HomeMy WebLinkAboutRESCHECK - 17-00120 - 555 W Mikan Dr - Eden Apartments Bldg 1 - 30 UnitsCOMcheck Software Version 4.0.0 Envelope Compliance Certificate Project Information Energy Code: 2012 IECC Project Title: Eden Apartments Location: Rexburg, Idaho Climate Zone: 6b Project Type: New Construction Vertical Glazing / Wall Area: 13% Construction Site: Owner/Agent: 950 Mikan Drive Rexburg„ ID 823440 Building Area Floor Area 1 -MAIN FLOOR (Multifamily) : Residential 7234 2 -2ND FLOOR (Multifamily) : Residential 7234 3 -3RD FLOOR (Multifamily) : Residential 7234 Designer/Contractor: Additional Efficiency Package High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist report. Envelope Assemblies Assembly Roof 1: Attic Roof with Wood Joists, [Bldg. Use 3 - 3RD FLOOR] Exterior Wall 1: Wood -Framed, 16" o.c., [Bldg. Use 3 - 3RD FLOOR] Window 1: Vinyl/Fiberglass Frame:Operable, Pert. Specs.: Product ID na, SHGC 0.70, [Bldg. Use 3 - 3RD FLOOR] (c) Door 1: Other Door, Swinging, [Bldg. Use 3 - 3RD FLOOR] Exterior Wall 2: Wood -Framed, 16" o.c., [Bldg. Use 2 - 2ND FLOOR] Window 2: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID na, SHGC 0.70, [Bldg. Use 2 - 2ND FLOOR] (c) Door 2: Other Door, Swinging, [Bldg. Use 2 - 2ND FLOOR] Exterior Wall 3: Wood -Framed, 16" o.c., [Bldg. Use 1 - MAIN FLOOR) Window 3: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID na, SHGC 0.70, [Bldg. Use 1 - MAIN FLOOR] (c) Door 3: Other Door, Swinging, [Bldg. Use 1 - MAIN FLOOR] Floor 1: Wood -Framed, [Bldg. Use 3 - 3RD FLOOR] Floor 2: Wood -Framed, [Bldg. Use 2 - 2ND FLOOR] Floor 3: Slab -On -Grade: Unheated, Vertical 2 ft., [Bldg. Use 2 - 2ND Gross Area Cavity Cont. Proposed Budget U - or R -Value R -Value U -Factor Factor(.) Perimeter 7234 49.0 0.0 0.021 0.021 5931 23.0 0.0 0.059 0.051 796 --- --- 0.300 0.430 160 --- --- 0.025 0.370 5931 23.0 0.0 0.059 0.051 796 -- --- 0.300 0.430 160 -- --- 0.025 0.370 5931 23.0 0.0 0.059 0.051 796 -- --- 0.300 0.430 160 --- --- 0.025 0.370 7234 0.0 40.0 0.023 0.033 7234 0.0 40.0 0.023 0.033 659 -- 10.0 0.550 0.520 (a) Budget U -factors are used for software baseline calculations ONLY, and are not code requirements. (b) 'Other'components require supporting documentation for proposed U -factors. (c) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation. (d) Slab -On -Grade proposed and budget U -factors shown in table are F -factors. Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 1 of 9 Envelope Compliance Statement Compliance Statement: The proposed envelope design represented in this document Is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envelope systems have been designed to meet the 2012 IECC requirements in COMcheck Version 4.0.0 and to comply with the mandatory requirements listed in the Inspection Checklist. Date Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 2 of 9 COMcheck Software Version 4.0.0 Inspection Checklist Energy Code: 2012 IECC Requirements: 0.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. 2012 :ECC Plan Review Complies? Comments/Assumptions C103.2 ;Plans and/or specifications provide all❑Complies [PR111 :information with which compliance❑Does Not ; can be determined for the building ;envelope and document where ❑Not Observable; I❑Not Applicable :exceptions to the standard are ; ;claimed. 0406 .Plans, specifications, and/or ❑Complies [PR911 :calculations provide all Information j❑Does Not :with which compliance can be :[]Not Observable; (determined for the additional energy :efficiency package options.❑Not Applicable 0402.3.1 ;Vertical fenestration area <= 30 ;❑Complies [PR1011 ; percent of the gross above -grade wall ;❑Does Not :area. ;❑Not Observable' ❑Not Applicable 04023,1 jSkylight area <= 3 percent of the :❑Complies [PR1111 ;gross roof area.❑Does Not ❑Not Observable: ' ;❑Not Applicable j C402.3.2. (Areas with obstructions that block❑Complies 2 (direct beam sunlight on >= 1/2 of the :❑Does Not : [PR15]1 :roof over the enclosed area for more : : :❑Not Observable; :than 1,500 daytime hours per year :between 8 am and 4 pm. I❑Not Applicable Additional Comments/Assumptions: 1 I High Impact (Tier 1) Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 3 of 9 Section # Footing / Foundation Plans Verified Field Verified Complies. Comments/Assumptions & Req .ID Inspection Value Value C402.2.6 'Slab edge insulation R-value. R- R-_❑Complies ;See the envelope Assemblies [FO31z ❑ Unheated ❑ Unheated❑Does Not table for values. ❑ Heated❑Heated❑Not Observable j❑Not Applicable C303.2 !Slab edge insulation installed per❑Complies i; [FO412 manufacturer's instructions. �r ❑Does Not r ❑Not Observable '.❑Not Applicable 0402.2.6 ;Slab edge insulation ft ft❑Complies See the Envelope Assemblies [FO5]2 (depth/length. Slab insulation❑Does Not ;table for values. ;extending away from building is Observable (covered by pavement or >= 10❑Not '.'.❑Not Applicable inches of soil. 0403.2.7, Exterior insulation protected❑Complies C408.2.8, !against damage, sunlight,❑Does Not C404.5 ;moisture, wind, landscaping and ❑Not Observable I [FO611 ;equipment maintenance', ;activities. ',.❑Not Applicable C402,2.8 Bottom surface of floor structures Complies ;See the Envelope Assemblies [FO12]3. incorporating radiant heating Roes Not :table for values. •,insulated to >=R-3.5. '..❑Not Observable ❑Not Applicable Additional Comments/Assumptions: 11 High Impact (Tier 1) Medium Impact (Tier 2) 1z,fl Low Impact (Tier 3) Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 4 of 9 Section # Framing / Rough -In Inspection Plans Verified Value Field Verified Value Complies? Comments/Assumptions & Reci.ID C402.4.1, ;The building envelope contains a❑Complies C402.4.2 :continuous air barrier that is -❑Does Not [FR161' ;sealed in an approved manner Observable :and either constructed or tested❑Not in an approved manner. Air ❑Not Applicable j :barrier penetrations are sealed in -. :an approved manner. C402.4.3, ; Factory -built fenestration andzaap❑Complies C402.4.4 !doors are labeled as meeting air 'I]Does Not [FR1813 �', leakage requirements. ❑Not Observable ❑Not Applicable C402.4.7 !Vestibules are installed on all '.. .❑Complies [FR17]3 'building entrances. Doors have❑Does Not self-closing devices. '.. ',..❑Not Observable ❑Not Applicable 0402.33, Vertical fenestration U -Factor. '.. U- U- ❑Complies see the envelope Assemblies C402.3.4❑Does Not table for values. [FR8]'❑Not Observable ❑Not Applicable 04023.3 (Vertical fenestration SHGC value.! SHGC: SHGC:❑Complies ',See the envelope assemblies [FR1011❑Does Not table for values. I❑Not Observable ❑Not Applicable C303.1.3 .;Fenestration products rated in ,❑Complies [FR12j2 r!accordance with NFRC. - ❑Does Not ❑Not Observable ''. :❑Not Applicable C303.1.3 Fenestration products are❑Complies [FR13]1 'certified as to performance labels -❑Does Not or certificates provided. ❑Not Observable I ❑Not Applicable C402.2.7 U -factor of opaque doors U- '.. U- ❑Complies ;See the envelope Assemblies [FR141' 'associated with the building _ E Swinging ❑ Swinging',❑Does Not (table for values. thermal envelope meets ❑ Nonswinging ❑ Nonswinging ;❑Not Observable ; requirements. ❑Not Applicable Additional Comments/Assumptions: 1 I High Impact (Tier 1) Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 5 of 9 Mechanical Rough -in Inspection I Complies? Stair and elevator shaft vents have ❑Complies motorized dampers that automatically []Does Not close. ❑Not Observable; C402,4.5. ;Outdoor air and exhaust systems have;❑Complies 2 i motorized dampers that automatically I❑Does Not [ME58]3 ;shut when not In use and meet maximum leakage rates. Check❑Not Observable !gravity dampers where allowed. ;❑Not Applicable Additional Comments/Assumptions: Comments/Assumptions 1 I High Impact (Tier 1) Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 6 of 9 Section # Insulation Inspection Plans Verified Value Field Verified Value Complies? Comments/Assumptions & Re .ID C402.4.1. :All sources of air leakage in the ❑Complies 1 -:building thermal envelope are❑Does Not [IN111 :sealed, caulked, gasketed, - :❑Not Observable I :weather stripped or wrapped with moisture vapor -permeable !❑Not Applicable :wrapping material to minimize air' leakage. C402.4.2. ;Roof R -value. For some ceiling R- R -❑Complies see the Envelope Assemblies 1 :systems, verification may need to. ❑Above deck ❑Above deck Not table for values. [IN211 ;occur during Framing Inspection. ❑ Metal 1 ❑ Metal ❑Not Observable i ❑ Attic ❑ Attic❑Not Applicable C303.2 ;Roof insulation installed per❑Complies [IN311 manufacturer's instructions.❑Does Not ;Blown or poured loose -fill - :.insulation is installed only where ❑Not Observable :the roof slope is <=3 in 12. !❑Not Applicable pp C303.2 ;Above -grade wall insulation '..❑Complies [IN7]1 installed per manufacturer's'❑Does Not instructions. :.❑Not Observable []Not Applicable C402.2.5 ! Floor insulation R -value. R- R- ❑Complies ;see the Envelope Assemblies [INS]1 ;❑ Mass ❑ Mass C]Does Not table for values. ❑ Steel ❑ Steel ;❑Not Observable I ❑ Wood I ❑ Wood ❑Not Applicable C303.2 ;Floor insulation installed per ❑Complies [IN9]1 !manufacturer's instructions. ❑Does Not ❑Not Observable ❑Not Applicable C303.1 :Building envelope insulation is ❑Complies [IN10]2 labeled with R -value or insulation ❑Does Not ;certificate providing R -value and ;other relevant data.❑Not Observable ; - ❑Not Applicable C303.2.1 Exterior insulation is protected '.. ❑Complies [IN1412 )from damage with a protective ❑Does Not material. Verification for exposed '.. Observable ; foundation insulation may need❑Not to occur during Foundation ❑Not Applicable j Inspection. C402.2.1 !Insulation intended to meet the ❑Complies [:N171' goof insulation requirements - ❑Does Not ;cannot be installed on top of a Observable' 'suspended ceiling. Mark this❑Not !. requirement compliant if❑Not Applicable :insulation is Installed accordingly..: Additional Comments/Assumptions: 1 High Impact (Tier 1) 1 Te Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 7 of 9 20121ECC Final Inspection Complies? Comments/Assumptions C402.4.6 jWeatherseals installed on all loading ❑Complies [FI37]1 dock cargo doors. ❑Does Not ❑Not Observable ❑Not Applicable C402.4.8 !Recessed luminaires in thermal ;LJComplies [F126 ]3 !envelope to limit infiltration and be IC❑Does Not !rated and labeled. Seal between Observable ;interior finish and luminaire housing.❑Not ❑Not Applicable 0406 Efficient HVAC performance, efficient ❑Complies [FI3411 lighting system, or on-site supply of❑Does Not i renewable energy consistent with ;what is shown the approved plans. , Observable ;n Nn« An..lirohle Additional Comments/Assumptions: 11 High Impact (Tier 1) #'2„. Medium Impact (Tier 2) 3S1 LOW Impact (Tier 3) Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 8 of 9 Project Title: Eden Apartments Report date: 04/17/17 Data filename: C:\Users\Guy\Documents\COMcheck\Eden 30 unit Apartment Buildings.cck Page 9 of 9