HomeMy WebLinkAboutINSPECTION REPORT - 8-14-14 - 75 N 2nd E - Maverik Site RemodelCommunity Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-COMR ELEC-UNGD
Permit Number:
Address: 75 North 2nd East
Project:
14-00217 Maverik Site Remodel
Inspection Date
8/14/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Labeling and listing-installation of
materials and equipment, direct burial, etc.
90.7, 110.3(B)
COMPLETED
Underground wiring method or circuit
wiring cover depth approved. 300.5
COMPLETED
Stub up approved for protection against
physical damage sch. 80 PVC, RMC, IMC,
RTRC-XW or equivalent 300.5(D)(4)
COMPLETED
Ferrous metal equipment must have
corrosion protection, elbows wrapped, etc.
300.6(A)
COMPLETED
Backfill material must not contain large
rocks, cinders, paving materials, etc.
300.5(F)
COMPLETED
Approved for backfill For conduits to dispensers-both low and
high voltage(20).
COMPLETED
Inspector: Bret Stoddard