HomeMy WebLinkAboutPLANS - 17-00454 - 995 Hillview Dr - Solar PanelsS H E E T I N D E X P V 1 - C O V E R S H E E T P V 2 - P R O P E R T Y P L A N P V 3 - S I T E P L A N P V 4 - E Q U I P M E N T & A T T A C H M E N T D E T A I L P V 5 - E L E C T R I C A L S I N G L E L I N E D I A G R A M P V 6 - E L E C T R I C A L C A L C U L A T I O N S & S T R I N G D I A G R A M P V 7 - M B D C A L C S . ( I F N E E D E D ) P V 8 - L A B E L S & L O C A T I O N S P V 9 - S T R I N G & S E O P T I M I Z E R P V 1 0 - P L A C A R D ( I F N E E D E D - N E C 6 9 0 . 5 6 ( B ) ) GENERAL NOTES O C C U P A N C Y - R 3 C O N S T R U C T I O N - V - B Z O N I N G : R E S I D E N T I A L ASC E 7 - 1 0 W I N D S P E E D : 1 1 5 M P H GRO U N D S N O W L O A D : 3 0 P S F EXP O S U R E C A T E G O R Y : C SEIS M I C D E S I G N C A T E G O R Y : D SCOP E O F W O R K DC SY S T E M S I Z E : 4 . 6 4 k W D C ROOF T Y P E : C o m p S h i n g l e MODU L E S : ( 1 6 ) Q . C e l l s Q . P e a k B L K - G 4 . 1 2 9 0 INVER T E R ( S ) : S o l a r E d g e S E 3 8 0 0 H - U S , - - - - RACKI N G : I r o n R i d g e X R 1 0 P V M o u n t i n g & R a c k i n g S y s t e m ANCH O R E D O N M A X 4 8 I N C H C E N T E R S U S I N G U L L I S T E D R A C K I N G SYST E M T O S P E C . AERIA L V I E W SITE NOTES1. A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.2. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITYINTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.3. THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, ORBUILDING ROOF VENTS.4. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICALEQUIPMENT WILL BE PROVIDED AS PER SECTION [NEC 110.26]5. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGEBETWEEN THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IF SMALLER THAN #6AWG COPPER WIRE PER NEC 250-64B. THE GROUNDING ELECTRODE CONDUCTOR WILL BECONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64C.]6. ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITHTHIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOFCOVERING SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE.7. RIGID CONDUIT (AND/OR NIPPLES) MUST HAVE A PULL BUSHING TO PROTECT WIRES.8. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDEDCONDUCTOR (USE POLARIS BLOCK OR NEUTRAL BAR)9. ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT. REDUCING WASHERSDISALLOWED ABOVE LIVE PARTS, MEYERS HUBS RECOMMENDED10. UV RESISTANT CABLE TIES(NOT ZIP TIES) USED FOR PERMANENT WIRE MANAGEMENT OFFTHE ROOF SURFACE IN ACCORDANCE WITH NEC 110.2,110.3(A-B). 300.411. SOLADECK JUNCTION BOXES MOUNTED FLUSH W/ROOF SURFACE TO BE USED FOR WIREMANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS.SOLAR CONTRACTOR1. MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646, IEC61730.2. IF APPLICABLE, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDINGLUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.3. AS INDICATED BY DESIGN, OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USEDIN PLACE OF STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATIONAND APPROVED BY THE AHJ.4. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS ANDARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.5. CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED ANDSEALED WITH A SUITABLE SEALING COMPOUND.6. DC WIRING LIMITED TO MODULE FOOTPRINT W/ ENPHASE AC SYSTEM.7. ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/SUITABLE WIRING CLIPS.8. MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FORVOC UNLESS NOT AVAILABLE.9. ALL INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS,AC PHOTOVOLTAIC MODULES, DC COMBINERS, DC-TO-DC CONVERTERS,SOURCE CIRCUITCOMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWERSYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (B).10. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE.EQUIPMENT LOCATIONS1. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY [NEC 110.26].2. EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATINGTEMPERATURE AS SPECIFIED BY [NEC 690.31 (A)-(B)] AND [NEC TABLE 310.15 (B)].3. ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT ADJACENTTO THE UTILITY AC DISCONNECT, OR NOT WITHIN SIGHT OF THE UTILITY AC DISCONNECT.4. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDINGTO NEC APPLICABLE CODES.5. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGEWHEN APPROPRIATE.1. ALL WORK SHALL COMPLY WITH 2014 NATIONAL ELECTRIC CODE (NEC), 2015INTERNATIONAL RESIDENTIAL CODE (IRC), 2014 NATIONAL BUILDING CODE (NBC), 2015INTERNATIONAL BUILDING CODE (IBC), 2015 INTERNATIONAL PLUMBING CODE (IBC), ANDALL STATE AND LOCAL BUILDING, ELECTRICAL, AND PLUMBING CODES.2. DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. D A T E D R A W I N G B Y P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . P V 1 C O V E R S H E E T C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7 0 SITE INFORMATION: DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 MACINVMSP N DCDCDCDCDCDCDCDCDCDCDCDCDCDCDCDCDCD C DCDCDCDC DCDCDCD C DCDCDCDCDCDCJB J B FRONT OF HOME995 Hillview DrDC SYSTEM SIZE: 4.64 kW DCROOF TYPE: Comp Shingle(16) Q. Cells Q.Peak BLK-G4.1 290 SolarEdge SE3800H-US,----INVERTER 8 ' 1 6 ' S C A L E : 1 / 1 6 " = 1 ' - 0 " 0 ' 3 2 ' 4 ' L E G E N D A C M I N V E R T E R & D C D I S C O N N E C T I N V A C D I S C O N N E C T U T I L I T Y M E T E R / S E R V I C E P A N E L P V R E V E N U E M E T E R J B J U N C T I O N B O X P R O P E R T Y L I N E F I R E S E T B A C K P V S O L A R M O D U L E E M T C O N D U I T R U N ( T O B E D E T E R M I N E D I N F I E L D ) P V W I R E S T R I N G P V S U B ( E ) S U B P A N E L L C ( N ) L O A D C E N T E R MP1AZIMUTH:181°PITCH:28°TSRF:93% M P 2 A Z I M U T H : 9 1 ° P I T C H : 2 8 ° T S R F : 8 0 % D A T E D R A W I N G B Y P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . P V 2 P R O P E R T Y P L A N 0 C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7 SITE INFORMATION: DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 2 5 4 ' - 4 " 9 7 ' - 1 1 " 2 5 4 ' - 4 " 97'-11"AC disconnect to be located within 10' of Utility Meter. MACINVMSP N D C D C D C D C D C D C D C D C D C D C DCDCDCDCDCDC D C D C D C D C D C D C DCDCD C D C DCDCDCDCDCDC J B J B FRONT OF HOME 4 ' 8 ' S C A L E : 1 / 8 " = 1 ' - 0 " 0 ' 2 ' 1 6 ' L E G E N D A C M I N V E R T E R & D C D I S C O N N E C T I N V A C D I S C O N N E C T U T I L I T Y M E T E R / S E R V I C E P A N E L P V R E V E N U E M E T E R J B J U N C T I O N B O X P R O P E R T Y L I N E F I R E S E T B A C K P V S O L A R M O D U L E E M T C O N D U I T R U N ( T O B E D E T E R M I N E D I N F I E L D ) P V W I R E S T R I N G P V S U B ( E ) S U B P A N E L L C ( N ) L O A D C E N T E R DC SYSTEM SIZE: 4.64 kW DCROOF TYPE: Comp Shingle(16) Q. Cells Q.Peak BLK-G4.1 290 SolarEdge SE3800H-US,----INVERTER M P 1 A Z I M U T H : 1 8 1 ° P I T C H : 2 8 ° T S R F : 9 3 % M P 2 A Z I M U T H : 9 1 ° P I T C H : 2 8 ° T S R F : 8 0 % D R A W I N G B Y D A T E P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . P V 3 S I T E P L A N C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7 0 SITE INFORMATION: DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 AC disconnect to be locatedwithin 10' of Utility Meter. I r o n R i d g e X R 1 0 P V R A I L F l a s h F o o t 2 2 ' - 8 " M I N - 3 ' - 1 0 " M A X H P V 4 I r o n R i d g e X R 1 0 P V R A I L P V M O D U L E 4 8 " M A X . " 1 ' - 1 1 " M A X . E P V 4 G P V 4 A R R A Y D E T A I L , F R O N T V I E W S c a l e : 3 / 8 " = 1 ' - 0 " 2 8 ° 1 0 " M I N - 1 ' - 4 " M A X 2 ' - 8 " M I N - 3 ' - 1 0 " M A X R O O F T Y P E : C o m p S h i n g l e R O O F F R A M I N G T Y P E : M a n u f a c t u r e d t r u s s R A F T E R O R T O P C H O R D S I Z E : 2 x 4 R A F T E R O R T O P C H O R D S P A C I N G : 2 4 " O . C . C E I L I N G J O I S T O R B O T T O M C H O R D S I Z E : 2 x 4 C E I L I N G J O I S T O R B O T T O M C H O R D S P A C I N G : 2 4 1 0 " M I N - 1 ' - 4 " M A X A R R A Y D E T A I L , S I D E V I E W S c a l e : 3 / 8 " = 1 ' - 0 " (E) ROOFMEMBRANEIRONRIDGEFLASHFOOTASSEMBLY PV MODULE(E) BUILDIN G STRUCTUREDETAIL, STANDOFFScale: 3" = 1'-0"H Q. Cells Q.P e a k B L K - G 4 . 1 2 9 0 5/16" STAIN L E S S S T E E L L A G BOLT AND F L A T W A S H E R 4"Iron Ridge X R 1 0 P V I R O N R I D G E RAIL2 12" MIN.DEPTHFLASHING PV ARRAY STRUCTURAL CRITERIAPV MODULE COUNT:ARRAY AREA:ARRAY WEIGHT:DISTRIBUTED LOAD:16 MODULESModule Count X 17.51ft² = 280.2ft²Array Weight ÷ Array Area = 2.86 lbs/ft²Module Count x 50lbs = 800.0lbs #OF ATTACHMENT POINTS:38POINT LOAD:Array Weight ÷ Attachments = 21.3lbs/attac h m e n t ROOF AREA:3235.8ft²%OF ARRAY/ROOF:9.8%PV MODULE FRAMEIRONRIDGE RAILDETAIL, END CLAMP FRONTScale: 6" = 1'-0"G IRONRIDGE STOPPER SLEEVEIRONRIDGE UNIVERSALFASTENING OBJECT1"P V M O D U L E F R A M E I R O N R I D G E R A I L DETAIL, MID CLA M P F R O N T Sc a l e : 6 " = 1 ' - 0 " E IRONRIDG E U N I V E R S A L FASTENIN G O B J E C T D R A W I N G B Y D A T E P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . P V 4 E Q U I P . D E T A I L C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7 0 SITE INFORMATION: DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 ASCE 7-10 WIND SPEED: 115 MPHGROUND SNOW LOAD: 30 PSF EXPOSURE CATEGORY: CSEISMIC DESIGN CATEGORY: D 120/240 VAC 60HZTO UTILITYGRID (E)(E)LOADSNG SUPPLY SIDE CONNECTIONPER NEC 230.46, NEC 230.79(D), NEC 705.12(A)NEGC L2 L1 (E)200A / 2PL2L1 (E)200A MAIN SERVICE PANEL(E)200A / 2P MAIN BREAKER20AFUSES15(E)GROUNDINGELECTRODEINTERCONNECTION NOTES1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95]2. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING.3. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)] WITH SERVICEENTRANCE CONDUCTORS IN ACCORDANCE WITH [NEC 240.21(B)]DISCONNECT NOTES1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH ISOPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THETERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS)2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BELOCKABLE, AND BE A VISIBLE-BREAK SWITCH3. DC CURRENT CONDUCTORS ARE TO REMAIN OUTSIDE OF BUILDING PRIOR TOEITHER A FUSEABLE SOURCE CIRCUIT PV AC DISCONNECTFUSED, AIC 10kALOCKABLE, VISIBLE OPEN30A, 240V, 2-POLE A C D C L 1 L 2 + - + - N G ( 1 ) S T R I N G O F 1 6 M O D U L E S + G - ( 1 6 ) Q . C e l l s Q . P e a k B L K - G 4 . 1 2 9 0 3 / 4 " E M T 2 1 I N T E G R A T E D R A P I D S H U T D O W N D C D I S C O N N E C T J U N C T I O N B O X = = = = = = = = ( 1 6 ) P 3 0 0 S o l a r E d g e D C - t o - D C P o w e r O p t i m i z e r S o l a r E d g e S E 3 8 0 0 H - U S I N V E R T E R U L 1 7 4 1 C O M P L I A N T D A T E D R A W I N G B Y P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . P V 5 E L E C . 3 L I N E D I A G . C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7 0 SITE INFORMATION: DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 AC disconnect to be located withi n 1 0 ' o f U t i l i t y M e t e r . GROUNDING NOTES1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH [NEC 690-47] AND[NEC 250-50] THROUGH [NEC 250-60] SHALL BE PROVIDED. PER NEC,GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED ANDBONDED TO AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE,OR INADEQUATE, OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTALGROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATIONCONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP.2. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN #8 AWG ANDNO GREATER THAN #6 AWG COPPER AND BONDED TO THE EXISTING GROUNDINGELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM.3. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO [NEC 250.21], [NEC TABLE250.122],AND ALL METAL PARTS OR MODULE FRAMES ACCORDING TO [NEC690.46].4. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO [NEC690.42].5. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THATTHE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTORTO ANOTHER MODULE.6. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTSIDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.7. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISHAS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH TERMINATIONGROUNDING LUGS.8. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, ANDGROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECTBURIAL.9. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR STRANDED, A N D B A R E W H E N E X P O S E D . 10. EQUIPMEN T G R O U N D I N G C O N D U C T O R S S H A L L B E S I Z E A C C O R D I N G T O [ N E C 690.45]AND B E A M I N I M U M O F # 1 0 A W G W H E N N O T E X P O S E D T O D A M A G E ( # 6 A W G SHALL BE USE D W H E N E X P O S E D T O D A M A G E ) . 11. GROUNDIN G A N D B O N D I N G C O N D U C T O R S , I F I N S U L A T E D , S H A L L B E C O L O R CODED GREE N ( O R M A R K E D G R E E N I F # 4 A W G O R L A R G E R ) 12. ALL COND U I T B E T W E E N T H E U T I L I T Y A C D I S C O N N E C T A N D T H E P O I N T O F CONNECTION S H A L L H A V E G R O U N D E D B U S H I N G S A T B O T H E N D S . 13. SYSTEM G E C S I Z E D A C C O R D I N G T O [ N E C 6 9 0 . 4 7 ] , [ N E C T A B L E 2 5 0 . 6 6 ] , D C SYSTEM GEC S I Z E D A C C O R D I N G T O [ N E C 2 5 0 . 1 6 6 ] , M I N I M U M # 8 A W G W H E N INSULATED, # 6 A W G W H E N E X P O S E D T O D A M A G E . 14. EXPOSED N O N - C U R R E N T C A R R Y I N G M E T A L P A R T S O F M O D U L E F R A M E S , EQUIPMENTS, A N D C O N D U C T O R E N C L O S U R E S S H A L L B E G R O U N D E D I N ACCORDANCE W I T H 2 5 0 . 1 3 4 O R 2 5 0 . 1 3 6 ( A ) R E G A R D L E S S O F V O L T A G E . WIRING & CO N D U I T N O T E S 1. ALL CONDUI T S I Z E S A N D T Y P E S , S H A L L B E L I S T E D F O R I T S P U R P O S E A N D APPROVED F O R T H E S I T E A P P L I C A T I O N S 2. ALL PV CAB L E S A N D H O M E R U N W I R E S B E # 1 0 A W G * U S E - 2 , P V W I R E , O R PROPRIETARY S O L A R C A B L I N G S P E C I F I E D B Y M F R , O R E Q U I V A L E N T ; R O U T E D T O SOURCE CIRC U I T C O M B I N E R B O X E S A S R E Q U I R E D 3. ALL CONDU C T O R S A N D O C P D S I Z E S A N D T Y P E S S P E C I F I E D A C C O R D I N G T O [ N E C 690.8]FOR M U L T I P L E C O N D U C T O R S 4. ALL PV DC C O N D U C T O R S I N C O N D U I T E X P O S E D T O S U N L I G H T S H A L L B E DERATED ACC O R D I N G T O [ N E C T A B L E 3 1 0 . 1 5 ( B ) ( 2 ) ( a ) , N E C T A B L E 3 1 0 . 1 5 ( B ) ( 3 ) ( a ) , & NEC 310.15( B ) ( 3 ) ( c ) ] 5. EXPOSED R O O F P V D C C O N D U C T O R S S H A L L B E U S E - 2 , 9 0 ° C R A T E D , W E T A N D U V RESISTANT, A N D U L L I S T E D R A T E D F O R 6 0 0 V , U V R A T E D S P I R A L W R A P S H A L L B E U S E D T O P R O T E C T W I R E F R O M S H A R P E D G E S 6 . P H A S E A N D N E U T R A L C O N D U C T O R S S H A L L B E D U A L R A T E D T H H N / T H W N - 2 I N S U L A T E D , 9 0 ° C R A T E D , W E T A N D U V R E S I S T A N T , R A T E D F O R 6 0 0 V 7 . 4 - W I R E D E L T A C O N N E C T E D S Y S T E M S H A V E T H E P H A S E W I T H T H E H I G H E R V O L T A G E T O G R O U N D M A R K E D O R A N G E O R I D E N T I F I E D B Y O T H E R E F F E C T I V E M E A N S . 8 . A L L S O U R C E C I R C U I T S S H A L L H A V E I N D I V I D U A L S O U R C E C I R C U I T P R O T E C T I O N 9 . V O L T A G E D R O P L I M I T E D T O 2 % F O R D C C I R C U I T S A N D 3 % F O R A C C I R C U I T S 1 0 . N E G A T I V E G R O U N D E D S Y S T E M S D C C O N D U C T O R S S H A L L B E C O L O R C O D E D A S F O L L O W S : D C P O S I T I V E - R E D ( O R M A R K E D R E D ) , D C N E G A T I V E - G R E Y ( O R M A R K E D G R E Y ) 1 1 . P O S I T I V E G R O U N D E D S Y S T E M S D C C O N D U C T O R S C O L O R C O D E D : D C P O S I T I V E - G R E Y ( O R M A R K E D G R E Y ) , D C N E G A T I V E - B L A C K ( O R M A R K E D B L A C K ) 1 2 . A C C O N D U C T O R S > 4 A W G C O L O R C O D E D O R M A R K E D : P H A S E A O R L 1 - B L A C K , P H A S E B O R L 2 - R E D , P H A S E C O R L 3 - B L U E , N E U T R A L - W H I T E / G R A Y * U S E - 2 I S N O T I N D O O R R A T E D B U T P V C A B L E I S R A T E D T H W N / T H W N - 2 A N D M A Y B E U S E D I N S I D E * * U S E - 2 I S A V A I L A B L E A S U V W H I T E 1 3 . I F C O N D U I T D E T E R M I N E D T O B E R A N T H R O U G H A T T I C I N F I E L D T H E N C O N D U I T W I L L B E E I T H E R E M T , F M C , O R M C C A B L E I F D C C U R R E N T C O M P L Y I N G W I T H N E C 6 9 0 . 3 1 , N E C 2 5 0 . 1 1 8 ( 1 0 ) . D I S C O N N E C T I N G M E A N S S H A L L C O M P L Y W I T H 6 9 0 . 1 3 A N D 6 9 0 . 1 5 1 4 . C O N D U I T R A N T H R O U G H A T T I C W I L L B E A T L E A S T 1 8 " B E L O W R O O F S U R F A C E C O M P L Y I N G W I T H N E C 2 3 0 . 6 ( 4 ) A N D S E C U R E D N O G R E A T E R T H A N 6 ' A P A R T P E R N E C 3 3 0 . 3 0 ( B ) . 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 D A T E D R A W I N G B Y P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N P V 6 E L E C . C A L C S . C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7 0 SITE INFORMATION: DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC LABEL 1AT EACH DIRECT CURRENT JUNCTION BOX, COMBINERBOX, DISCONNECT, AND DEVICE WHERE ENERGIZEDUNGROUNDED CONDUCTORS MAY BE EXPOSED DURINGSERVICE.[NEC. 690.35(F)]LABEL 2FOR PV DISCONNECTING MEANS WHERE ALLTERMINALS OF THE DISCONNECTING MEANS MAY BEENERGIZED IN THE OPEN POSITION.[NEC 690.17(E), NEC 705.22]LABEL 3AT EACH DC DISCONNECTING MEANS, INCLUDING THEDC DISCONNECT AT THE INVERTER.[NEC 690.53, NEC 690.13(B)]LABEL 4AT POINT OF INTERCONNECTION, MARKED AT ACDISCONNECTING MEANS.[NEC 690.54, NEC 690.13 (B)]LABEL 5AT POINT OF INTERCONNECTION FOR EQUIPMENTCONTAINING OVERCURRENT DEVICES IN CIRCUTSSUPPLYING POWER TO A BUSBAR OR CONDUCTORSUPPLIED FORM MULTIPLE SOURCES, EACH SERVICEEQUIPMENT AND ALL ELECTRIC POWER PRODUCTIONSOURCE LOCATIONS.[NEC 705.10. NEC 705.12(D)(3)] L A B E L 6 A T D I R E C T - C U R R E N T E X P O S E D R A C E W A Y S , C A B L E T R A Y S , C O V E R S A N D E N C L O S U R E S O F J U N C T I O N B O X E S , A N D O T H E R W I R I N G M E T H O D S ; S P A C E D A T M A X I M U M 1 0 F T S E C T I O N O R W H E R E S E P A R A T E D B Y E N C L O S U R E S , W A L L S , P A R T I T I O N S , C E I L I N G S , O R F L O O R S . [ N E C 6 9 0 . 3 1 ( G ) ( 3 & 4 ) ] L A B E L 7 P L A C E D A D J A C E N T T O T H E B A C K - F E D B R E A K E R F R O M T H E I N V E R T E R I F T I E I N C O N S I S T S O F L O A D S I D E C O N N E C T I O N T O B U S B A R . [ N E C 7 0 5 . 1 2 ( D ) ( 2 ) ( 3 ) ( b ) ] LABELING NOTES:1.LABELING REQUIREMENTS BASED ON THE 2014 NATIONAL ELECTRIC CODE, OSHA STANDARD19010.145, ANSI Z535.2.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.3.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC110.21]4.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE,AND PERMANENTLY AFFIXED [IFC 605.11.1.1] L A B E L 8 S I G N L O C A T E D A T U T I L I T Y S E R V I C E E Q U I P M E N T . [ N E C 6 9 0 . 5 6 ( C ) ] * E L E C T R I C A L D I A G R A M S H O W N A B O V E I S F O R L A B E L I N G P U R P O S E S O N L Y . N O T A N A C T U A L R E P R E S E N A T I O N O F E Q U I P M E N T A N D C O N N E C T I O N S T O B E I N S T A L L E D . L A B E L L O C A T I O N S P R E S E N T E D M A Y V E R Y D E P E N D I N G O N T Y P E O F I N T E R C O N N E C T I O N M E T H O D A N D L O C A T I O N P R E S E N T E D O N P V 5 O F 3 L I N E D I A G R A M . P V 5 L I N E D I A G R A M T O R E F L E C T A C T U A L R E P R E S E N T A T I O N O F P R O P O S E D S C O P E O F W O R K . J U N C T I O N B O X O R C O M B I N E R B O X M A I N S E R V I C E P A N E L A C D I S C O N N E C T E X I S T I N G S U B P A N E L ( I F W H E R E P O I N T O F I N T E R C O N N E C T I O N I S M A D E ) P V C O M B I N E R S U B P A N E L - I F U S E D T O C O M B I N E P V O U T P U T C I R C U I T S A C D C I N V E R T E R ( S ) I N T E G R A T E D D C D I S C O N N E C T 2 3 4 4 5 5 1 8 4 1 7 ( O N L Y I F P V I N T E R C O N N E C T I O N C O N S I S T S O F L O A D S I D E B R E A K E R ) 6 9 2 2 2 2 5 7 ( O N L Y I F P V I N T E R C O N N E C T I O N C O N S I S T S O F L O A D S I D E B R E A K E R ) 5 6 4 L A B E L I N G D I A G R A M : L A B E L 9 ( O N L Y I F 3 O R M O R E S U P P L Y S O U R C E S T O A B U S B A R ) S I G N L O C A T E D A T L O A D C E N T E R I F C O N T A I N S 3 O R M O R E P O W E R S O U R C E S . [ N E C 7 0 5 . 1 2 ( D ) ( 2 ) ( 3 ) ( C ) ] D R A W I N G B Y D A T E P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . P V 8 L A B E L S C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7 0 SITE INFORMATION: DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 D C D C D C D C D C D C D C D C DCD C DCDCDCDCDCDC D C D C D C D C D C D C DCDCD C D C DCDCDCDCDCDC J B J B FRONT OF HOME M P 1 A Z I M U T H : 1 8 1 ° P I T C H : 2 8 ° M P 2 A Z I M U T H : 9 1 ° P I T C H : 2 8 ° D A T E SITE INFORMATION: D R A W I N G B Y P R O J E C T N U M B E R S H E E T N A M E P A G E N U M B E R R E V I S I O N 1 2 2 0 S . 6 3 0 E S T E . 4 3 0 A M E R I C A N F O R K , U T 8 4 0 0 3 8 0 0 - 3 7 7 - 4 4 8 0 W W W . B L U E R A V E N S O L A R . C O M C O N F I D E N T I A L - T H E I N F O R M A T I O N H E R E I N C O N T A I N E D S H A L L N O T B E U S E D F O R T H E B E N E F I T O F A N Y O N E E X C E P T B L U E R A V E N S O L A R N O R S H A L L I T B E D I S C L O S E D I N W H O L E O R I N P A R T T O O T H E R S O U T S I D E R E C I P I E N T S O R G A N I Z A T I O N , E X C E P T I N C O N N E C T I O N W I T H T H E S A L E A N D U S E O F T H E R E S P E C T I V E E Q U I P M E N T , W I T H O U T T H E W R I T T E N P E R M I S S I O N O F B L U E R A V E N S O L A R L L C . P V 9 S E S e r i a l L a y o u t 0 DC SYSTEM SIZE: Lary Duque 995 Hillview Dr 4.64 Rexburg, ID 83440 kW DC PROJECT MANAGER: SCOTT GURNEY 385-498-4401 CONTRACTOR: BLUE RAVEN SOLAR 800.377.4480 C a r s o n G r o v e r 3 7 1 3 5 4 1 0 J u l y 2 7 , 2 0 1 7