HomeMy WebLinkAboutINSPECTION REPORT (08.14.14) - 13 00493 - 76 W 2nd S - NorthPointe Retail & ClubhouseCommunity Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-COM ELECOMSERV
Permit Number:
Address: 76 West 2nd South
Project:
13-00493 NorthPointe Retail & Clubhouse
Inspection Date
8/14/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Each building has only one service or
justified for more than one. 230.2
COMPLETED
Underground fed services have proper
strapping and expansion fittings.
352.30(A)(B), 352.44
COMPLETED
Services are grouped together and limited
to six disconnects. 230.71, 230.72
COMPLETED
Unused openings have been closed. (K.O.
seals, etc.) 110.12(A), 408.7
COMPLETED
Securely mounted gear-panels, meter
base, etc. 110.13
COMPLETED
Proper labeling of panels, switchgear, and
similar equipment. 110.22, 408.4
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc.
250.52(A)(4-7)
COMPLETED
Grounding electrode system conductors
sized and protected appropriately. 250.66,
250.64(F), 250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved
methods. 250.64(C)(F)
COMPLETED
Identify wet and damp locations for
panels-NEMA 3R, etc. 408.16, 408.37,
312.12
COMPLETED
Approved to be energized for permanent
power (will send permit to utility).
Only for commons portion of main
service-1000A breaker portion.
COMPLETED
Inspector: Bret Stoddard