HomeMy WebLinkAboutINSPECTION TICKET - 17-00316 - 1069 Summers Dr - Temporary ServiceInspection Ticket Temporary Electrical Service on 06/08/2017: PASS Permit Number: 17-00316Permit Details Electrical Only Commercial Permit Issued Date: 06/08/2017 Final Inspections Required 1069 Summers Dr 1069 Summers Dr - Temporary Service Inspection Details bret.stoddard@rexburg.org Inspected By: Bret Stoddard Temporary Electrical Service on 06/08/2017: PASS D ESCRIPTIO N CO MMEN TS STATUS Unused openings have been effectively closed (K.O. seals, etc.) 110.12(A), 408.7 Need to install K.O. seals in bottom of panel.COMPLETED Securely mounted gear-panels, meter base, etc. 110.13 COMPLETED Proper clearances about electrical equipment indoors and outdoors. 110.26 (A), (E),(E)(2) and (F) COMPLETED •Grounding electrode system installed-ufer, ground rods, etc. 250.52(A)(4-7) COMPLETED Grounding electrode system conductors sized and protected appropriately. 250.66, 250.64(F), 250.64(A)(B) COMPLETED Grounding electrode conductor is either un-spliced or spliced using approved methods. 250.64(C)(F) COMPLETED Temporary 125V & 250V 15A & 20A receptacles must have GFCI protection. 590.4(D) Four GFCI receptacles installed for temporary power. COMPLETED Temporary receptacles in wet/damp locations must have in-use extra duty covers. 590.4(D)(2), 406.9(A)(B) COMPLETED Any associated wiring with service meets article 300 wiring methods. COMPLETED Identify wet and damp locations for panels-NEMA 3R, etc. 408.16, 408.37, 312.12 COMPLETED Panel or switchgear service rated. 408.3(C)COMPLETED Approved to be energized for temporary power (will send permit with temporary note to utility) To be energized for temporary power after K.O. seals are installed. COMPLETED