COM & MFR Electrical Service Inspection on 08/14/2017: PASS
Permit Number: 17-00418Permit Details
Electrical Only Commercial
Permit Issued Date: 07/21/2017
Final Inspections Required
104 College Ave
Calvary Chapel - Replace Panel
Inspection Details
bret.stoddard@rexburg.org
Inspected By: Bret Stoddard
COM & MFR Electrical Service Inspection on 08/14/2017: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Overhead service conductors-proper clearances.
230.24(A)&(B)
COMPLETED
Each building has only one service or justified for
more than one. 230.2
COMPLETED
Unused openings have been closed. (K.O. seals,
etc.) 110.12(A), 408.7
COMPLETED
Securely mounted gear-panels, meter base, etc.
110.13
COMPLETED
Check temperature ratings of equipment-lugs,
breakers, splices, etc. 110.14(A), (B), (C)
COMPLETED
Proper clearances about electrical equipment
indoors and outdoors. 110.26 (A), (E),(E)(2) and
(F)
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc. 250.52(A)
(4-7)
COMPLETED
Grounding electrode system conductors sized
and protected appropriately. 250.66, 250.64(F),
250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved methods.
250.64(C)(F)
COMPLETED
Grounding electrode connection(s) are accessible
if not irreversible. 250.68(A)
COMPLETED
Identify wet and damp locations for
panels-NEMA 3R, etc. 408.16, 408.37, 312.12
COMPLETED
Proper wiring bending space in panel &
associated enclosures, gutters, etc. 408.3(G),
312.6, 408.55(A)(B)&(C)
COMPLETED
Panel or switchgear service rated. 408.3(C)COMPLETED
Main bonding jumper sized to 250.28(D), and all
panels bonded together using an equipment
bonding conductor sized in accordance with
250.122 or 250.66 as appropriate.
COMPLETED
Page 1 of 2
(Continued)
Permit Number: 17-00418
D ESCRIPTIO N CO MMEN TS STATUS
Service conductors are adequate size and rating.
230.23, 230.31, 230.42
COMPLETED
Approved to be energized for permanent power
(will send permit to utility).
To be re-energized for permanent power-all
items corrected from prior inspection. They
moved the electrical service over past the
windows and away from the drip edge of the
roof.
COMPLETED