HomeMy WebLinkAboutRESCHECK - 17-00487 - 802 S 2275 W - New SFRfZREScheck Software Version 4.6.2 Compliance Certificate Project SF4B8 - DAVENPORT Energy Code: 2012 IECC Location: Rexburg, Idaho Construction Type: Single-family Project Type: New Construction Orientation: Unspecified Conditioned Floor Area: 2,204 ft2 Glazing Area 9% Climate Zone: 6 (8693 HDD) Permit Date: Permit Number: 30 Construction Site: Owner/Agent: Designer/Contractor: 802 S. 2275 W. Kartchner Homes Summerfeild, Block -8, Lot -4 Logan, UT 84321 RESBURG, ID 83440 Compliance: Passes using JA trade-off Compliance: 1.0% Better Than Cade Maximum UA: 200 Your UA: 198 The % Better or Worse Than Code Index reflects how close to compliance the house Is based on code trade-off rules. It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home. Envelope Assemblies Ceiling 1: Flat Ceiling or Scissor Truss 1,446 50.0 0.0 0.026 38 Main Wall Front: Wood Frame, 16" D.C. 432 22.0 0.0 0.056 21 Orientation: Front Window 4: Vinyl/Fiberglass Frame:Double Pane with Low -E 30 0.300 9 Orientation: Front Door 1: Solid 20 0.170 3 Orientation: Front Main Wall Right: Wood Frame, 16" o.c. 324 22.0 0.0 0.056 17 Orientation: Right side Window 7: Vinyl/Fiberglass Frame:Double Pane with Low -E 25 0.300 8 Orientation: Right side Main Wall Rear: Wood Frame, 16" o.c. 336 22.0 0.0 0.056 15 Orientation: Back Window 5: Vinyl/Fiberglass Frame:Double Pane with Low -E 51 0.300 15 Orientation: Back Door 2: Glass 20 0.170 3 Orientation: Back Main Wall Left: Wool(Frame, 16" o.c. 312 22.0 0.0 0.056 17 Orientation: Left side BASEMENT WALL FRONT: Wood Frame, 16" o.c. 131 22.0 0.0 0.056 7 Orientation: Front BASEMENT WALL LEFT: Wood Frame, 16" o.c. 174 22.0 0.0 0.056 9 Orientation: Left side Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 1 of 9 Winoow, 9: Vinyl/Fiberglass Frame:Double Pane with Low -E 20 0.300 6 Orientation: Left side BASEMENT WALL REAR: Wood Frame, 16" o.c. 156 22.0 0.0 0.056 8 Orientation: Back Window 8: Vinyl/Fiberglass Frame:Double Pane with Low -E 20 0.300 6 Orientation: Back Basement - FOUNDATION WALL: Solid Concrete or Masonry 232 0.0 21.0 0.039 9 Orientation: Front Wall height: 3.0' Depth below grade: 3.0' Insulation depth: 3.0' Crawl 1: Solid Concrete or Masonry 269 0.0 21.0 0.041 7 Wall height: 3.0' Depth below grade: 3.0' Insulation depth: 3.0' Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in REScheck Version 4.6.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist. Date Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 2 of 9 CREScheck Software Version 4.6.2 �J( Inspection Checklist Energy Code: 2012 IECC Requirements: 0.0% were addressed directly in the REScheck software Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Pre-Inspection/Plan Review & Req.ID Plans Verified Value Field Verified Value Complies? Comments/Assumptions 103.1, ;Construction drawings and❑Complies 103.2 (documentation demonstrate ❑Does Not [PRl]1 ;energy code compliance for the :building envelope. ❑Not Observable ❑Not Applicable 103.1, ;Construction drawings and❑Complies 103.2, :documentation demonstrate,❑Does Not 403.7 ;energy code compliance for [PR3]1 :lighting and mechanical systems. -- :❑Not Observable :Systems serving multiple❑Not Applicable j :dwelling units must demonstrate ;compliance with the IECC '.. ;Commercial Provisions. 302 1, c,Heating and cooling equipment is Isized Heating: Heating: Elcomplies 403.6 [PR2]2 per ACOA Manual S based ;on loads calculated per ACCA Btu/hr_ I Btu/hr !F -]Does Not .0) J Manual J or other methods Cooling: ;Cooling: ❑Not Observable Btu/hr_ approved by the code official, ;Btu/hr_❑Not Applicable n.anronal Comments/Assumptions: 1 I High Impact (Tier 1) Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 3 of 9 Section # Foundation Inspection Plans Verified Value Field Verified Value Complies? Comments/Assumptions & Req.ID 402.1.1 (F0411 'Conditioned basement wall ; 'insulation R -value. Where interior; R- R- R -❑Complies See the Envelope Assemblies ',❑Does Not ;table for values. 0' insulation is used, verification !may need to occur during❑Not R- — Observable Insulation Inspection. Not ;❑Not Applicable ;required in warm -humid locations ;in Climate Zone 3. 303.2 ;Conditioned basement wall -� ❑Complies [F05]1 :insulation installed per ❑Does Not ,manufacturer's instructions. - ❑Not Observable j ❑Not Applicable j 402.2.8 [F0611 ;Conditioned basement wall :insulation depth of burial or ft ftI❑Complies ;See the Envelope Assemblies ❑Does Not ;table for values. ;distance from top of wall. ❑Not Observable j❑Not Applicable 402.2.10 [FO7]1 ;Unvented crawl space wall ;insulation R -value. R- R -❑Complies ;See the Envelope Assemblies for R- R -_❑Does Not ;table values. I❑Not Observable ❑Not Applicable 303.2 ;Unvented crawl space wall❑Complies [F08]1 !insulation installed per❑Does Not manufacturer's instructions. ❑Not Observable ; ❑Not Applicable 402.2.10 'Unvented crawl space continuous '..❑Complies [F09]1 'vapor retarder installed over❑Does Not exposed earth, joints overlapped- ;by 6 in, and sealed, extending at❑Not Observable j :least 6 in. up and attached to the❑Not Applicable ;wall 402.2.9 F01011 '.. Unvented crawl space wall '.insulation depth of burial or❑Does in._ in.❑Complies ;See the Envelope Assemblies Not ;table for values. distance from tap of wall. ❑Not Observable ❑Not Applicable 303.2.1 iA protective covering is installed '...❑Complies [F011]' to protect exposed exterior'.❑Does Not J insulation and extends a minimum of 6 in, below grade !❑Not Observable !❑Not Applicable 403.8 ;Snow- and ice -melting system !.❑Complies [F012]2 :controls installed. ❑Does Not '..❑Not Observable ; ❑Not Applicable j Additional Comments/Assumptions: 1 I High Impact (Tier 1) Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 4 of 9 # Framing / Rough -In Inspection Plans Verified I Field Verified & Re .ID Value Value 402.1.1, Door U -factor. U-- 402.3.4 .are determined in accordance [FR111 ;with the NFRC test procedure or leakage at 75 Pa. ;taken from the default table. _ .402.1.1, ;Glazing U -tactor (area -weighted ; U- 402.3.1, 'average). — 402.3.3, ;3. 402.3.6, Protection of insulation on HVAC 402.5 403.2.2!All [FR211 [FR1311 � I 303.1.3 U -factors of fenestration products- [FR411 .are determined in accordance 'and labeled to indicate <_2.0 cfm ;with the NFRC test procedure or leakage at 75 Pa. ;taken from the default table. _ 402.4.1.1 ;Air barrier and thermal barrier [FR2311 .installed per manufacturer's ;® ;instructions. 402.4.3 !Fenestration that is not site built [FR2011 ;is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 ;or has Infiltration rates per NFRC 1400 that do not exceed code 402.4.4 ,a IC -rated recessed li htin fixtures' (FR1612 'aealed ;Building cavities are not used at housing/interior9finish g/ 'and labeled to indicate <_2.0 cfm leakage at 75 Pa. 403.2.1 'Supply ducts in attics are [FR1211 insulated to 2!R-8. All other ducts — ;® in unconditioned spaces or R — ;3. loutside the building envelope are Protection of insulation on HVAC 'insulated to all -6. 403.2.2!All joints and seams _,fair ducts, [FR1311 lair handlers, and filter boxes are - ;sealed. 403.2.3 ;Building cavities are not used [FR1511 as ;ducts or plenums. 403.3 'HVAC piping conveying fluids j' [FR1711 R- !above 105 4F or chilled fluids below 55 QF are insulated to l ;3. 403.3.1 Protection of insulation on HVAC [FR2411 (piping. 403.4.2 Hat water pipes are insulated to R- [FR18]2>_R-3. - �A R- R-. R-, U- Complies? I Comments/Assumptions omplles ;See the Envelope Assemblles oes Not ; table for values. Dt Observable U-- ;❑Complies ;See the Envelop ❑Does Not table for values. I❑Not Observable ❑Not Applicable cl�❑Complies ❑Does Not G5 I € ❑Not Observable ❑Not Applicable I❑Complies ❑Does Not ❑Not Observable ❑Not Applicable j ❑Complies ❑Does Not !❑Not Observable ❑Not Applicable ❑Complies ❑Does Not ❑Not Observable ❑Not ADolicahle 'L-IDoes Not ❑Not Observable ❑Not Applicable ❑Compl ❑Does Not ❑Not Observable ❑Not ADolirahla ❑Does Not ❑Not Observable j pnes s Not Observable LJCor lies ❑Does Not :❑Not Observable ❑Not ADDlirahla s Not Observable Project Title: SF4B8 - DAVENPORT - ""PdLi t I ier j1 Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF468-DAVENPORT.rck Report date: 08/07/17 Page 5 of 9 Section # Framing / Rough -In Inspection Plans Verified Value Field Verified Value Complies? Comments/Assumptions & Req.!D 403.5 -Automatic or gravity dampers are '...❑Complies [FR1912 installed on all outdoor air ❑Does Not , intakes and exhausts. ❑Not Observable; j❑Not Applicable Auuntionai comments/Assumptions: 1 High Impact (Tier 1) � Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: SF4138 - DAVENPORT Report date: 08/07/17 Data filename: C:\Users\jhoel lei n.MAI N\Documents\REScheck\SF4BEI - DAVENPORT.rck Page 6 of 9 Section Plans Verified Field Verified # Insulation Inspection Value Value Complies? Comments/Assumptions & Req.ID 3011 All installed insulation is labeled ❑Complies iIN��4 prthe installed R -values ❑Does Not .' ',❑Not Observable Additional Comments/Assumptions: 11 High Impact (Tier 1) r2:. Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:WsersUhoellei n -MAI N\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 7 of 9 ❑Not Applicable 402.1.1, 402.2.5, ;Wall insulation R -value. If this is a R- :mass wall with at least 'A of the ; ❑ Wood❑Wood R- ❑Complies :see the Envelope Assemblies Does Not table for values. 402.2.6 [IN311 ;wall insulation on the wall :exterior, the exterior insulation ❑Mass ❑Mass ❑Not Observable (arequirement applies (FR10). j ❑ Steel ❑ Steel❑Not Applicable j 303.2 .Wall insulation is installed per -'❑Complies [IN4)1 :manufacturer's instructions. El Does Not ❑Not Observable j ❑Not Applicable Additional Comments/Assumptions: 11 High Impact (Tier 1) r2:. Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:WsersUhoellei n -MAI N\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 7 of 9 Section # Final Inspection Provisions Plans Verified Value Field Verified Value Complies? Comments/Assumptions & Req.ID 402.1.1, (Ceiling insulation R -value. R- R -_❑Complies ;See the envelope Assemblles 402.2.1, j [D Wood ❑ Wood :❑Does Not :table for values. 402.2.2, 402.2.6 ❑ Steel ❑ Steel❑Not Observable [Fill' ❑Not Applicable 303.1.11, ;Ceiling insulation installed per❑Complies ' 303.2 :manufacturer's instructions. ` ;- +u ❑Does Not [FI211 ;Blown insulation marked every ft'. :'slur - ❑Not Observable 1300 ❑Not Applicable 402.2.3 !Vented attics with air permeable ❑Complies tFI2212 insulation include baffle adjacent ;_ .4,` - -.;, ❑Does Not oto soffit and eave vents that over insulation. - 'r - ❑Not Observable .'extends _ ❑Not Applicable 402.2.4 (Attic access hatch and door R- R - [ F1311 insulation all -value of the j❑Does Not ;adjacent assembly. I❑Not Observable ;❑Not Applicable 402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 =_ ACH 50=_ ;❑Complies [FI1711 lath in Climate Zones 1-2, and ;❑Does Not � <=3 ach in Climate Zones 3-8. :❑Not Observable ❑Not Applicable 403.2.2 ;Duct tightness test result of <=4 cfm/100 cfm/100❑Complies [FI411 ]cfm/100 ft2 across the system or ft' ft' ;❑Does Not 'handler <=3 cfm/100 ft2 without air @ 25 Pa. For rough -in ❑Not Observable :tests, verification may need to -. ;❑Not Applicable ;occur during Framing Inspection. 403.2.2.1 ;Air handler leakage designated (❑Complies [F12411 Iby manufacturer at <=2% of ❑Does Not ,design airflow. '.. ❑Not Observable ❑Not Applicable 403.1.1 Programmable thermostats ❑Com lies P IF 19]2 installed on forced air furnaces. - ❑Does Not 9V ❑Not Observable ❑Not Applicable 403.1.2 '.. Heat pump thermostat installed❑Complies Fl 1012 ;on heat pumps.❑Does Not � ❑Not Observable I❑Not Applicable 403.4.1 ;Circulating service hot water ❑Complies [F:11]' -.systems have automatic or [:]Does Not accessible manual controls. ❑Not Observable ❑NotApplicable 403.5.1 A:: mechanical ventilation system -.❑Complies [FI25]' Mans not part of tested and listed ❑Does Not : HVAC equipment meet efficacy l and air flow limits. j Not Observable - ❑ ❑Not Applicable 404.1 75% of lamps in permanent Complies [FI611 fixtures or 75% of permanent❑Does ;fixtures have high Not efficacy lamps. : Does not apply to low -voltage ❑Not Observable (lighting.❑Not Applicable 1 I High Impact (Tier 1) Medium Impact (Tier 2) $ Low Impact (Tier 3) Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 8 of 9 Section # Final Inspection Provisions Plans Verified Value Field Verified Value Complies? Comments/Assumptions & Req.ID 404.1.1 Fuel gas lighting systems have ;❑Complies [FI23]3 no continuous pilot light. ❑Does Not ❑Not Observable ;i❑Not Applicable 401.3 .Compliance certificate posted. -;❑Complies [FI712 '...❑Does Not ❑Not Observable ❑Not Applicable 303.3 Manufacturer manuals for iOComplies [FI18]3 'mechanical and water heating - ,I❑Does Not systems have been provided.. -❑Not Observable ❑Not Applicable : Additional Comments/Assumptions: 111 High Impact (Tier 1) [1 1 Medium Impact (Tier 2) 13 Low Impact (Tier 3) Project Title: SF4B8 - DAVENPORT Report date: 08/07/17 Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\SF4B8 - DAVENPORT.rck Page 9 of 9 2012 IECC Energy Efficiency Certificate Above -Grade Wall 22.00 Below -Grade Wall 21.00 Floor 0.00 Ceiling / Roof 50.00 Ductwork (unconditioned spaces): Window 0.30 Door 0.17 Heating System: Cooling System: Water Heater: Name: Date: Comments