Loading...
HomeMy WebLinkAboutINSPECTION REPORT (08.18.14) - 13-00493 - 76 W 2nd S - NorthPointe Retail & ClubhouseCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-COM ELEROUGH-C Permit Number: Address: 76 West 2nd South Project: 13-00493 NorthPointe Retail & Clubhouse Inspection Date 8/18/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Wiring methods spaced from edges of framing and protection from nails and screws. (1/1/4”) 300.4(A)(B)(D)&(E) (1/1/2” roof decking) (1/16” nail plate) COMPLETED Insulating bushings/grommets where NM cable is installed through metal studs or conductors 4 AWG or larger enter enclosures. 300.4(B)(1)&(F) COMPLETED Adequate length of free conductors in boxes. 300.14 COMPLETED Boxes must be installed at junction, splice, outlet, switch, and pull points. 300.15 COMPLETED Closure of unused openings. 312.5(A)COMPLETED Approved for cover in noted areas In interior walls of level 3 and office in basement near elevator. COMPLETED Inspector: Bret Stoddard