3.6 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs if you are using SK
addressable devices (Table 3-2) or SD addressable devices (Table 3-3).
3.6.1 - Current Draw Worksheet Requirements
The following steps must be taken when determining 5808 current draw and standby battery requirements.
1. Use the Current Draw Worksheet to determine current draw and standby battery requirements. Use Table 3-
2 if installing SK SLC Devices and Table 3-3 if installing SD SLC Devices to determine current draw. For
the 5808, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders.
Fill in the number of addressable devices that will be used in the, system and compute: the current draw
requirements for alarm and standby. Record this information in the Current DrawWorksheet on Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliance circuits and auxiliary devices not mentioned in the manual; refer to the device
manual for the current ratings,
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
6.0 A. This is the maximum alarm current for the 5808 control panel.
If the current is above 6.0 A you will need to use a'notification power expander(s) such as the Silent Knight
5496 intelligent power module, to distribute the power loads so that the 5808 or the power expanders do not
exceed their power rating. Refer to the current draw worksheets provided with the 5496 manual so you do
not exceed their power requirements,
6. Complete the remaining instructions in the appropriate Current Draw Worksheet for determining battery size
requirements.
3.6.1.1 Current Draw Worksheet for SK SLC Devices
Use Table 3-2 to determine current requirements during alamilbattery standby operation when SK SLC devices
are installed. You can install up to 99 SK detectors and 99 SK modules. (Copy the page if additional space is
required.)
... . �_ ins Cr! n., iroe.
I4u1tl JAG. vun auc+ow••. ••v. �...+�..�-.....�_.._-
fax•.. �.;. ,_..
Number Standby ` Alarm
Device of Current per Device Current Current
Devices
or eac eV ce use i5 ormu a: Is co umm s co umn = urren ,per num or o eviaes.:
Fire Panel (current draw from 1 Standby: 471 mA 171 ml
battery) Alarm: $65 mA 365-mA
'Addressable SLC Detectors
3-5
Before You Begin Installing 151274-L8
Table 3-2: Current Draw Worksheet for SK Devices
Device
Number
of
Devices
Current per Device
Standby Alarm
Current Current
o
Z
1
(99 max.)
Standby/Alarm: .30mAs
.
MW 0 LO MT -O- 1.
SK -Photo -r
mA mA
SK -Ion
mA. mA
SK -Heat
mA 0,-5 mA S
SK -Heat -HT
mA mA
SK -Duct (includes PhotoRr
SK -Acclimate
SK-Heat-ROR
mA mA
mA mA
SK -Beam (without integral test)
-
SLC
Standby/Alarm:. 2 mA
Pwr
Standby:. 2 mA
mA
Alarm: 8.5 mA
mA
SK -Beam -T (with integral tao
SLC
Standby/Alarm: 2 mA
Aux. Pwrtandby2
mA
mA
`Alarm: 8.5 mA
mA
SK -FIRE -CO
SLC
Standby: .30 mA
mA
Alarm: -7.2 mA
-. mA...
Addressable ' --SLC Devices
SK -Monitor
L
5'
(99 max.)?
-
Standby/Alarm: .375 mA
mA L). mA
SK-Minimon
mA mA
SK-Pull-SA/SK-Pull-DA
MA '�,, p MA �- a
SK -Monitor -2
St andbylAlarm: .75 MA
mA mA
SK-Mon•10
Standby/Alarm:. 3.5 mA
MA. MA
SK -Control.
-
-
SLC
:Standby: .375 mA
Alarm: .375 mA
mA
mA
Aux.
Power
Standby: 1.7 mA
mA
Alarm:. 7 FA
mA
SK -Control -6
SLC
'Standby: 2.25 mA
Alarm:, 2.25mA
mA
mA.
Aux. Pwr
Standby: 6.mA
Alarm: 20 mA
mA
mA
SK -Relay -
Standby/Alarm: .255 mA
mA mA
SK-Ralay-6
:Standby/Alarm: 1.45 mA
mA mA
SK-RelayMon-2 -
.
Standby: 1.3mA.mA
Alarm: 24 mA
mA
SK -Zone
SK -Zone -6
(99max.)�
Aux Pwr
Standby: 12 mA
mA
.Alarm: BDmA
mA
SLC
Standby/Alarm: - .27 mA
mA mA
Aux Pwr
Standby: 50mA
mA
Alarm: 270 mA
mA
SLC
StandbylAlarm: 2 mA
mA MA
3-6
IntelliKnight 5808 Installation Manual
A
Table 3-2: Current Draw Worksheet for SK Devices
151274-L8
Device
Number
of
Devices
Current per Device
Standby
Current
Alarm
Current
SLQ Accessories
'Standby:
B200SR Sounder Base
max.)
Aux Pwr
.5 mA
mA
Alarm: 35 mA
mA
SLC
Alarm: .7 mA -`
mA
B200S Sounder Base
Aux Pwr
Standby: .5 mA mA
Alarm: 35 mA
mA
SLC
Alarm: - .7 mA s
mA
B200SR-LF Low Frequency Sounder(99
Base
Aux Pwr
Standby: - 1 mA mA
Alarm: - 125 mA
mA
B20OS-LF Low Frequency Sounder
Base
Aux
Standby .55 mA mA
Alarm (high vol) 140 mA -
mA
SLC
Standby .30 mA mA
B224RB Relay Base
Standby/Alarm: .5 mA mA
mA
RTS151/15 KKEY
Alarm: 7.5 mA -
mA
RA10OZ
Alarm: 10mAl
mA
SLC Isolator Devices
SK -ISO (Isolator Module)
(100 max.)
Standby/Alarm:
.45 mA
mA -
mA
1224B1 Isolator Base -
Standby/Alarm:
Accessories Modules
5860 Remote Fire Alarm Annunciator
(12 max)
Standby:
20 mA
mA
Alarm: 25 mA
mA
5824 Serial / Parallel Module
(2 max.)
Standby/Alarm:
45 mA
mA
mA
5496 Notification Power Expander
(8 max.)
Standby/Alarm:
10 mA
mA
mA
5895XL Intelligent Power expander
(8 max.)
Standby/Alarm:
10 mA
mA
mA
5865.4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby:
35 mA
mA
Alarm: 145 mA
mA
58653 LED Annunciator
Standby: 35 mA mA
Alarm: 145 mA
mA
5880 LED 1/0 Module
Standby: 35 mA mA
Alarm: 200 mA
MA
5883 Relay Interface
(32 max.)
Standby:
O mA
mA
Alarm: 220 mA
(22 mA per
relay)
mA
Total System Current
Auxlllary, Devices2 '
Refer to devices manual for current rating,
Alarm/Standby:
mA mA
ImA
Alarm/Standby:
mA mA
in
Alarm/Standby:
mA mA
mA
Alarm/Standby:
mA mA
mA
Auxiliary Devices Current
Notification Appliance -Circuits
Refer to devices manual for current rating.
\L—k
12.
Alarm:
iAlarm:
mAjI
Ca mA
MA —&00
3-7
IN
Before You Begin Installing 951274-L8
Table 3.2; Current Draw Worksheet for SK Devices
rn
C
M
D
E
y F
G
a H
Device
Number
of Current per Device
Devices
Standby
Current
Alarm
Current
2.
-Ala—rar. MA
m
during that time. However, during normal operation, door holders draw current and must be included in the 6.OA total current
Alarm: mA
mA
Notification Appliances Current
3.
mA "j 05
Total current ratings of all devices in system (line A+ line a + C)
mA 1-74
mA q I by'
Total current ratings converted to amperes (line. D x.001):
A O, t74
A '-1.1(.4
Number of standby hours (24 or 60 for NFPA 72, chapter 1,15,2.5):
H 21%A
The SK -Duct housing contains a vacant mount for a SK -Relay (sold separately). Current draw for the SK -Relay is calculated
Multiply lines E and F. Total standby AH
AH 14 -7 --
by increasing the SK -Relay row of the calculation sheet by one for each SK -Relay used with a SK -Duct.
Alarm sounding period In hours. (For example, 5 minutes -.0833 hours)
6.
H p, o`b°33
Multiply lines E and H. .Total alarm AH
AH:
Add lines G and Ls Total ampere hours required
H +�'.ej
I.
Total does not include isolator devices or accessory bases. 1
2.
If using door holders, you do not need to consider door holder current for alanwbattety standby, because power is removed
during that time. However, during normal operation, door holders draw current and must be included in the 6.OA total current
that can be drawn from the panel.
3.
Use next size battery with capacity greater than required.
4.
SK -Beam -T draws a maximum of5OOmA from Auxiliary power only when the test feature is used. This should be considered
when determining auxiliary power capacity but not calculated into current requirements for day to day operation,
5.
The SK -Duct housing contains a vacant mount for a SK -Relay (sold separately). Current draw for the SK -Relay is calculated
by increasing the SK -Relay row of the calculation sheet by one for each SK -Relay used with a SK -Duct.
+
6.
The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
- Installation
A
F
Table 11-2: Battery Calculation Worksheet
Number of
Device
Current per Device
Standby
Current
Alarm
Current
Devices
h device use this formula: This column
F5495
X This column
=Current
per numher
of devices.
stributed Power Module Standby: 75Alt
draw from battery)
5495 Current
75 mA
175 mA
Auzaliary PeYices " Refer to device mant<kl far current ratings. , f
AlamdStandby mA mA mA
Alarm/Standby mA
mA mA
Alarm/Standby mA
mA mA
Alarm/Standby mA
mA mA
Auxiliary Devices Current
mA mA
NofiRcanot%apphances Sefer to device rrimiuOjor curre»t ratings: "
�.,
Alarm: ? mA 0 mAJ�O� mA
Alarm: mA 0 mA mA
Alarm:
mA
0 mA
mA
Alarm:
mA
0 mA
mA
Notification Appliances Current
0 mA
2J�„d mA
Total current ratings of all devices in system (line A + line B + line C)
–75-mA
37"75" mA
Total current ratings converted to amperes (line D x .001):
O. L -0j A
'J✓' , y A
Number of standby hours (24 or 60 for NFPA 72, Chapter 1,1-52.5).
'ZIA H
Multiply lines E and F. Total standby AH
¢3j AH
Alarm sounding period in hours.
H
(For example, 5 minutes =.0833 hours.)
Multiply lines E and H. Total alarm AH
.Z
a vj t i AH
Add lines G and I. Total standby and alarm AH
• (� 5— AH
Multiply line 7 by 1.20.
` (20% extra insurance to meet desired performance) Total ampere -hours required
Z + i0 AH
P/N 151161