Inspection Type Building Type Inspection
ELECTRICAL BLD-COM ELE-FINAL
Permit Number:
Address: 673 North 2nd East
Project:
14-00050 Idaho Central Credit Union
Inspection Date
8/7/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Receptacles have correct polarity,
grounding, no open neutrals, etc.
200.10(B)
COMPLETED
Identify installations and equipment
requiring special approval or investigation.
90.4, 90.7, 110.2, 110.3
COMPLETED
Verify that interrupting ratings are
adequate for the conditions of the
installation. 110.9
COMPLETED
Verify that unused openings have been
effectively closed.110.12(A), 408.7
COMPLETED
Verify adequate working clearances,
dedicated spaces, and headroom around
equipment. 110.26(A), (E), and (F)
COMPLETED
Verify that working spaces have adequate
illumination.110.26(D)
COMPLETED
Check for identification of disconnecting
means and circuit directories for
panelboards, switchboards, and similar
equipment.110.22, 408.4
COMPLETED
Check for insulating bushings or grommets
where NM cable is installed through metal
studs or conductors 4 AWG or larger enter
enclosures. 300.4(B)(1) and (F)
COMPLETED
Check cover, fill, protection, and
allowances for ground
movement on underground conductors
and raceways.300.5 and Table 300.5
COMPLETED
Check for continuity and completeness in
metal raceways and enclosures. 300.10
COMPLETED
Page 1 of 2
Verify that wiring methods are securely
fastened in place, supported
independently of suspended ceilings, and
not used as supports.300.11 and
applicable Chapter 3 article(s)
APPROVED
Verify that raceway systems are complete
prior to installation of conductors.
300.18(A)
COMPLETED
Verify that raceways and cables are
secured to boxes.314.17(B) and (C)
COMPLETED
Check for closure of unused
openings.314.17(A)
COMPLETED
Check for excessive gaps between edges
of boxes and
plaster, plasterboard, or drywall
surfaces.314.21
COMPLETED
Check for covers on boxes.314.25,
314.28(C)
COMPLETED
Verify that switches are located not over 6
ft 7 in. (2 m) high and that they can be
operated from readily accessible places
unless otherwise permitted.404.8(A),
240.24(A)
COMPLETED
Check receptacles for proper polarity and
for grounding
and bonding connections. 406.3, 250.146,
200.11
COMPLETED
Verify that receptacle ratings and
branch-circuit ratings
are compatible. 210.21, 210.24
COMPLETED
Approved for a final and Temporary C.O.
in noted areas.
For preliminary final electrical
inspection-need to change breaker for
A/C unit to listed size and bond to water
line in main panel room.
COMPLETED
Inspector: Bret Stoddard