
❑Does Not
;provided.
viz ,r ti €``✓t�,.
❑Not Observable
❑Not Applicable
402.1.1,
Floor insulation R -value.
R-
R -❑Complies ;See the Envelope Assemblies
402.2.6
❑ Wood
❑ Wood ❑Does Not ;table for values.
[IN1]1
❑ Steel
! ❑ Steel ❑Not Observable
`❑Not
:
Applicable
!❑Complies
303.2, ;Floor
insulation installed perNE.'s,tv
402.2.7 :manufacturer's
instructions, and❑Does
Not
[IN2]i
in substantial contact with thIunderside
wk�rW_"�
of the subfloor.
❑Not Observable
❑Not Applicable j
402.1.1,
Wall insulation R -value. If this is a: R-_
R -_❑Complies ;See the Envelope Assemblies
402.2.5, :mass
wall with at least 112 of the
E] Woad
1 E]Wood ❑Does Not ;table for values.
402.2.6 :wall
[IN3)1 :exterior,
insulation on the wall
the exterior insulation
I El Mass
; El Mass ;❑Not Observable
:requirement
i
applies (FR10).
❑ Steel
1 ❑ Steel ❑Not Applicable
303.2 'Wall
insulation is installed peri`❑Complies
[IN4)1 !manufacturer's
instructions.
-
❑Does Not
❑Not Observable
_
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) ' �' Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: SF5B8 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF5B8 - HARTFORD.rck Page 7 of 9
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
402.1.1,
;Ceiling insulation R -value. ; R-
R-
❑Complies ! see the Envelope Assemblies
402.2.1,❑
Wood
ElWood❑Does
Not ;table for values.
402.2.2,
402.2.6
; El steel
; ❑ Steel
;❑Not Observable ;
[Fill'❑Not
Applicable
403.1.2
!.
LIComplies
303.1.1.1,
Ceiling insulation installed per❑Complies
303.2
manufacturer's instructions.
El Does Not
[FI211
Blown insulation marked every
Applicable
300 ftz.
service hot t
_ ❑ Not Observable
•-
JFl 11 ]2
systems have automatic•
❑Not Applicable
402.2.3
Vented attics with air permeable
:accessible manual contr Is
❑Complies
[FI22]�
insulation include baffle adjacent "
El Does Not
ApplicableElcomplies
to soffit and eave vents that
extends over insulation. - z
-- -
❑Not Observable
y
❑Not Applicable j
402.2.4
;Attic access hatch and door R-
R-
I❑Complies
[FI311
insulation >_R -value of the❑Does
Not
;adjacent assembly.
❑Not Observable
•
❑Not Applicable
402.4.1.2
Blower door test @ 50 Pa. <=5 ACH 50 =
j ACH 50 =❑Complies
[FI17]1
lath in Climate Zones 1-2, and❑Does
Not
i <=3 ach in Climate Zones 3-8.❑Not
Observable
❑Not Applicable
403.2.2
;Duct tightness test result of <=4 cfm/100cfm/100
;❑Complies
[FI411
:cfm/100 ft2 across the system or I ft2
ft'
;❑Does Not
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough -in
;❑Not Observable
;tests, verification may need to
;❑Not Applicable
;occur during Framing Inspection.
403.2.2.1
;Air handler leakage designated❑Complies
[FI2411
;by manufacturer at <=2% of
WIMM.E]Not
❑Does Not
design air flow.
Observable I
403.1.1
Programmable thermos tats
ocomplies
[Flgj2
'installed on forced air furnaces.
i h OlDoes Not
E]Not Observable
E]Not Applicable
403.1.2
Heat pump thermostat instanle
LIComplies
(F110]2
on heat pumps.
E]Does Not
v
able
[]Not ObseryONot
Applicable
403.4.1•
service hot t
r(� t•
w
•-
JFl 11 ]2
systems have automatic•
AIRF, Y K4 a#*�"
�i1 r • -ONot
:accessible manual contr Is
ObservableEhot
ApplicableElcomplies
LL-
•
_
�3
�I•- •
1 I High Impact (Tier 1) 12 IMedium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: SF5138 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF5B8 - HARTFORD.rck Page 8 of 9
Section
#
Final Inspection Provisions
Plans Verified
Value
Field Verified
Value
Complies? Comments/Assumptions
& Req.ID
404.1.1
'Fuel gas lighting systems have
14WE-EINotApplicable
❑Complies
[FI23]3
Ino continuous pilot light.
❑Does Not
❑Not Observable
❑Not Applicable
4013 -Compliance certificate posted.
❑Compliesz1F171
❑Does Not
❑Not Observable
❑Not Applicable
303.3
;Manufacturer manuals for
❑Complies
[FI18]3
!mechanical and water heating❑Does
Not
!systems have been provided.
_
[]Not Observable
-
❑Not Applicable j
Additional Comments/Assumptions:
1 1 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: SF5138 - HARTFORD Report date: 08/09/17
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\SF5138 - HARTFORD.rck Page 9 of 9
2012 IECC Energy
Efficiency Certificate
Above -Grade Wall 22.00
Below -Grade Wall 0.00
Floor 10.00
Ceiling / Roof 50.00
Ductwork (unconditioned spaces):
Window 0.32
Door 0.15
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments