HomeMy WebLinkAboutRESCHECK - 17-00121 - 555 W Mikan Dr - Eden Apartments Bldg 2 - 42 UnitsCOMcheck Software Version 4.0.0
Envelope Compliance Certificate
Project Information
Energy Code:
2012 IECC
Project Title:
Eden Apartments
Location:
Rexburg, Idaho
Climate Zone:
6b
Project Type:
New Construction
Vertical Glazing /Wall Area:
16%
Construction Site: Owner/Agent:
950 Mikan Drive
Rexburg,, ID 83440
Building Area
Floor Area
1 -MAIN FLOOR (Multifamily): Residential 10910
2 -2ND FLOOR (Multifamily) : Residential 10910
3 -3RD FLOOR (Multifamily): Residential 10910
Designer/Contractor:
Additional Efficiency Package
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Envelope Assemblies
Assembly
Gross Area Cavity Cont. Proposed Budget U.
or R -Value R -Value U -Factor Factorm
Perimeter
Roof 1: Attic Roof with Wood Joists, [Bldg. Use 3 - 3RD FLOOR]
10910
49.0 0.0
0.021
0.021
Exterior Wall 1: Wood -Framed, 16" o.c., [Bldg. Use 3 - 3RD FLOOR]
7974
23.0 0.0
0.059
0.051
Window 1: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID
1286
--- ---
0.300
0.430
na, SHGC 0.70, [Bldg. Use 3 - 3RD FLOOR] (c)
Door 1: Other Door, Swinging, [Bldg. Use 3 - 3RD FLOOR]
240
--- ---
0.025
0.370
Exterior Wall 2: Wood -Framed, 16" o.c., [Bldg. Use 2 - 2ND FLOOR]
7974
23.0 0.0
0.059
0.051
Window 2: Vinyl/Fiberglass Frame:Operable, Pert. Specs.: Product ID
1286
--- ---
0.300
0.430
na, SHGC 0.70, [Bldg. Use 2 - 2ND FLOOR] (c)
Door 2: Other Door, Swinging, [Bldg. Use 2 - 2ND FLOOR]
240
--- ---
0.025
0.370
Exterior Wall 3: Wood -Framed, 16" o.c., [Bldg. Use 1 - MAIN FLOOR]
7974
23.0 0.0
0.059
0.051
Window 3: Vinyl/Fiberglass Frame:Operable, Pert. Specs.: Product ID
1286
--- ---
0.300
0.430
na, SHGC 0.70, [Bldg. Use 1 - MAIN FLOOR] (c)
Door 3: Other Door, Swinging, [Bldg. Use 1 - MAIN FLOOR]
240
--- ---
0.025
0.370
Floor 1: Wood -Framed, [Bldg. Use 3 - 3RD FLOOR]
10910
0.0 40.0
0.023
0.033
Floor 2: Wood -Framed, [Bldg. Use 2 - 2ND FLOOR]
10910
0.0 40.0
0.023
0.033
Floor 3: Slab-On-Grade:Unheated, Vertical 2 ft., [Bldg. Use 2 - 2ND
886
--- 10.0
0.550
0.520
FLOOR] (d)
(a) Budget U -factors are used for software baseline calculations ONLY, and are not code requirements.
(b) 'Other components require supporting documentation for proposed U -factors.
(c) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(d) Slab -On -Grade proposed and budget U -factors shown in table are F -factors.
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings.cck Page 1 of 9
Envelope Compliance Statement
Compliance Statement., The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.0.0 and to comply with the mandatory requirements listed
in the Inspection Checklist.
Name - Title Signature
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings.cck Page 2 of 9
COMcheck Software Version 4.0.0
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen, For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
2012 IECC
Plan Review
Complies?
Comments/Assumptions
C103.2
!Plans and/or specifications provide all❑Complies
[PR111
: information with which compliance
;❑Does Not
.can be determined for the building
:❑Not Observable!
;envelope and document where
:exceptions to the standard are
;❑Not Applicable
:claimed.
C406
-'.Plans, specifications, and/or❑Complies
[PR911
calculations provide all information
❑Does Not
;with which compliance can be
(determined for the additional energy❑Not
:
Observable
:efficiency package options.
I❑Not Applicable
C402.3.1
'Vertical fenestration area <= 30❑Complies
[PRIO]1
; percent of the gross above -grade wall
;❑Does Not
;area.
❑Not Observable
:[]Not Applicable
0402.3.1
(Skylight area <= 3 percent of the
[Complies
[PR11]1
:gross roof area.
❑Does Not
I❑Not Observable I
❑Not Applicable
C4023.2.
(Areas with obstructions that block❑Complies
2
(direct beam sunlight on >= 1/2 of the
:❑Does Not i
[PR1511
!;roof over the enclosed area for more
:❑Not Observable;
(than 1,500 daytime hours per year
:. between 8 am and 4 pm.
;❑Not Applicable ;
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 13, 1 low Impact (Tier 3)
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings,cck Page 3 of 9
Section
#
Footing / Foundation
Plans Verified
Field Verified
Complies?
Coin ments/Assumptions
& Req.ID
Inspection
Value
Value
C402 rSlab
edge insulation R -value.
R-
R-
:❑Complies .See the Envelope Assemblies
[FO31.;'
;❑ Unheated
❑ heated
Not table for values.
El Heated
E] Heated
j❑Not Observable 1
':�
j❑Not Applicable
0303.2
;Slab edge insulation installed per
.�
'�'
❑Complies
[F04 12
i manufacturer's instructions,
❑Does Not
`,❑Not Observable
❑Not Applicable
0402.2.6
;Slab edge insulation
ft
ft
Complies ;See the Envelope Assemblies
[F05 12
:depth/length. Slab insulation❑Does
Not (table for values.
;extending away from building is
'covered
❑Not Observable
by pavement or >= 10
inches of soil.❑Not
Applicable
C403.2.7,
Exterior insulation protected
❑Complies
C408,2.8,
'against damage, sunlight,
❑Does Not
C4045
moisture, wind, landscaping and
-
❑Not Observable
[F06]1
.equipment maintenance
T
❑Not Applicable
activities.
-,-
e s3 rx`
C402.2.8;.
, Bottom surface of floor structures
❑Complies ;See the Envelope Assemblies
[FO12]3
incorporating radiant heating
❑Does Not ;table for values.
-
:insulated to >=R-3.5.
[]Not Observable
-;
.y , >W„�,
_ _.ter ❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 'r.g Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings.cck Page 4 of 9
Section
#I
Framing / Rough -In Inspection
Plans Verified
Value
Field Verified
Value
Complies?
EComments/AssumptionsmmtI/Assumptions
& Req. ID
C402.4.1,
;The building envelope contains a❑Complies
C402.4.2
(continuous air barrier that is
:
❑Does Not
[FR16]1
;sealed in an approved manner
'..❑Not
land either constructed or tested
Observable
lin an approved manner. Air❑Not
-'
Applicable
;barrier penetrations are sealed in
:an approved manner.
C402.4.3,
;Factory -built fenestration and '..❑Complies
0402.4.4
,doors are labeled as meeting air
❑Does Not
[FR18]3
leakage requirements.
][]Not Observable
{❑Not Applicable
0402.4.7
!Vestibules are installed on all '..',❑Complies
[FR1713
building entrances. Doors have❑Does
Not
self-closing devices.
❑Not Observable
❑Not Applicable
C402.3.3,
;Vertical fenestration U -Factor. U-
'.. U_
Complies ;see the Envelope Assemblies
0402.3.4❑Does
Not table for values.
[FR811❑Not
Observable
❑Not Applicable
0402.3.3
;Vertical fenestration SHGC value. SHGC:_
SHGC:_
:❑Complies ;See the Envelope Assemblies
[FR1011❑Does
Not ;table for values.
:[--]Not Observable
❑Not Applicable
C303.1.3
;Fenestration products rated in '..❑Complies
[FR1212
:accordance with NFRC. ',.
l❑Does Not
❑Not Observable
❑Not Applicable j
C303.1.3
;Fenestration products are
❑Complies
[FR1311
:certified as to performance labels❑Does
Not
or certificates provided.
❑Not Observable
j❑Not Applicable
C402.2.7
U -factor of opaque doors U-
U-
❑Complies ;Seethe Envelope Assemblies
[FR1412
'associated with the building ❑ Swinging
❑ Swinging
',❑Does Not ; table for values.
;thermal envelope meets ❑ Nonswinging
; ❑ Nonswinging❑Not
Observable I
;requirements.
j❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 1. Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings.cck Page 5 of 9
Mechanical Rough -In Inspection I Complies? I Comments/Assumptions
C402.4.5. Stair and elevator shaft vents have
1 motorized dampers that automatically
[ME313 close.
s Not
Observable;
C402.4.5. Outdoor air and exhaust systems have ILJComplies
2 motorized dampers that automatically❑Does Not
[ME5813 shut when not in use and meet
maximum leakage rates. Check❑Not Observable:
gravity dampers where allowed.❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings.cck Page 6 of 9
Section
#
Insulation Inspection
plans Verified
Value
Field Verified
Value
Complies? Coin me nts/Assumptions
& Req.ID
C402.4.1.
:All sources of air leakage in the
'..
❑Complies
1
building thermal envelope are
'..
❑Does Not
[IN111
:sealed, caulked, gasketed,
Observable f
:weather stripped or wrapped with
moisture vapor-permeable❑Not
.❑Not
Applicable :
;wrapping material to minimize air
(leakage.
C402.4.2.
;Roof R -value. For some ceiling
; R- R-
❑Complies :see the Envelope Assemblies
1
:systems, verification may need to
❑Above deck ❑ Above deck
Does Not ;table for values.
[IN211
;occur during Framing Inspection.
❑ Metal ❑ Metal❑Not
Observable
❑ Attic ❑ Attic❑Not
Applicable
0303.2
;Roof insulation installed peri;
': s` 4"tea a:�`•.,'
- -❑Complies
[IN311
:manufacturer's instructions.
❑Does Not
:Blown or poured loose -fill
;insulation is installed only where
❑Not Observable
ahe roof slope is <=3 in 12.❑Not
Applicable
C303.2
;Above -grade wall insulation
- '.'❑Complies
[IN711
:installed per manufacturers
❑Does Not
;instructions.
Not Observable
� ❑❑Not
'
Applicable
C402.2.5
Floor insulation R -value.
R- R -❑Complies
;see the Envelope Assemblies
[IN8]2
j ❑Mass ❑ Mass
;❑Does Not ;table for values.
❑Steel ; ❑ Steel
;❑Not Observable
❑ Wood ❑ Wood
;❑Not Applicable
C303.2
Floor insulation installed per
'❑Complies
[IN9]2
manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
0303.1
Building envelope Insulation is
❑Complies
[IN10]2
labeled with R -value or insulation❑Does
Not
!certificate providing R -value and
'..
I❑Not Observable
other relevant data.
j❑Not Applicable
C303.2.1 ;Exterior
insulation is protected
'..
I❑Complies
[IN14]2 :from
damage with a protective
❑Does Not
material. Verification for exposed
Observable
l
',to
foundation Insulation may need❑Not
occur during Foundation❑Not
Applicable :
;Inspection.
C402.2.1
Insulation intended to meet the
'..❑Complies
[IN17]3
:roof insulation requirements
❑Does Not
:cannot be installed on top of a
❑Not Observable ;
(suspended ceiling. Mark this
jrequirement compliant if
❑Not Applicable
insulation is installed accordingly.
Additional Comments/Assumptions:
1 I High Impact (Tier 1) DZI Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings.cck Page 7 of 9
0121ECC Final Inspection
Complies? Comments/Assumptions
C402.4.6
; Weatherseals installed on all loading
❑Complies
[FI37]1
dock cargo doors.❑Does
Not
❑Not Observable:
❑Not Applicable
C402.4.8
;Recessed luminaires in thermal❑Complies
[FI26]3
:envelope to limit infiltration and be IC
I❑Does Not
:rated and labeled. Seal between
Observable;
;interior finish and luminaire housing.❑Not
❑Not Applicable
C406
Efficient HVAC performance, efficient❑Complies
[F13411
lighting system, or on-site supply of❑Does
Not
; renewable energy consistent with
!❑Not Observable
what is shown the approved plans.
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings.cck Page 8 of 9
Project Title: Eden Apartments Report date: 04/17/17
Data filename: C:\Users\Guy\Documents\COMcheck\Eden 42 unit Apartment Buildings,cck Page 9 of 9