Loading...
HomeMy WebLinkAboutINSPECTION REPORT (08.14.14) - 13 00493 - 76 W 2nd S - NorthPointe Retail & ClubhouseCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-COM ELECOMSERV Permit Number: Address: 76 West 2nd South Project: 13-00493 NorthPointe Retail & Clubhouse Inspection Date 8/14/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Each building has only one service or justified for more than one. 230.2 COMPLETED Underground fed services have proper strapping and expansion fittings. 352.30(A)(B), 352.44 COMPLETED Services are grouped together and limited to six disconnects. 230.71, 230.72 COMPLETED Unused openings have been closed. (K.O. seals, etc.) 110.12(A), 408.7 COMPLETED Securely mounted gear-panels, meter base, etc. 110.13 COMPLETED Proper labeling of panels, switchgear, and similar equipment. 110.22, 408.4 COMPLETED Grounding electrode system installed-ufer, ground rods, metal water piping, etc. 250.52(A)(4-7) COMPLETED Grounding electrode system conductors sized and protected appropriately. 250.66, 250.64(F), 250.64(A)(B) COMPLETED Grounding electrode conductor is either un-spliced or spliced using approved methods. 250.64(C)(F) COMPLETED Identify wet and damp locations for panels-NEMA 3R, etc. 408.16, 408.37, 312.12 COMPLETED Approved to be energized for permanent power (will send permit to utility). Only for commons portion of main service-1000A breaker portion. COMPLETED Inspector: Bret Stoddard