Loading...
HomeMy WebLinkAboutINSPECTION REPORT - 14-00307 - 26 N Center St - Madison Fire Department Apts - RemodelCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-COMR ELEROUGH-C Permit Number: Address: 26 North Center Street Project: 14-00307 Madison Fire Department Apts - Remodel Inspection Date 8/26/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Unused openings have been closed. 110.12(A), 408.7 COMPLETED Wiring methods spaced from edges of framing and protection from nails and screws. (1/1/4”) 300.4(A)(B)(D)&(E) (1/1/2” roof decking) (1/16” nail plate) COMPLETED Continuity and tightness of fittings in metal raceways and enclosures. 300.10 COMPLETED Raceways and cables are secured to boxes. 314.17(B)(C) COMPLETED All boxes will be accessible. 314.29 COMPLETED Closure of unused openings. 312.5(A)COMPLETED Verify that wiring methods used are appropriate for the conditions and occupancy. Chapter 3 COMPLETED Panelboards-proper overcurrent protection and wire size. 408.30, 310.15(B)(16), 210.3, 220 COMPLETED Positioning of boxes that are intended to be flush with combustible and noncombustible finished surfaces. COMPLETED Approved for cover in noted areas In remodeled areas in living area of building-seperate grounding conductors in sub fed panel. COMPLETED Inspector: Bret Stoddard