HomeMy WebLinkAboutREVIEWS (7-27-16) - 16-00454 - Madison Park Apartments ClubhouseMadison Park Apartments Clubhouse
Building ReviewReview Date: 07/26/2016
Permit Number: 16-00454
Reviewed By: Quinton Owens Current Building Review Status: REVISIONS
D ESCRIPTIO N CO MMEN TS STATUS
Use classification is shown on plans as per
IBC Section 302
Shown as B occupancy only, but also has
assembly room large enough for more than
49 occupants (A occupancy). Will this be
separated or non-separated mixed use?
REVISIONS
Incidental use meets the requirements of
Table 508.2.5
1 hr fire separation between laundry room
& rest of building shall extend to roof
sheathing above (IBC 509.4.1 & 707.5.
COMPLETED
Fire barriers meet the requirements of IBC
Section 707
Washer boxes are to be fire rated or
outside of the rated wall.
COMPLETED
fireblocking and draftstopping meet the
requirements of IBC Section 717.
No details. It will be approved based on
inspection.
COMPLETED
Automatic sprinklers are provided or
exempted as per IBC Section 903.2
Not required.N/A
Occupant load is identified on plans as per
IBC Section 1004
Occupant load is not indicated on plans.
Occupant load is to be posted near main
exit or exit access door for the community
room.
REVISIONS
Exits meet the requirements of IBC Sections
1020 and 1021
Add exit sign above door from community
room to waiting room.
COMPLETED
An Energy Review is provided Please submit an updated energy report.REVISIONS
Glass and Glazing meets the requirements
of IBC Chapter 24
Windows by bathroom door & laundry room
door are to be tempered (within 24" from a
door).
REVISIONS
Madison Park Apartments Clubhouse
Electrical ReviewReview Date: 06/29/2016
Permit Number: 16-00454
Reviewed By: Bret Stoddard Current Electrical Review Status: REVISIONS
D ESCRIPTIO N CO MMEN TS STATUS
Electrical: Service Electrical service calculations not in plans
submitted-available fault current calculation
and load calculation. Also nothing is noted
for AIC rating of main equipment proposed.
REVISIONS
Electrical: Wiring Method No wiring method noted on plans.REVISIONS
Electrical: Exit Signs/Emergency Lighting Reviewed for code compliance.COMPLETED
Electrical: Energy Compliance Report
Submitted
Passes code as per report by 1% interior
and 88% exterior.
COMPLETED
Madison Park Apartments Clubhouse
Plumbing ReviewReview Date: 06/29/2016
Permit Number: 16-00454
Reviewed By: Don Allen Current Plumbing Review Status: REVISIONS
D ESCRIPTIO N CO MMEN TS STATUS
Meter Size/ Wye Strainer need to know the water meter size for the
building
REVISIONS
Additional Inspector Comments:
No gas line on the print.
Madison Park Apartments Clubhouse
HVAC ReviewReview Date: 06/29/2016
Permit Number: 16-00454
Reviewed By: Don Allen Current HVAC Review Status: REVISIONS
D ESCRIPTIO N CO MMEN TS STATUS
Meter Size/ Wye Strainer need to know the water meter size for the
building
REVISIONS
Additional Inspector Comments:
No gas line on the print.
Madison Park Apartments Clubhouse
Public Works Review - Site PlanReview Date: 07/07/2016
Permit Number: 16-00454
Reviewed By: Joel Gray Current Public Works Review - Site Plan
Status: REVISIONS
D ESCRIPTIO N CO MMEN TS STATUS
Water Service only.N/A
Sewer Service only.N/A
Storm Storm water must be retained on-site.REVISIONS
Storm Size of french drains for roof drains.REVISIONS
Lighting No proposed site lighting. Lights for
parking lot can not be building mounted.
N/A
Plans are approved for a footing/foundation
ONLY permit?
YES