HomeMy WebLinkAboutPLANS - 17-00426 - 525 S Center St - BYUI Campus - Steam & Condensate ReplacementF 1 1 2 1 3 I C W I SITE PLAN - ELECTRICAL NORTH SCALE: 1" = 60'- 0" 0" 60' 120' M KEY NOTES 0 COORDINATE WITH OWNER INSTALLED 2" CONDUIT IN COMMON TRENCH. O2 CAREFULLY HAND EXCAVATE ALONG WALL OF VAULT OR BUILDING. CORE DRILL FOR CONDUIT PENETRATIONS. SEAL WITH SILICONE AROUND CONDUITS BOTH FROM OUTSIDE AND INSIDE. TYPICAL FOR ALL VAULT PENETRATIONS. OPROVIDE AND INSTALL A 120V. 20A CIRCUIT FROM NEAREST ELECTRICAL VAULT TO THIS STEAM VAULT. INSTALL A GFI RECEPTACLE, SWITCH AND (2) LITHONIA DMW2-L24-4000 CM-AFL-WD-MVOLT-40K FIXTURES. LOCATE SWITCH ADJACENT TO VAULT ENTRY. FIELD LOCATE LIGHTS AND DEVICES PER OWNER IN FIELD. E.C. SHALL PROVIDE AND INSTALL CONDUIT, VAULT PENETRATIONS, TRENCHING, BACKFILL, ETC. AS REQUIRED TO ACCOMPLISH THIS WORK. (ALT #1) O INSTALL NEW DUCT BANK ADJACENT TO EXISTING. TAKE GREAT CARE TO MAINTAIN AND PROTECT EXISTING DUCT BANK. ANY DAMAGE TO EXISTING SERVICE SHALL BE REPAIRED AND REPLACED AT CONTRACTORS EXPENSE. ANY DISRUPTION TO EXISTING SERVICES SHALL BE WORKED CONTINUOUSLY UNTIL SERVICES ARE RESTORED. COORDINATE INSTALLATION WITH ALL EXISTING UTILITIES. OCAREFULLY REMOVE EXISTING POLE LIGHT AND PROTECT DURING CONSTRUCTION. CLEAN, REINSTALL AND RECONNECT AFTER STEAM LINE IS INSTALLED. INSTALL NEW CONDUCTORS AS REQUIRED. OREMOVE EXISTING FOUNDATION AND POLE LIGHT IN CONFLICT WITH NEW STEAM LINE. REINSTALL ON NEW FOUNDATION AS PART OF THIS PROJECT. INSTALL NEW CONDUCTORS TO ADJACENT POLES AND RECONNECT. OCORE DRILL AND INSTALL (2) 3" SLEEVES THROUGH BOTTOM OF IT PULL BOX INTO VAULT BELOW. (ALT #5) O PROVIDE AND INSTALL 343/0 + GROUND FROM NEW 200A 3P BREAKER THROUGH EXISTING CONDUIT TO EXISTING VAULT WEST OF THE M.C. (ALT #5) O PROVIDE AND INSTALL A NEW 200A 3P BREAKER IN EXISTING PANEL-"EHDP". (ALT #5) 10 REMOVE EXISTING GENERATOR AND ALL ASSOCIATED EQUIPMENT AND TURN OVER TO OWNER. (ALT #5) 0 2"C., 343/0 + GROUND TO NEW TRANSFORMER. PENETRATE BUILDING AND ROUTE FEEDER THROUGH BUILDING TO ELECTRICAL ROOM. (ALT #5)(@ NEW 200A 3P BREAKER IN ENCLOSURE. LABEL "480V. EM. POWER FROM SMITH GENERATOR". NEW EM FEEDER TO SMITH BUILDING 5 (ALT #5)(D NEW 150 KVA TRANSFORMER. 480 -120/208V 3PH 4W. (ALT #5) GPROVIDE AND INSTALL A NEW 400A MB I -LINE WITH (2) 200A 3P BREAKERS. LABEL PANEL-"EML" (ALT #5)15 PROVIDE 4410 WITH 600V INSULATION FROM EACH EXISTING TRANSFER SWITCHES IN FEEDER CONDUIT FOR GENERATOR CONTROL. (ALT #5) 16 PROVIDE AND INSTALL 21/2"C., 443/0 + GROUND FROM EACH NEW 200A BREAKER IN EML TO EACH EXISTING TRANSFER SWITCH. (ALT #5) 17 INTERCEPT EXISTING CONDUIT ABOVE DATA ROOM CEILING AND EXTEND 2" CONDUIT TO EXISTING PANEL. (ALT #5) 18 CORE DRILL PENETRATIONS AND SEAL WALL AROUND CONDUIT FOR NEW FEEDER (ALT #5) 19 REMOVE EXISTING CONDUITS AND SEAL WALL. (ALT #5)20 DISCONNECT AND REMOVE EXISTING J -BOX ABOVE TRANSFER SWITCHES. REMOVE EXISTING GENERATOR FEEDER TO TRANSFER SWITCHES. (ALT #5) 21 REMOVE EXISTING TRANSFORMER, LIGHT FIXTURE, RECEPTACLE, LOAD CENTER AND ALL ASSOCIATED CONDUIT FROM EXISTING VAULT. (ALT #5) @ PROVIDE AND INSTALL A NEW 60A 3P BREAKER IN EXISTING PANEL201-32" FOR NEW VAULT POWER. INSTALL A 1"C., 446 + GROUND THROUGH EXISTING ELECTRICAL ROOM IN TESTING CENTER TO NEW LOAD CENTER IN EXISTING VAULT. UTILIZE EXISTING 4" CONDUIT, INSTALL VAULT POWER IN 1" NONMETALIC FLEX THRU EXISTING 4" CONDUIT ALONG WITH NEW 200A FEEDER. (ALT #5) 23 PROVIDE AND INSTALL ANEW 12 SPACE NEMA 3R LOAD CENTER WITH DOUBLE LUGS AND (4) 20A 1 P BREAKERS IN EXISTING VAULT. INSTALL A NEW GFI RECEPTACLE, SWITCH AND A LITHONIA DMW2-L24-4000. UTILIZE NON METALLIC CONDUIT IN VAULT. SPECIAL NOTE: EC SHALL VISIT THE SITE, AND THOROUGHLY INVESTIGATE EXISTING CONDITIONS AS THEY RELATE TO THE SCOPE OF WORK INDICATED. INCLUDE PROVISIONS FOR THESE CONDITIONS IN BID. V ENLARGED MCKAY LIBRARY - POWER SCALE: 1/16" = 1'- 0" (ALT #5) 0" 16' 32' ORIGINAL SIGNED BY: TODD E. PAYNE DATED ORIGINAL SIGNED: 3-15-2017 ON FILE AT: PAYNE ENGINEERING INC. N P.E. JOB #1716 pNAL �NCi STE9�o'�c� 4 9 8270 \rFOF`y�� \ADD QP WO] IIIIIIIIIIIIII10 PAYNE Engineering Inc. Consulting Engineers 1823 E. Center Pocatello, Idaho 83201 tel (208) 232-4439 fax (208) 232-1435 HEATH Engineering Company Mechanical/Electrical/Plumbing Consultants 377 West 800 North Salt Lake City, Utah 84103 Tel: (801) 322-0487 Fax: (801) 322-0490 REVISIONS: 1 03.28.2017 ADDENDUM NO. 2 1888 r BYU si IDAHO +! W Q z O LU d' CD p co 0�af O > LU m L C/) a) U) ry Q U PROJECT DESIGNATION: 11340 PROPERTY PHASE: CONSTRUCTION DOCUMENTS HEATH PROJECT No: 17008 CHECKED BY: DRAWN BY: DATE: MARCH 15, 2017 SHEET DESCRIPTION PARTIAL SITE PLAN ELECTRICAL NORTH SHEET NUMBER El ■ C EX. VAULT n TI =31 RE PA AN RE EXIS,,,.. UP HILL PANEL -"H" PANEL "I" FEEDER DETAIL 5GALE: NONE POLE LIGHT 4" ALUMINUM POLE. EXISTING RELOCTED OR NEW // / / I i I I I I I / P� BASE LUGS ASOVER REQ'D. AG. EGINEERING SITE PLAN - ELECTRICAL SOUTH SCALE: 1" = 60'- 0" 0" 60' 120' E RICKS �N. UNDISTURBED OR COMPACTED EARTH Fil POLE LIGHT MOUNTING DETAIL 10 NO 5GALE KEY NOTES OPROVIDE AND INSTALL A 120V. 20A CIRCUIT FROM NEAREST ELECTRICAL VAULT TO THIS STEAM VAULT. INSTALL A GFI RECEPTACLE, SWITCH AND (2) LITHONIA DMW2-L24-4000 CM-AFL-WD-MVOLT-40K FIXTURES. LOCATE SWITCH ADJACENT TO VAULT ENTRY. FIELD LOCATE LIGHTS AND DEVICES PER OWNER IN FIELD. OEXISTING PANEL -"I" TO REMAIN. INSTALL ELBOWS AND RISERS TO EXTEND FEEDER CONDUITS UP TO PANEL. OPROVIDE AND INSTALL 20FT. OF 4" PERFORATED PIPE IN 24" DEEP TRENCH. ENCASE IN GRAVEL FOR PANEL DRAINAGE. SEE DETAIL. OEXISTING 200A DISCONNECT. REMOVE AND REPLACE WITH NEW 18x18 NEMA 3R J -BOX. O5 REMOVE EXISTING 200A FEEDER CONDUCTORS AND CONDUIT IN CONFLICT WITH NEW STEAM LINE. O6 REMOVE EXISTING GROUND BOX. O7 REMOVE EXISTING POWER LINK CONTROL CABLE IN CONFLICT WITH STEAM LINE. O8 UTILIZE EXISTING 2" CONDUIT FOR NEW FEEDER TO NEW PANEL -"I" WHENEVER POSSIBLE. O9 INTERCEPT EXISTING 1" CONDUIT AT EXISTING GROUND BOX AND EXTEND TO EXISTING PANEL "I". INSTALL (2) NEW POWER LINK CONTROL CABLES FROM BUILDING TO PANEL -"I" AND RECONNECT (1 SPARE). 10 EXISTING POLE LIGHT LOCATION TO REMAIN. E.C. SHALL CAREFULLY REMOVE POLE. PROTECT DURING CONSTRUCTION, THEN CLEAN AND REINSTALL ON NEW FOUNDATION. 11 E.C. SHALL REMOVE THIS POLE AND FOUNDATION. TURN POLE AND FIXTURE OVER TO OWNER. REPAIR AND REPLACE 1" CONDUIT BETWEEN POLES. INSTALL NEW #10 CONDUCTORS TO REMAINING POLES AND RECONNECT. 12 REMOVE EXISTING FOUNDATION AND REINSTALL NEW AS SHOWN. INSTALL NEW CONDUIT AND CONDUCTORS BETWEEN POLES. 13 INSTALL A 2" CONDUIT FROM J -BOX UP WALL, THEN LB THROUGH WALL ABOVE CLASSROOM CEILING TO EXISTING PANEL -"M" FOR NEW FEEDER TO PANEI-21". 14 CORE DRILL WALL PENETRATIONS AS REQUIRED. 15 PROVIDE AND INSTALL A NEW 200A 3P BREAKER IN EXISTING PANEL -"M". LABEL "PANEL -I" INSTALL A 2"C., 443/0 + GROUND TO EXISTING PANEL "I". aIF MOW WHERE APRON WITH REBAR LOCATED IN LAWN AREA. FINISH GRADE 60 SOD i�i ii IF II 1 03.28.2017 ADDENDUM NO. 2 LAWN r=1 I I-1 I I -III—III—I IIII if I I IIIb 11 I I r l 11 I III =_' ❑ ❑ I I—III 1-1I-1 I r I I r� 11 I I I I 11=III=1' — ANCHOR BOLTS TO SUIT ❑ ===-irr�= l t t l r �i 1•H rr–==� POLE BY E.C. Z C? I—I I I_I I:I I I a. 41 ❑ ❑ ❑ I1=1II-1 LTi—III b1 I I III—II 314" CONDUIT (PVC) 24" MIN. ❑ _1 l� �� DEPTH. REFER TO PLAN. ❑ ❑ a. ❑ POLE BASE WITH 4#5 RE -BARS ❑ 111-111-1I1-1 ° LU AND #3 TIES @ 12" O.C. 12" i=ll 111 111 -1 11.-1 11-1 11-1 11-1 ❑ I 111=111-� .I 11 3000 PSI MIN. UNDISTURBED OR COMPACTED EARTH Fil POLE LIGHT MOUNTING DETAIL 10 NO 5GALE KEY NOTES OPROVIDE AND INSTALL A 120V. 20A CIRCUIT FROM NEAREST ELECTRICAL VAULT TO THIS STEAM VAULT. INSTALL A GFI RECEPTACLE, SWITCH AND (2) LITHONIA DMW2-L24-4000 CM-AFL-WD-MVOLT-40K FIXTURES. LOCATE SWITCH ADJACENT TO VAULT ENTRY. FIELD LOCATE LIGHTS AND DEVICES PER OWNER IN FIELD. OEXISTING PANEL -"I" TO REMAIN. INSTALL ELBOWS AND RISERS TO EXTEND FEEDER CONDUITS UP TO PANEL. OPROVIDE AND INSTALL 20FT. OF 4" PERFORATED PIPE IN 24" DEEP TRENCH. ENCASE IN GRAVEL FOR PANEL DRAINAGE. SEE DETAIL. OEXISTING 200A DISCONNECT. REMOVE AND REPLACE WITH NEW 18x18 NEMA 3R J -BOX. O5 REMOVE EXISTING 200A FEEDER CONDUCTORS AND CONDUIT IN CONFLICT WITH NEW STEAM LINE. O6 REMOVE EXISTING GROUND BOX. O7 REMOVE EXISTING POWER LINK CONTROL CABLE IN CONFLICT WITH STEAM LINE. O8 UTILIZE EXISTING 2" CONDUIT FOR NEW FEEDER TO NEW PANEL -"I" WHENEVER POSSIBLE. O9 INTERCEPT EXISTING 1" CONDUIT AT EXISTING GROUND BOX AND EXTEND TO EXISTING PANEL "I". INSTALL (2) NEW POWER LINK CONTROL CABLES FROM BUILDING TO PANEL -"I" AND RECONNECT (1 SPARE). 10 EXISTING POLE LIGHT LOCATION TO REMAIN. E.C. SHALL CAREFULLY REMOVE POLE. PROTECT DURING CONSTRUCTION, THEN CLEAN AND REINSTALL ON NEW FOUNDATION. 11 E.C. SHALL REMOVE THIS POLE AND FOUNDATION. TURN POLE AND FIXTURE OVER TO OWNER. REPAIR AND REPLACE 1" CONDUIT BETWEEN POLES. INSTALL NEW #10 CONDUCTORS TO REMAINING POLES AND RECONNECT. 12 REMOVE EXISTING FOUNDATION AND REINSTALL NEW AS SHOWN. INSTALL NEW CONDUIT AND CONDUCTORS BETWEEN POLES. 13 INSTALL A 2" CONDUIT FROM J -BOX UP WALL, THEN LB THROUGH WALL ABOVE CLASSROOM CEILING TO EXISTING PANEL -"M" FOR NEW FEEDER TO PANEI-21". 14 CORE DRILL WALL PENETRATIONS AS REQUIRED. 15 PROVIDE AND INSTALL A NEW 200A 3P BREAKER IN EXISTING PANEL -"M". LABEL "PANEL -I" INSTALL A 2"C., 443/0 + GROUND TO EXISTING PANEL "I". r L L 12" PANEL "I" DRAIN DETAIL GRADE � I I -III -III -III -III -III -III , ; COMPACT FILL 4" MIN. 3" MIN. 00 (TYP) (TYP) z 4" MIN. lo d, (TYP) -----= �L----_= * LOCATE ON WEST SIDE -II OF EXISTING DUCT BANK RED CONCRETE 5"C 5"C 5"C 2O{ - d , - d' ° ;° 511C 5"CI°- #4 REBAR � CONDUIT WRAP DUCT BANK WITH REBAR (TYP FOR (TYPICAL) 36" O.C. FOR ENTIRE PORTION EACH CORNER) CROSSING AND DRIVEWAY OR STREETS. ORIGINAL SIGNED BY: TODD E. PAYNE DATED ORIGINAL SIGNED: 3-15-2017 ON FILE AT: PAYNE ENGINEERING INC. NOTES: 1. ALL ELBOWS SHALL BE RIGID STEEL LONG SWEEPING. 2. ALL RISERS SHALL BE RIGID STEEL 3. E.C. SHALL MAINTAIN THESE SPECIFIED SPACINGS FOR ALL CONCRETE ENCASED CONDUITS. 4. E.C. SHALL SWAB EACH SPARE CONDUIT IN ALL NEW DUCT BANKS, THEN INSTALL A REUSABLE FACTORY DUCT SEAL IN EACH END TO KEEP CLEAN. 5. E.C. MAY SUBMIT CONFIGURATION MODIFICATIONS FOR APPROVAL BASED UPON SITE CONDITIONS. 6. REUSABLE DUCT SEAL SHALL BE SUCH AS TYCO MP0326. SIZE TO DUCT. DUCT BANK DETAIL - A (ALT 41) %\ONAL FNc� aQ°� srE9Fo�� co 8270 o �FOF�y�� \ODD QP/ P.E. JOB #1716 PAYNE f ngineering Inc. Consulting Engineers 1823 E. Center Pocatello, Idaho 83201 tel (208) 232-4439 fax (208) 232-1435 HEATH Engineering Company Mechanical/Electrical/Plumbing Consultants 377 West 800 North Salt Lake City, Utah 84103 SOD REVISIONS: 1 03.28.2017 ADDENDUM NO. 2 LAWN ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ BYU ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ LU 12" ❑ ❑ ❑ ❑ ❑ 13❑ ❑ ❑ ❑ ❑ EARTH co >- CU ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ CHECKED BY: DRAWN BY: DATE: MARCH 15, 2017 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 3E ❑ 3C ❑ 3E ❑ 3C ❑ 3E ❑ 3E 3E ❑ ❑ 3C ❑ DE ❑ 3C ❑ 3L ❑ ❑ 00000000 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 20FT. 4" PERFORATED DRAIN PIPE WRAPPED ,... ° WITH FILTER CLOTH d d ° 12" ° q. d d q d d WASHED ° GRAVEL r L L 12" PANEL "I" DRAIN DETAIL GRADE � I I -III -III -III -III -III -III , ; COMPACT FILL 4" MIN. 3" MIN. 00 (TYP) (TYP) z 4" MIN. lo d, (TYP) -----= �L----_= * LOCATE ON WEST SIDE -II OF EXISTING DUCT BANK RED CONCRETE 5"C 5"C 5"C 2O{ - d , - d' ° ;° 511C 5"CI°- #4 REBAR � CONDUIT WRAP DUCT BANK WITH REBAR (TYP FOR (TYPICAL) 36" O.C. FOR ENTIRE PORTION EACH CORNER) CROSSING AND DRIVEWAY OR STREETS. ORIGINAL SIGNED BY: TODD E. PAYNE DATED ORIGINAL SIGNED: 3-15-2017 ON FILE AT: PAYNE ENGINEERING INC. NOTES: 1. ALL ELBOWS SHALL BE RIGID STEEL LONG SWEEPING. 2. ALL RISERS SHALL BE RIGID STEEL 3. E.C. SHALL MAINTAIN THESE SPECIFIED SPACINGS FOR ALL CONCRETE ENCASED CONDUITS. 4. E.C. SHALL SWAB EACH SPARE CONDUIT IN ALL NEW DUCT BANKS, THEN INSTALL A REUSABLE FACTORY DUCT SEAL IN EACH END TO KEEP CLEAN. 5. E.C. MAY SUBMIT CONFIGURATION MODIFICATIONS FOR APPROVAL BASED UPON SITE CONDITIONS. 6. REUSABLE DUCT SEAL SHALL BE SUCH AS TYCO MP0326. SIZE TO DUCT. DUCT BANK DETAIL - A (ALT 41) %\ONAL FNc� aQ°� srE9Fo�� co 8270 o �FOF�y�� \ODD QP/ P.E. JOB #1716 PAYNE f ngineering Inc. Consulting Engineers 1823 E. Center Pocatello, Idaho 83201 tel (208) 232-4439 fax (208) 232-1435 HEATH Engineering Company Mechanical/Electrical/Plumbing Consultants 377 West 800 North Salt Lake City, Utah 84103 Tel: (801) 322-0487 Fax: (801) 322-0490 REVISIONS: 1 03.28.2017 ADDENDUM NO. 2 i888 BYU ,. r IDAHO � . s r LU Q W � z 0 C'7 00 o0Of o cq C — ZZD Q � mw LU co >- CU cl U PROJECT DESIGNATION: 11340 PROPERTY PHASE: CONSTRUCTION DOCUMENTS HEATH PROJECT No: 17008 CHECKED BY: DRAWN BY: DATE: MARCH 15, 2017 SHEET DESCRIPTION PARTIAL SITE PLAN ELECTRICAL SOUTH SHEET NUMBER El ■