HomeMy WebLinkAboutREPORT REVIEW 2 - 17-00118 - 555 W Mikan Dr - Eden Apartments Site PlanReview
Report
Current Fire Department Review - Site Plan Status: REVISIONS
Application Number: 17-00118Permit Details
Application Received Date: 03/20/2017
Site Plan
Application Approved Date:
Application Approved Status: APPROVED
03/20/2017
550 W Mikan Dr
Eden Apartments Site Plan
Status of Plan Reviews Completed
03/21/2017Public Works Review - Site Plan REVISIONS
03/22/2017Planning and Zoning Review - Site Plan REVISIONS
03/28/2017Fire Department Review - Site Plan REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Public Works Review - Site Plan
Planning and Zoning Review - Site Plan
Fire Department Review - Site Plan
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Plans are approved for a footing/foundation
ONLY permit?
YES
Hydrant located within 150' from FDC REVISIONSBuilding 10&11 need a hydrant between them.
Move the hydrant near building 13 to the North
entrance.Move the hydrant near building 4$5 to
the North East corner of the entrance.Move the
hydrant in front o building 7 to the North to
cover building 6 better.Move hydrant in front of
building 11 to the South East corner of Area A.
*Revisions Response :
Minimum fire lane clearance 13'6"N/A
Fire lanes exceeding 150' require a turn-around COMPLETED
30' inside radius and 45' outside radius COMPLETED
Building height >30' - fire lane to be 30' to 45'
from building
COMPLETED
No hydrants within 40' of building COMPLETED
Reviewed By: Dale Pickering
Review Date: 03/28/2017
Plan Review Details
dale.pickering@rexburg.org
Fire Department Review - Site Plan Status: REVISIONS
Additional Inspector Comments:
Chief Davis came in to talk about his review today. He said that he'd need clarification if the blue dots that say HYD
are fire hyrdrants (he's assuming they are) and said that if so, the water lines for buildings 3 and 6 are too far from
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Fire Department Review - Site Plan (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
a hydrant and suggested bringing the line under the buildings to the other side in order to bring them closer to
hydrants. Other than that they look good. - CM
Page 2 of 2
Approval of plans does not constitue approval of variance from code