Loading...
HomeMy WebLinkAboutINSPECTION REPORT (08.28.14) - 13-00493 - 76 W 2nd S - NorthPointe Retail & ClubhouseCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-COM ELEROUGH-C Permit Number: Address: 76 West 2nd South Project: 13-00493 NorthPointe Retail & Clubhouse Inspection Date 8/28/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Unused openings have been closed. 110.12(A), 408.7 COMPLETED Wiring methods spaced from edges of framing and protection from nails and screws. (1/1/4”) 300.4(A)(B)(D)&(E) (1/1/2” roof decking) (1/16” nail plate) COMPLETED Insulating bushings/grommets where NM cable is installed through metal studs or conductors 4 AWG or larger enter enclosures. 300.4(B)(1)&(F) COMPLETED Continuity and tightness of fittings in metal raceways and enclosures. 300.10 COMPLETED Adequate length of free conductors in boxes. 300.14 COMPLETED Raceways and cables are secured to boxes. 314.17(B)(C) COMPLETED Approved for cover in noted areas In both stairways all levels.COMPLETED Inspector: Bret Stoddard