HomeMy WebLinkAboutCOMCHECK - 16-00399 - CFT Retail PlazaCOMcheck Software Version 4.0.2.9
Mechanical Compliance Certificate
Project Title:
2012 IECC
Project Type:New Construction
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:
303 E MOODY ROAD
REXBURG, ID
Owner/Agent:
CFT NV. DEVELOPMENTS, INC
1683 Walnut Grove Ave.
Rosemead, CA 91770
626-8-799-9898
Designer/Contractor:
GARY WANG & ASSOCIATES, INC.
1255 Corporate Center Dr., Suite 8
Monterey Park, CA 91754
TEL: (626) 288-6898
Project Information
Energy Code:
CFT RETAIL PLAZA
On-site Renewable Energy
Additional Efficiency Package
Mechanical Systems List
Quantity System Type & Description
Heating: 2 each - Central Furnace, Gas, Capacity = 115 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency = 80.00% Et
Cooling: 2 each - Field-Assembled DX System, Capacity = 53 kBtu/h, Air-Cooled Condenser, Air Economizer
No minimum efficiency requirement applies
Fan System: Unspecified
2 RTU-110, 120 (Single Zone):
Heating: 2 each - Central Furnace, Gas, Capacity = 180 kBtu/h
Proposed Efficiency = 82.00% Et, Required Efficiency = 80.00% Et
Cooling: 2 each - Field-Assembled DX System, Capacity = 88 kBtu/h, Air-Cooled Condenser, Air Economizer
No minimum efficiency requirement applies
Fan System: Unspecified
2 RTU-100, 130 (Single Zone):
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.0.2.9 and to comply with the mandatory requirements
listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
CFT RETAIL PLAZA
JT working folder new\JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
81 ofPage
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.2.9
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2012 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CFT RETAIL PLAZA
JT working folder new\JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
82 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C403.2.4.
5
[FO9]3
Freeze protection and snow/ice
melting system sensors for future
connection to controls.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CFT RETAIL PLAZA
JT working folder new\JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
83 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.5.
1
[ME59]1
Demand control ventilation provided
for spaces >500 sq.ft. and >25
people/1000 sq.ft. occupant density
and served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
C403.2.7
[ME60]2
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
in or under a slab, verification may
need to occur during Foundation
Inspection.
Complies
Does Not
Not Observable
Not Applicable
C403.2.8
[ME61]2
HVAC piping insulation thickness.
Where piping is installed in or under a
slab, verification may need to occur
during Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
C403.2.8
[ME61]2
HVAC piping insulation thickness.
Where piping is installed in or under a
slab, verification may need to occur
during Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
C403.2.8.
1
[ME7]3
Piping Insulation exposed to weather
is protected from damage (due to sun,
moisture, wind, etc.).
Complies
Does Not
Not Observable
Not Applicable
C403.2.8
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C403.2.7
[ME10]2
Ducts and plenums sealed based on
static pressure and location.
Complies
Does Not
Not Observable
Not Applicable
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.7.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.3.1,
C403.3.1.
1
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CFT RETAIL
JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
84 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.3.1,
C403.3.1.
1
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2
[ME66]2
VAV fan motors >=7.5 hp to be driven
by variable speed drive, have a vane-
axial fan with variable pitch blades, or
have controls to limit fan motor
demand.
Complies
Does Not
Not Observable
Not Applicable
C403.2.6
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.6
Complies
Does Not
Not Observable
Not Applicable
C403.2.11
[ME71]2
Unenclosed spaces that are heated
use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CFT RETAIL PLAZA
JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
85 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
3
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
3
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CFT RETAIL PLAZA
JT working folder new\JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
86 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
3
[FI32]1
Economizers have been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C406
[FI34]1
Efficient HVAC performance, efficient
lighting system, or on-site supply of
renewable energy consistent with
what is shown the approved plans.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CFT RETAIL PLAZA
JT working folder new\JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
87 ofPage
Project Title:
Data filename:
CFT RETAIL PLAZA
JT working folder new\JT 2012, 2013\JT 2016\mix\Comcheck\1605016.cck
07/14/16Report date:
88 ofPage