COMcheck Software Version 4.0.6.1
Interior Lighting Compliance Certificate
Project Information
Energy Code:
Project Title:
Project Type:
Construction Site:
PHYSICAL PLANT WAY
REXBURG, ID 83440
Additional Efficiency Package
2012 IECC
BYU-I AUSTIN BUILDING REMODEL
New Construction
Owner/Agent:
BYU-IDAHO
REXBURG, ID
Designer/Contractor:
Payne Engineering
1823 E. Center Street
Pocatello, ID 83201
208-232-4439
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Allowed Interior Lighting Power
A
B
C
D
Area Category
Floor Area
Allowed
Allowed Watts
(ft2)
Watts / ft2
(B X C)
1 -ROOM 105AI105B (Common Space Types:Classroom / Lecture / Training)
1900
1.30
2470
2 -Common Space Types:Restroom
735
1.00
735
3 -ROOM 170/150 (Common Space Types:Classroom / Lecture / Training)
1930
1.30
2509
4 -ROOM 163/171 C (Common Space Types:Classroom / Lecture / Training)
2476
1.30
3219
5 -ROOM 181 (Common Space Types:Classroom / Lecture / Training)
1100
1.30
1430
6 -LEVEL 3 ROOMS (Common Space Types:Classroom / Lecture / Training)
5179
1.30
6733
7 -Common Space Types:Corddor / Transition
658
0.70
461
Total Allowed Watts = 17556
Proposed Interior Lighting Power
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
1 -ROOM 105A/105B (Common Space Types Classroom/ Lecture/ Training)
LED 1: F1/FIE: HIGHBAY LED: Other:
1
9
55
495
LED 1 copy 1: F2: HIGHBAY LED: Other:
1
6
80
460
2 -Common Space Types7Restroom
LED 3: F3: 4FT STRIP: Other:
1
1
75
75
LED 3 copy 1: F6/F6A: 4FT SURFACE WRAP: Other:
1
10
40
400
LED 3 copy 2: 178: 2X4 TROFFER: Other:
1
2
32
64
3 -ROOM 170/150 (Common Space Types'Class=tn / Lecture / Training)
LED 1 copy 1: F1/FIE: HIGHBAY LED: Other:
1
15
55
825
LED 1 copy 2: F2: HIGHBAY LED: Other:
1
6
80
480
4 -ROOM 163/171C (Common Space Types7Classroom / Lecture / Training)
LED 1 copy 2: F1/FIE: HIGHBAY LED: Other:
1
16
55
880
LED 3 copy 3: F5: 2X4 TROFFER: Other:
1
6
35
210
5 -ROOM 181 (Common Space Types:Classroom / Lecture / Training)
Project Title: BYU-1 AUSTIN BUILDING REMODEL
Report date:
05/25/17
Data filename: Untitled.cck
Page
1 of 7
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
LED t copy 3: F2: HIGHBAY LED: Other:
LED 3 copy 2: F6/F6A: 4FT SURFACE WRAP: Other:
6 -LEVEL 3 ROOMS (Common Space Types Classroom / Lecture / Training/
LED 3 copy 4: F7/F7E: 2X2 TROFFER: Other:
LED 3 copy 5: F4A: 2X2 TROFFER: Other:
7 -Common Space Tyoes:Corridor / Transition
LED 3 copy 6: F4A: 2X2 TROFFER: Other:
LED 3 copv 3: F8: 2X4 TROFFER: Other:
Interior Liahtina PASSES: Design 570 hetter than Inde
B C D E
Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
1 6 80 480
1 2 40 80
1 63 40 2520
1 4 40 160
1 6 40 240
1 3 32 96
Total Proposed Watts = 7485
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.0.6.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Shawn Meador, PE
Shawn Meador
05/25/17
Date
Project Title: BYU-1 AUSTIN BUILDING REMODEL Report date: 05/25/17
Data filename: Untitled.cck Page 2 of 7
COMcheck Software Version 4.0.6.1
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
#
& Re .ID
Plan Review
Complies?
Comments/Assumptions
C103.2
Plans, specifications, and/or
❑Complies
(PR411
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
.determined for the interior lighting
❑Not Applicable
- andelectrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 13 1 Low Impart (Tier 3)
Project Title: BYU-I AUSTIN BUILDING REMODEL Report date: 05/25/17
Data filename: Untitled.cck Page 3 of 7
Section
#
Rough -In Electrical InspectionComplies?
Comments/Assumptions
& Re .ID
C405.2.2.
Automatic controls to shut off all
❑Complies
1
building lighting installed in all
❑Does Not
[EL22]2
buildings.
❑Not Observable
❑Not Applicable
C405.2.1.
Independent lighting controls installed
❑Complies
1
per approved lighting plans and all
❑Does Not
[EL23]2
manual controls readily accessible and
❑Not Observable
visible to occupants.
❑Not Applicable
C405.2.1.
Lighting controls installed to uniformly
❑Complies
2
reduce the lighting load by at least
❑Does Not
[EL15]1
50%.
❑Not Observable
❑Not Applicable
C405.2.2.
Daylight zones provided with
❑Complies - -
3
individual controls that control the
❑Does Not
[EL16]'
lights independent of general area
-
❑ Not Observable
lighting.
❑Not Applicable
C405.2.3
Sleeping units have at least one
❑Complies
[EL17]3
master switch at the main entry door
❑Does Not
that controls wired luminaires and
Observable
switched receptacles.❑Not
❑Not Applicable
C405.2.2.
Occupancy sensors installed in
❑Complies
2
required spaces.
❑Does Not
[EL18]1
❑Not Observable
❑Not Applicable
C405.2.2
Primary sidelighted areas are
❑Complies
3
equipped with required lighting
❑Does Not
[EL2011
controls.
❑Not Observable
❑Not Applicable
C405.2.2..
Enclosed spaces with daylight area
❑Complies
3
under skylights and rooftop monitors
❑Does Not
[EL21]1
are equipped with required lighting
-controls.
❑Not Observable
-
❑Not Applicable
0405.23
Separate lighting control devices for
❑Complies
[EL4]1
specific uses installed per approved
❑Does Not
,lighting plans.
❑Not Observable
❑Not Applicable
C405.3
Fluorescent luminaires with odd
❑Complies
[EL19]3
numbered lamp configurations that
❑Does Not
are within 10 feet center to center (if
erval
❑Not Observable
recess mounted) or are within 1 foot
❑Not Applicable
edge to edge (if pendant or surface
mounted) shall be tandem wired.
0405.4
Exit signs do not exceed 5 watts per
❑Complies
[EL611
face.❑Does
Not
❑Not Observable
❑Not Applicable
C405.2.3
Additional interior lighting power
❑Complies
[EL8]1
allowed for special functions per the
❑Does Not
approved lighting plans and is
❑Not Observable
automatically controlled and
separated from general lighting.
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: BYU-I AUSTIN BUILDING REMODEL Report date: 05/25/17
Data filename: Untitled.cck Page 4 of 7
U
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BYU-I AUSTIN BUILDING REMODEL Report date: 05/25/17
Data filename: Untitled.cck Page 5 of 7
5
Section
I.
Al
Final InspectionComplies?
Comments/Assumptions
& Re .ID
C408.2.5.
Furnished as -built drawings for
❑Complies
1
electric power systems within 30 days
❑Does Not
[FI16]3
of system acceptance.
❑Not Observable
❑Not Applicable
C303.3,
Furnished O&M instructions for
❑Complies
C408.2.5.
systems and equipment to the
❑Does Not
2
[FI17]3
building owner or designated
representative.
❑Not Observable
❑Not Applicable
C405.5.2
Interior installed lamp and fixture❑Complies
See the Interior Lighting fixture schedule for values.
[FI18]1
lighting power is consistent with what
❑Does Not
is shown on the approved lighting❑Not
Observable
plans, demonstrating proposed watts
❑Not Applicable
are less than or equal to allowed
watts.
C408.3
-Lighting systems have been tested to
❑Complies - ---
[FI33]1
ensure proper calibration, adjustment,
❑Does Not
programming, and operation.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: BYU-I AUSTIN BUILDING REMODEL Report date: 05/25/17
Data filename: Untitled.cck Page 6 of 7