HomeMy WebLinkAboutFS CALCS 2 - 16-00683-684 - Sugar Mill ApartmentsAl ± ) ) \ ME |" �| y : !§IL # § £ •# £c ® ® , 7 ul IL k0 \ \ 14P 6 !L0. IL 0 0 \� ME HYDRAULIC CALCULATIONS for Job Information Project Name : SUGAR MILL APARTMENTS Contract No.: 17-207 City: REXBURG, IDAHO Project Location: 267 W 4TH S Date: 3/20/2017 Contractor Information Name of Contractor: PHOENIX FIRE Address: 4130 AIRPORT RD City: NAMPA, IDAHO 83687 Phone Number: 208.468.9115 E-mail: BROOK@PHOENIXFP.COM Name of Designer: BROOK STEWART Authority Having Jurisdiction: IDAHO STATE FIRE MARSHAL Design Remote Area Name 4 Remote Area Location STANDPIPE Occupancy Classification Density (gpm/fl') 1 Area of Application (ft-) 500 Coverage per Sprinkler (ft') 250 Number of Calculated Sprinklers 2 In -Rack Demand (gpm) 0 Special Heads Hose Streams (gpm) 0 Total Water Required (incl. Hose Streams) (gpm) 503.2 Required Pressure at Source (psi) 133.7 Type of System Dry Volume - Downstream DPV (gal) 61.6 gal Water Supply Information Date 03/28/2017 Location FDC Source PMP Notes File: C:\Users\Ownerappdata\local\temp\17-207FP_1_1_9249.sv$ Date 4/4/2017 Copyright 0 2002-2012 Tyco Fire Protection Products Page 2 �r 00 on". micyn:ak,iitwnma:4LL1gz169 Calculation Info Calculation Mode Hydraulic Model Fluid Name Fluid Weight, (Ib/ft3) Fluid Dynamic Viscosity, (Ib•s/R2) Water Supply Parameters Supply 1 : PMP Supply Analysis Hydraulic Analysis for: 4 Demand Hazen -Williams Water @ 60F (15.6C) N/A for Hazen -Williams calculation. N/A for Hazen -Williams calculation. Flow m Pressure sI 0 180 1500 150 2250 97.5 Hoses Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm) Sprinklers Static Pressure Residual Flow Available Total Demand Required Pressure Node at Source (psi) Pressure (gpm) Pressure Pressure (gpm) (psi) (psi) PMP 180 150 1500 176 503.2 133.7 Hoses Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm) Sprinklers Ovehead Sprinkler Flow (gpm) 503.2 InRack Sprinkler Flow (gpm) 0 Other (custom defined) Sprinkler Flow (gpm) 0 Total Sprinkler Flow (gpm) 503.2 Other Required Margin of Safety (psi) 0 PMP - Pressure (psi) 133.7 PMP -Flow (gpm) 503.2 Demand w/o System Pump(s) N/A File: C:\Users\Owner\appdata\local\temp\17-207FP_1_1_9249.sv$ Date 4/4/2017 Copyright 0 2002-2012 Tyco Fire Protection Products Page 4 0 n M N L °a [.r-- W c04 CD N O m co It �" V C U. w N U Im Job: SUGAR MILL APARTMENTS Hydraulic Analysis for: 4 Graph Labels Label Description Flow (gpm) Values Pressure (psi) Si Supply paint #1 - Static 0 180 S2 Supply point #2 1500 150 S3 Supply point #3 2250 97.5 D1 Elevation Pressure 0 13.9 D2 System Demand 503.2 133.7 Curve Intersections & Safety Margins Curve Name Intersection Safety Margin Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm) Supply 174.7 589.9 42.3 503.2 Open Heads File: C:\Users\Owner\appdataVocahtemp\17-207FP_1_1_9249.sv$ Date 4/4/2017 Copyright ® 2002-2012 Tyco Fire Protection Products Page 6 Required Calculated Head Ref. Head Type Coverage K -Factor Density Flow Pressure Density Flow Pressure (ft') (gpm/PSI'/2) (gPm/ft') (gpm) (psi) (gpm/ft') (gPm) (psi) S401 Overhead Sprinkler 250 25 1 250 100 1 250 100 S402 Overhead 250 25 1 250 100 1.013 253.2 102.6 Sprinkler File: C:\Users\Owner\appdataVocahtemp\17-207FP_1_1_9249.sv$ Date 4/4/2017 Copyright ® 2002-2012 Tyco Fire Protection Products Page 6 Job: SUGAR MILL APARTMENTS Node Data Hydraulic Calculations / Fluid Delivery Time Analysis Node# Type K -Fact. Discharge Coverage Tot. Pres. Req. Pres. Elev Hgroup Open/Closed Overdischarge Density Elev. Pres. Req. Discharge gpm/psiy2 glom ft2 psi psi ft gpm gpm/ft2 psi gpm 5401 Overhead Sprinkler 25 250 250 100 100 34 HEAD Open 0 1 -13.9 250 5402 Overhead Sprinkler 25 253.2 250 102.6 100 34 HEAD Open 3.2 1.013 -13.9 250 001 Node 102.7 34 NODE -13.9 015-0 Node 128.8 -3.01 NODE 2.2 015-I Node 130.2 -4.16 NODE 2.7 PMP Supply -5032 133.7 2 SUPPLY . 0 File: C:\Users\Owner\appdata\local\temp\17-207FP_1_1_9249.sv$ Date 4/4/2017 Copyright 02002-2012 Tyco Fire Protection Products Page 7 Job: SUGAR MILL APARTMENTS PIPE INFORMATION Hydraulic Calculations Node 1 Elev 1 K -Factor 1 Flow, added (q) Nominal ID Fittings L C Factor total (Pt) Node 2 Elev 2 K -Factor 2 Total flow (Q) Actual ID quantity x (name) = length F I Pf per R elev (Pe) NOTES T frict (Pf) 001 (ft) (gpm/psiy') (gpm) (In) (ft) (ft) (psi) (psi) Path No: 1 S401 34 25 250 2.5 1x(us.Tee-Br)=11.75 0.33 100 100 001 34 250 2.635 11.75 0.2203 0 12.08 2.7 001 34 253.2 4 lx(coupling)=0.94 82.59 100 102.7 015-0 -3.01 503.2 4.26 5x(us.90)=46.94 47.88 0.0775 16 130.47 10.1 015-0 -3.01 0 4 1.15 0 128.8 DPV-1 015-I -4.16 503.2 0 0 0.7639 0.5 *** 1.15 0.9 -4.16 0 4 5x(us.90)=65.84 19.82 120130.2 rPmp 2 503.2 4.26 lx(us.Tee-Br)=26.33 92.170.0553 -2.7 111.9 133.7 Path No: 2 5402 34 25 253.2 2.5 0.33 100 102.6 001 34 253.2 2.635 1 0 0.2255 0 0.33 0.1 001 102.7 * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. * Maximum Velocity of 14.9 ft/s occurs in the following pipe(s): (001-S402) *** Device pressure loss (gain in the case of pumps) is calculated from the device's curve. If the device curve is printed with this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction loss per unit of length is calculated based upon the length and the curve -based loss/gain value. Internal ID and C Factor values are Irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based solely on the curve data. File: C:\Users\Owner\appdataVocahtemp\17-207FP_1_1_9249.sv$ Date 4/4/2017 Copyright 02002-2012 Tyco Fire Protection Products Page 8 Job: SUGAR MILL APARTMENTS 200- 190 - ISO 170 160 - ISO! 140: 1 CL W 120� 1w Im It go - so 707 60= 50= 40- 30- 20 10 0:2010 0 a 7 6 2. L 0, Device Graphs Pressure vs. Flow Function Design Area: 4; Supply Ref.: PMP; Supply Name:PMP T- -- - -- ----- ----- . .. .... ------------ Flow, gpni Pressure Loss Function Design Area: 4; DPV Ref.: 1141 (DPV-1, Size = 4); Inlet Node: 015-1; Outlet Node: 015-0 Flow, gpm File: C:\Users\Owner\appdataVocal\temp\17-207FP_1_7 —9249.sv$ Date 4/4/2017 Copyright 02002-2012 Tyco Fire Protection Products Page 9 ------------ I .9 @503.2 0 " 'Si _ gpm .......... S Flow, gpm File: C:\Users\Owner\appdataVocal\temp\17-207FP_1_7 —9249.sv$ Date 4/4/2017 Copyright 02002-2012 Tyco Fire Protection Products Page 9