HomeMy WebLinkAboutINSPECTION REPORT 1 - 14 00332 - Corner of 2nd S and 1st W - City of Rexburg - ElectricalCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-ELEC ELECOMSERV Permit Number: Address: Corner of 2nd South and 1st West Project: 14-00332 City of Rexburg - Electrical Inspection Date 10/1/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Underground fed services have proper strapping and expansion fittings. 352.30(A)(B), 352.44 COMPLETED Services are grouped together and limited to six disconnects. 230.71, 230.72 COMPLETED Unused openings have been closed. (K.O. seals, etc.) 110.12(A), 408.7 COMPLETED Grounding electrode system installed-ufer, ground rods, metal water piping, etc. 250.52(A)(4-7) COMPLETED Grounding electrode system conductors sized and protected appropriately. 250.66, 250.64(F), 250.64(A)(B) COMPLETED Any associated wiring with service meets article 300 wiring methods. COMPLETED Panel or switchgear service rated. 408.3(C) COMPLETED Approved to be energized for permanent power (will send permit to utility). This inspection is for the power pedestal for the traffic signal for TEMPORARY only. COMPLETED Inspector: Bret Stoddard