HomeMy WebLinkAboutINSPECTION TICKET 1 - 17-00279 - Broulims Remodel - PharmacyInspection
Ticket
Commercial Electrical Rough-in on 06/29/2017: PASS
Permit Number: 17-00279Permit Details
Commercial Remodel
Permit Issued Date: 06/19/2017
Final Inspections Required
124 W Main St
Broulims Remodel - Pharmacy
Inspection Details
bret.stoddard@rexburg.org
Inspected By: Bret Stoddard
Commercial Electrical Rough-in on 06/29/2017: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Unused openings have been closed. 110.12(A),
408.7
COMPLETED
Wiring methods spaced from edges of framing
and protection from nails and screws. (1/1/4”)
300.4(A)(B)(D)&(E) (1/1/2” roof decking) (1/16”
nail plate)
COMPLETED
Continuity and tightness of fittings in metal
raceways and enclosures. 300.10
COMPLETED
Adequate length of free conductors in boxes.
300.14
COMPLETED
Boxes must be installed at junction, splice,
outlet, switch, and pull points. 300.15
COMPLETED
Raceways and cables are secured to boxes.
314.17(B)(C)
COMPLETED
All boxes will be accessible. 314.29 COMPLETED
Positioning of boxes that are intended to be
flush with combustible and noncombustible
finished surfaces.
COMPLETED
Approved for cover in noted areas.For cover in the framed walls remodeled area in
the south area of the pharmacy only. This is a
small remodel including the doorway and little
room on the south end of the pharmacy.
COMPLETED