HomeMy WebLinkAboutINSPECTION REPORT - 14-00307 - 26 N Center St - Madison Fire Department Apts - RemodelCommunity Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-COMR ELEROUGH-C
Permit Number:
Address: 26 North Center Street
Project:
14-00307 Madison Fire Department Apts -
Remodel
Inspection Date
8/26/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Unused openings have been closed.
110.12(A), 408.7
COMPLETED
Wiring methods spaced from edges of
framing and protection from nails and
screws. (1/1/4”) 300.4(A)(B)(D)&(E) (1/1/2”
roof decking) (1/16” nail plate)
COMPLETED
Continuity and tightness of fittings in metal
raceways and enclosures. 300.10
COMPLETED
Raceways and cables are secured to
boxes. 314.17(B)(C)
COMPLETED
All boxes will be accessible. 314.29 COMPLETED
Closure of unused openings. 312.5(A)COMPLETED
Verify that wiring methods used are
appropriate for the conditions and
occupancy. Chapter 3
COMPLETED
Panelboards-proper overcurrent protection
and wire size. 408.30, 310.15(B)(16),
210.3, 220
COMPLETED
Positioning of boxes that are intended to
be flush with combustible and
noncombustible finished surfaces.
COMPLETED
Approved for cover in noted areas In remodeled areas in living area of
building-seperate grounding conductors in
sub fed panel.
COMPLETED
Inspector: Bret Stoddard