Inspection Type Building Type Inspection
ELECTRICAL BLD-ELEC ELECOMSERV
Permit Number:
Address: Corner of 2nd South and
1st West
Project:
14-00332 City of Rexburg - Electrical
Inspection Date
10/1/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Underground fed services have proper
strapping and expansion fittings.
352.30(A)(B), 352.44
COMPLETED
Services are grouped together and limited
to six disconnects. 230.71, 230.72
COMPLETED
Unused openings have been closed. (K.O.
seals, etc.) 110.12(A), 408.7
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc.
250.52(A)(4-7)
COMPLETED
Grounding electrode system conductors
sized and protected appropriately. 250.66,
250.64(F), 250.64(A)(B)
COMPLETED
Any associated wiring with service meets
article 300 wiring methods.
COMPLETED
Panel or switchgear service rated.
408.3(C)
COMPLETED
Approved to be energized for permanent
power (will send permit to utility).
This inspection is for the power pedestal
for the traffic signal for TEMPORARY
only.
COMPLETED
Inspector: Bret Stoddard