510
CPVC - COPPER - STEEL
HANGER
SIZE - SYSTEM PIPE: 3/4" thm 3"
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
`®" 203 - EX 4231, EX 2551
FUNCTION - Support horizontal piping: 3/4" -3" CPVC.
Support horizontal piping: 3/4"-2" Steel and Copper.
Size 3/4" - 2" provides listed vertical/lateral restraint and prevents upward
movement of pipe that supplies a pendent sprinkler below a ceiling.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Install on horizontal or vertical mounting surface.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC pipe - #905 screw - no pre -drill.
3/4" - 2" Steel and Copper pipe - 1/4"x 11/2" lag bolt - no pre -drill.
in STEEL - min. 18 GA.
3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Steel and Copper pipe - 1/4" or #14 Tek Screw.
FEATURES
• Offset edge eliminates abrasion.
• Retainer dimples secure hanger to pipe during installation.
• Required AFCON #905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
SpeoifcAFCONpmducts are exclusively designed to be compatible ONLY with other AFCONproducts including parts and f orenee, rennin, in a listed sway brace, reseainer or hangerassembly.
Be adobed thefollowingwarranty restrietioowill apply. DISCL VIER-AFCON tsill NOT wetrantagaimnhe filureofitspmducts whenusN wcontbioatioowith other products,panaorsysten¢
rut manufactured or sold by AFCON. AFCON shall NOT be liable under any cimumsmnoes wharmomr for any direct or indium, incidental or consequential damages ofany kind, including but not
limited to loss ofbusinen, or profit when non-AFCONproduets have b«n, or are used.
1/12
P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
CPVC- COPPER
•STEEL
OFFSET HANGER
SIZE - SYSTEM PIPE: 3/4" thru 3" •
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized..
LISTING/APPROVAL -
1203 - EX 4231, EX 2551
PATENT - No. 6,648,278.
FUNCTION - Support horizontal piping: 3/4" -3" CPVC or Copper.
• Support horizontal piping: 3/4" - 2" Steel.
Size 3/4" - 2" provides listed vertical/lateral restraint and prevents upward movement
of pipe that supplies a pendent sprinkler below a ceiling.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions. Listed
Install on horizontal or vertical mounting surface. 3/4'
Snap over pipe then squeeze strap back allowing pipe to slide freely. o-
When #905 threads are exposed in wood, install #906 backing nut.
FASTENERS - UL Listed per NFPA 13
WOOD - 3/4" - 3" CPVC pipe - #905 screw- no pre -drill.
3/4" - 2" Copper pipe - #905 screw- no pre -drill.
3/4" - 2" Steel pipe - 1/4"x1 1/2" lag screw - no pre -drill.
Thru 5/8" gypsum board - 1/4" x T' lag screw.
STEEL - min. 18 GA. - 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or 914 Tek Screw.
3/4" - 2" Steel pipe - 1/4" or #14 Tek Screw.
CONCRETE: Required minimum load each fastener= 5(wt)+250lbs.
2
FEATURES
* 1 1/2" Offset - loose fit allows pipe to slide.
* 3/4" and I" pipe size made with common center -line.
* Patented design for superior strength.
* Offset edge eliminates abrasion.
* AFCON#905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold separately.
!0'01
Y
o �
t v
�p�
Listed Restraint
3/4" thru 2"
SwificA£CONproducta an, exclonoaly designed to be compatible ONLY with otherAFCONpmduce, including pans W parteners, resulting in a listed sway brace, restrainer or banger assembly
ae advhed the following warranty restriction will apply. DISCLAIMER- AFCOF will NOT warrant against Um failure of da producb when used in combination with other produc¢, pans or systems
rmt manufactured or sold by AFCON. AFCONsball NOT be liable under any circumstances wh isaeuer for any direct or indirect, incidental oraonsequential damages ofany kind, including hot not
IiniitM m loss of business orprofit, when nun-AFCONpmduces have bxn, or arc mM
10/08
P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
511
CPVC - COPPER
SIDE MOUNT HANGER
SIZE - SYSTEM PIPE: 3/4" thru 2"
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
203 - EX 4231, EX 2551
FUNCTION - Support horizontal piping - CPVC or Copper.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Install on vertical mounting surface.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre -drill.
3/4" - 2" Copper pipe - #905 screw - no pre -drill.
in STEEL -min. 18 GA.
3/4" - 2" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* RequiredAFCON#905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
Side Yew - For
Drawings Below
Hanger -Wood Stud
So!
Hanger - Metal Stud
SpmiacAFCONpmduccs are exclusively designed to be compatible ONLY with onerAFCON products including pans and fasteners, resulting in a listed sway brace, restrainer or banger assembly.
He advised the following wamnty restriction will apply DISCLAIMER - AFCO.Y will NOT wamant against the failure ofils produce aeben used in oambinilian with other products, pelts or systems
not manufactued or sold by AFCOR. AFCON shall NOT be liable under any circnmstances whntsoever for any dirmt or itMhmp incidental or consequential damages of any kind, including but not
limited to loss oflo ssmeca or profit, when non-AFCONpmdurbs have been, or ere used.
• i
9/08
tyco
Fire Protection
Products
BLAZEMASTER
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General
Description
TYCO CPVC Pipe and Fittings pro-
duced by Tyco Fire Protection Prod-
ucts (TFPP) are designed exclusively
for use in wet pipe automatic fire
sprinkler systems. The TYCO CPVC
Pipe and Fittings are produced from
BLAZEMASTER CPVC compound
that is a specially developed thermo-
plastic compound composed of post
chlorinated polyvinyl chloride (CPVC)
resin and state of the art additives.
TYCO CPVC Pipe and Fittings are
easier to install than traditional steel
pipe systems, and at the same time,
provide superior heat resistance and
strength as compared to traditional
CPVC and PVC piping materials used
in the plumbing trade. Various adapt-
ers are available to connect CPVC
pipe to metallic piping. All female pipe
thread adapters have brass inserts for
durability. Grooved adapters connect
directly to grooved end valves and
metallic pipe, with flexible grooved end
couplings.
NOTICE
The CPVC Pipe and Fittings produced
with BLAZEMASTER CPVC compound
described herein must be installed
and maintained in compliance with
this document and with the applicable
standards of the National Fire Protec-
tion Association (NFPA), in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Sizes
3/4 Inch thru 3 Inch
Maximum Working Pressure
175 psi
Approvals
UL and C -UL Listed
FM Approved
LPCB Approved
NSF Certified
MEA Approved
City of Los Angeles
(Refer to Installation Handbook IH -1900
dated June 2008 for exact listing/approval
information.)
Manufacture Source
U.S.A.
Material
Pipe:
ASTM F442, SDR 13.5
Fittings:
ASTM F438 (Sch. 40)
ASTM F439 (Sch. 80)
ASTM F1970
Color
Orange
WorldwideI wwwtyco-fire.com
Contacts
Installation
TYCO CPVC Pipe and Fittings are to
be to be installed in accordance with
Installation Handbook IH -1900 dated
April 2016.
Page 1 of 2 APRIL 2016 TFP1915
TFP1915
Page 2 of 2
Care and Limited
Maintenance Warranty
TYCO CPVC Pipe and Fittings are to be For warranty terms and conditions, visit
maintained and serviced in accordance www.tyco-fire.com
with this section.
Before closing a fire protection system
control valve for Inspection or main-
tenance work on the fire protection
system that it controls, permission to
shut down the affected fire protection
system must first be obtained from
the proper authorities and all person-
nel who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and de -vices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the
standards of any authority having juris-
diction. Contact the Installing contrac-
tor or product manufacturer with any
questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700
Copyright 0 2016 Tyco Fire Products, I.P. All rights reserved. i-yG.�
SLAZEMASTEA Is a trademark of The LODrizol Corporation,
FireProtection Proeructs
&D
BACKFLOW
DIRECT
ADer%uger
8aclr8owPrerention ProductLfne
4�pS51Fj�O
C UL US
17ademritersLaboratoryClassziffedRatingAFlow Q raciezisfics
The Deringer 20, 30, 40 and 50 backflow prevention valves are Sizes: 2Y2", 3 ", 4 ", 6", 8"
designed to prevent non-health/health hazard pollutants from Working Pressure: 10-175psi (0.7-12.1 bar)
entering the potable water supply system caused by Temperature Range: 33°-1407 (I °-60°C)
backpressure and/or backsiphonage conditions. Orientations: 40/50(X) 20130(H, V)
DeriugerNodels
Zoo t7amcBm / ANP) Newmiv
Deriager4a/vf'asosizoatal
Qpm) 379 757 1136 1514 1893 2271 2650 3028
30
26
a
v
m 22
N
18
14
N
10
d
6
207
193
179
165
151
138
124
110
96
83
69
55
(kPa)
0 100
200
300 400
500 600 700 800
- Rated Flow
16-
150% of Rated
Rate of Flow (gpm)
Qpm) 1136
2271
3407 4592
5678 6813 7949 9084
26
a
Q 22
0 18
J
2 14
y
10
a
6
0®0
179
165
151
137
124
110
96
82
69
55
(Va)
0 300 600 900 1200 1500 1800 2100 2400
Rate of Flow(gpm)
Backflow Direct, LLC • 3290 Monier Circle • Rancho Cordova • California • 95742 • United States of America
Phone: 916-760-4524 Website: www.backflowdirect.com
Deri ager zfl1, y % 8orisowAj
(1pm) 1514 3028 4542 60:6 757; 9085
16 110
26 14„ 95
8 12 8 83
O18 - - _ 6°(2000x) 55
N 6 41
n 4 28
N
14
LL Q - faereasing i7ow (kPa)
0 400 800 1200 1600 2000 2400
Derin�ger�0�30 Pert,s'oal Rate of Flow(gpm)
(1pm) 379 7.57 1136 1514 1893 2271 2650 3028
20
fN
16
y
0 12
J
8
LO0
m 4
a
0
138
124
110
96
83
69
55
41
28
14
(kPa)
757 1136 151.1 7893 2271 26507 3028
200 300 400
18
Rate of Flow (gpm)
124
- Rated Flow
♦ - 150% of Rated
4
(1p(11) 1514
14
♦ 2 Y2'
3., 110
10-
----
96
12
124
N
N
8„
83
10
110
8
J
69
96
n
126°
.. 83
55
10
6
J
N
4
69
41
28
Q.
O
14
inaeasing
N
n
Flow
41
(kPa)
0 100 200 300 400 500 600 700 800
28
Rated Flow ♦ - 150% of Rated
Rate of Flow (gpm)
(1pm) 1514 3028 4542 60:6 757; 9085
16 110
26 14„ 95
8 12 8 83
O18 - - _ 6°(2000x) 55
N 6 41
n 4 28
N
14
LL Q - faereasing i7ow (kPa)
0 400 800 1200 1600 2000 2400
Derin�ger�0�30 Pert,s'oal Rate of Flow(gpm)
(1pm) 379 7.57 1136 1514 1893 2271 2650 3028
20
fN
16
y
0 12
J
8
LO0
m 4
a
0
138
124
110
96
83
69
55
41
28
14
(kPa)
Backflow Direct, LLC • 3290 Monier Circle • Rancho Cordova • California • 95742 • United States of America
Phone: 916-760-4524 Website: www.backflowdirect.com
0 100
200 300 400
500 600 700 800
Rate of Flow (gpm)
- Rated Flow
♦ - 150% of Rated
(1p(11) 1514
3028 4542
6056 7571 9085
18
124
N
16
8„
110
8
14
96
n
126°
.. 83
O
10
20x130x
J
69
d
8
55
6
N
n
4
41
28
L1
2
icreaslagFlow 14
(kPa)
0 400
800 1200
1600 2000 2400
Rate of Flow(gpm)
Backflow Direct, LLC • 3290 Monier Circle • Rancho Cordova • California • 95742 • United States of America
Phone: 916-760-4524 Website: www.backflowdirect.com
FIRE
CORPORATION
DESCRIPTION AND OPERATION
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT • PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
The Globe Quick Response GL Series Sprinklers are a
low profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
pleasing appearance, it can be installed wherever standard spray
sprinklers are specified when allowed by the applicable stan-
dards. It offers the additional feature of greatly increased safe-
ty to life and is available in various styles, orifices, temperature
ratings and finishes to meet many varying design requirements.
Quick Response Sprinklers should be used advisedly and under
the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuat-
ing assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is ab-
sorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distrib-
uted in an approved pattern depending upon the deflector style
used.
QUICK RESPONSE
UPRIGHT CONVENTIONAL
QUICK RESPONSE
PENDENT VERTICAL
SIDEWALL
TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141 °C) �.
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
• Frame - bronze • Deflector - brass • Screw - brass HORIZONTAL LPCICE
• Lodgement Wire -stainless steel • Bulb seat -copper SIDEWALL HORIZONTAL
• Spring - nickel alloy • Seal - teflon SIDEWALL
• Bulb - glass with alcohol based solution, 3mm size
*SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
NOV 2016 GFS -100a (Formerly A-20)
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR
THREAD SIZE
LENGTH'
FINISHES
2.8
(40 metric)
1/2"NPT
(15mm)
21/4"
(5.7cm)
STYLE
4.2
(60 metric)
1/2"NPT
(15mm)
2 1/4"
(5.7cm)
Factory Bronze
5.6
(80 metric)
1/2"NPT
(15mm)
21/4"
(5.7cm)
Chrome
White Polyester'
8.0
(115 metric)
1/2"NPT
(15mm)
2 1/4"
(5.7cm)
Black Polyester2.3
8.0
(115 metric)
I 3/4"NPT
(20mm)
27/16'
(6.2cm)
X
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 2 9/16".
'FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED COROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6' BELOW THE CEILING.
oINSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
}PENDENT VERTICAL SIDEWALL cULus LISTED FOR V MIN. SPACING.
TUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR V MIN. SPACING.
OR ORDINARY HAZARD
LH: LIGHT HAZARD
•1/2" NPT
ORDERING INFORMATION
SIN
K
Globe agrees to repair or replace any of its own manufactured
TEMPERATURE
products found to be defective in material or workmanship for a
• Thread Size • Temperature • Finishes desired
period of one year from date of shipment.
• Quantity - Wrenches - P/N 325390 (1/2");
NYC -DOB
STYLE
Terms and Conditions of Sale (Our Price List).
HAZARD'
cULus
FM
LPC
CE
FIRE SPRINKIER CORPORATION
NOV 2016 PRINTED U.S.A. GFS -100a (Formerly A-20)
MODEL
FACTOR
MEA 101.92-E
GL2815
2.8
LH
X
X
X
X
X
X
---
---
---
X
GL4215
4.2
LH
X
X
X
X
X
X
---
---
---
X
UPRIGHT
GL5615
5.6
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8115
8.0•
LH/OH
X
X
X
X
X
X
---
---
---
X
GL8118
8.0
LH/OH
X
X
X
X
X
X
X
X
X
X
GL2801
2.8
LH
X
X
X
X
X
X
---
---
---
X
GL4201
4.2
LH
X
X
X
X
X
X
---
---
---
X
PENDENT
GL5601
5.6
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8101
8.0'
LH/OH
X
X
X
X
X
X
X
---
-
X
GL8106
8.0
LH/OH
X
X
X
X
X
X
X
X
X
X
VERTICAL
GL5632
5.6
LH
X
X
X
X
X
X
X
---
---
---
SIDEWALL'
GL8133
8.0
LH
X
X
X
X
X
X
---
---
---
---
GL2826§
2.8
LH
X
X
X
X
X
X
---
---
---
X
GL4226§
4.2
LH
X
X
X
X
X
X
---
---
-
X
HORIZONTAL
GL5626§
5.6
LH/OH
X
X
X
X
X
X
X
---
--
X
SIDEWALL
GL5627o
5.6
LH/OH
X
X
X
X
X
---
---
X
X
---
GL8127§
8.0
LH/OH
X
X
X
X
X
X
---
---
---
---
CONVENTIONAL
GL5624
5.6
LH/OH
X
X
X
X
X
--
-
X
X
---
(OLD STYLE)
GL8125
8.0
LH/OH
X
X
X
X
X
---
-
X
X
---
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6' BELOW THE CEILING.
oINSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
}PENDENT VERTICAL SIDEWALL cULus LISTED FOR V MIN. SPACING.
TUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR V MIN. SPACING.
OR ORDINARY HAZARD
LH: LIGHT HAZARD
•1/2" NPT
ORDERING INFORMATION
GLOBE° PRODUCT WARRANTY
SPECIFY
Globe agrees to repair or replace any of its own manufactured
• Quantity • Model Number • Style • Orifice
products found to be defective in material or workmanship for a
• Thread Size • Temperature • Finishes desired
period of one year from date of shipment.
• Quantity - Wrenches - P/N 325390 (1/2");
For specific details of our warranty please refer to Price List
P/N 312366 (L.O.)
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-8464-84-5082FAX 989-846
0d)BE
1-800-248-0278 www.globesprinkler.com
rxo
FIRE SPRINKIER CORPORATION
NOV 2016 PRINTED U.S.A. GFS -100a (Formerly A-20)
DESCRIPTION AND OPERATION
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODELS GL4110 & GL4910
PENDENT
RECESSED PENDENT
The Globe Model GL4110 and GL4910 Residential Sprinklers
have a low profile yet durable design which utilize a 3mm fran-
gible glass ampule as the thermosensitive element. They feature
economy, aesthetics and low flow.
The combination of the 3mm frangible glass ampule and spe-
cially designed deflector make the Model GL4110 and GL4910
Residential Sprinklers the ultimate in life safety and fire control.
These Globe Pendent and Recessed Pendent Residential Sprin-
klers have met the strict requirements of Underwriters Laboratories
Inc. as described in the UL Standard for Residential Sprinklers for
Fire Protection Service, UL 1626, and should be used accordingly.
These sprinklers should also be installed in accordance with the
appropriate NFPA Standard 13, 13D or 13R and under the direc-
tion of the approving authorities having jurisdiction.
The heart of Globe's Model GL4110 and GL4910 sprinklers
proven actuating assembly is a hermetically sealed frangible glass
ampule that contains a precisely measured amount of fluid. When
heat is absorbed, the liquid within the bulb expands increasing the
internal pressure. At the prescribed temperature the internal pres-
sure within the ampule exceeds the strength of the glass causing
the glass to shatter. This results in water discharge which is distrib-
uted in an approved pattern.
The sprinkler and escutcheon are not factory assembled.
Assembly is done in the field.
TECHNICAL DATA
•See reverse side for Approvals and Specifications.
*Temperature Rating - 155°F (680C), 175°F (79°C)
*Water Working Pressure Rating - 175 psi (12 Bars)
•Factory tested hydrostatically to 500 psi (34 Bars)
*Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame - bronze • Deflector - brass • Screw - brass
*Bulb seat - copper *Spring - nickel alloy • Seal - teflon
• Bulb - glass with alcohol based solution, 3mm size
• Escutcheon Assembly - steel
RESIDENTIAL
PENDENT
GLOBE, '
�y�raawwwreq�y���_..
RESIDENTIAL
RECESSED PENDENT
-SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
MARCH 2015 A-1 BULLETIN GL4110/GL4910, REV. #9
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODEL GL4110 & GL4910
PENDENT • RECESSED PENDENT
SPECIFICATIONS AND APPROVALS
SIN
NOMINAL
THREAD
LENGTH
FINISHES
cULus
NYC - DOB
MODEL
"K" FACTOR
SIZE
BETWEEN
155°F 17WF
MEA 101.92-E
GL4110
4.1 (58 metric)
P.S.I. (bars) G.P.M. (Umin.)
SPRINKLERS
FEET(Meters)
Factory Bronze
PENDENT
X X
12 (3.7) x 12 (3.7)
7.2 (.50) 11 (42)
1/2"NPT
21/2"
Chrome
X
X
GL4910
4.9 (68 metric)
(15mm)
(6.4cm)
While Polyester'y
X X
16 (4.9) x 16 (4.9)
11.1 (.77) 14 (53)
X X
Black Polyester'.'
7.0 (.48) 13 (49)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS**
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED.
"REFER TO PAGE 2 OF GLOBE'S RESIDENTIAL SPRINKLER INSTALLATION GUIDE (BULLETIN R.S.I.G.) FOR NFPA 130 AND 13R REQUIREMENTS.
'FOR COVERAGE AREA DIMENSIONS LESS THAN OR BETWEEN THOSE INDICATED, USE THE MINIMUM REQUIRED FLOW FOR THE NEXT HIGHEST
COVERAGE AREA FOR WHICH HYDRAULIC DESIGN CRITERIA ARE STATED.
CROSS SECTION
1/2" ADJUSTMENT RECESSED PENDENT
GdSE
FIRE SPRINKLER CORPORATION
MARCH 2015
ORDERING INFORMATION
SPECIFY
•Quantity • Model Number •Style
.Orifice eTemperature.Finishes desired
*Quantity - Wrenches - P/N 325390
*Quantity - Recessed Wrenches - P/N 325391
*Quantity - Protective Caps - P/N 327109 -CAP
(Friction Fit Recessed)
GLOBE'S PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List),
PRINTED U.S.A.
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
BULLETIN GL41I OIGL4910, REV. #9
TEMPERATURE
MAX. AREA,
MIN. DISTANCE
SIN MODEL
STYLE
OF COVERAGE'
MIN. MIN.
PRESSUREFLOW
BETWEEN
155°F 17WF
(68°C) (79°C)
LENGTH Z WIDTH
Feet (Meters)
P.S.I. (bars) G.P.M. (Umin.)
SPRINKLERS
FEET(Meters)
PENDENT
X X
12 (3.7) x 12 (3.7)
7.2 (.50) 11 (42)
X --
14 (4.3) x 14 (4.3)
8.8 (.59) 12 (45)
GL4110
RECESSED
8(2.4)
PENDENT
X X
16 (4.9) x 16 (4.9)
11.1 (.77) 14 (53)
X X
12 (3.7) x 12 (3.7)
7.0 (.48) 13 (49)
X X
14 (4.3) x 14 (4.3)
8.2 (.57) 14 (53)
PENDENT
X X
16 (4.9) x 16 (4.9)
8.2 (.57) 14 (53)
GL4910
RECESSED
PENDENT
X X
18 (5.5) x 18 (5.5)
12.0 (.83) 17 (64)
X X
20(6.1)x20(6.1)
16.7(1.15) 20(76)1
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED.
"REFER TO PAGE 2 OF GLOBE'S RESIDENTIAL SPRINKLER INSTALLATION GUIDE (BULLETIN R.S.I.G.) FOR NFPA 130 AND 13R REQUIREMENTS.
'FOR COVERAGE AREA DIMENSIONS LESS THAN OR BETWEEN THOSE INDICATED, USE THE MINIMUM REQUIRED FLOW FOR THE NEXT HIGHEST
COVERAGE AREA FOR WHICH HYDRAULIC DESIGN CRITERIA ARE STATED.
CROSS SECTION
1/2" ADJUSTMENT RECESSED PENDENT
GdSE
FIRE SPRINKLER CORPORATION
MARCH 2015
ORDERING INFORMATION
SPECIFY
•Quantity • Model Number •Style
.Orifice eTemperature.Finishes desired
*Quantity - Wrenches - P/N 325390
*Quantity - Recessed Wrenches - P/N 325391
*Quantity - Protective Caps - P/N 327109 -CAP
(Friction Fit Recessed)
GLOBE'S PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List),
PRINTED U.S.A.
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
BULLETIN GL41I OIGL4910, REV. #9
FIRE
CORPORATION
DESCRIPTION AND OPERATION
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE
HORIZONTAL SIDEWALL
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler is designed for use in special applications such as freezing
environments and conditions where sediment orforeign materials might
accumulate in ordinary horizontal pipe nipples.
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive
element. This provides sprinkler operation approximately six times
faster than ordinary sprinklers. At the ampule's rated temperature,
the sprinkler opens releasing the bulb seat, causing the inner tube
assembly to move, allowing the spring assembly to pivot alongside
the inner tube. At this time, water flows through the sprinkler and is
distributed by the deflector, in an approved discharge pattern. It can be
installed wherever standard spray sprinklers are specified but offers the
additional feature of greatly increased safety to life. Quick Response
Sprinklers should be used advisedly and under the direction of approv-
ing authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly
is a hermetically sealed frangible glass ampule that contains a precisely
measured amount of fluid. When heat is absorbed, the liquid within
the bulb expands increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule exceeds the
strength of the glass causing the glass to shatter. This results in water
discharge which is distributed in an approved pattern.
TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C)
200°F (9YC), 286°F (141°C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame - bronze • Deflector - brass • Screw - brass
• Bulb Seat - brass • Spring - nickel alloy • Seal - teflon
• Retainer - brass • Pin - stainless steel
SURFACE MOUNT
SLEEVE & SKIRT
RECESSED
• Torsion Spring - stainless steel • Orifice Insert - brass EXTENDED
• Bulb - glass with alcohol based solution, 3mm size
• 3/4"NPT or 1"NPT • Outer Tube - galvanized steel pipe
• Inner Tube -stainless steel
NOTE: Globe's wrench P/N 337014 must be used to install this sprinkler.
*SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION
AVAILABLE SPRINKLER
BULB COLOR
N.F.P.A. MAXIMUM CEILING
TEMPERATURES
TEMPERATURE
ORDINARY
135°F/155'F 57°C/68°C
ORANGE/RED
INTERMEDIATE
175°F/200°F 79°C/93`C`,
YELLOW/GREEN
HIGH
286°F 14 VC '." ,
BLUE
DEC 2016 GFS -520a (Formerly A-58)
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE HORIZONTAL SIDEWALL
SPECIFICATIONS
SIN MODEL
NOMINAL
THREAD
LENGTH
FINISHES
"K' FACTOR
SIZE
GL5641 5.6 (80 metric) 1"NPT
MIN.
Factory Bronze
GL5642 5.6 (80 metric) 314"NPT
cLILus Variable to 48"
Chrome
155°F
FM Variable to 36"
White Polyester2
GL8141 8.0 (115 metric) 1"NPT
Black Polyester'A
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'FINISHES AVAILABLE ON SPECIAL ORDER.
kULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
18PRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPAI3 AND ANY OTHER RELATED DOCUMENTS.
'HORIZONTAL SIDEWALL STYLE - FM APPROVED 155-F (68°C), 200-F (93°C), AND 286•F (141°C)
'RECESSED HORIZONTAL SIDEWALL STYLE - FM APPROVED 155•F (68°C) AND 200-F (93°C)
LH: LIGHT HAZARD: OH: ORDINARY HAZARD
CROSS SECTIONS
EXTENDED RECESSED
SLEEVE & SKIRT SURFACE MOUNT
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
GL68E
FIRE SPRINKLER CORPORATION
DEC 2016 PRINTED U.S.A.
IMPORTANT INSTALLATION DATA
Globe GL Series Dry Pendent Sprinklers should be
installed in accordance with the requirements set
forth in NFPA 13. These sprinklers are to be installed
using a pipe wrench applied to the outer tube. When
this is not possible, the proper sprinkler head wrench
may be used with extreme care for lengths up to
approximately 18". Excessive force may distort the
frame thus destroying the unit.
When Installed in a wet system extending into a
freezing area see chart on Dry Caution Sheet for
minimum exposed barrel length to prevent ice
plugs. Please refer to our Dry Caution Sheet for further
important installation data.
ORDERING INFORMATION
SPECIFY
• Quantity • Model Number • Style • Orifice • Temperature
• Finishes desired • Quantity - Wrenches - PIN 333010
Quantity Recessed Wrenches - PIN 337014
Quantity - Protective Caps - PIN 327109 -cap (Faction Fit Recessed)
Escutcheons Desired
• "A" Dimension - Distance from face of fitting to the finished
ceiling line regardless of escutcheon used.
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
GFS -520a (Formerly A-58)
DEFLECTOR
MIN.
SIN
135°F
155°F
1757
200°F
286°F
TO CEILING
STANCE
BETWEEN
STYLE
MODEL
HAZARD'
(57°C)
(68°C)
(79°C)
(93°C)
(141°C)
FM
cULus
DISTANCE
Inches (mm)
SPRINKLERS
Feet (Meters)
Horizontal
GL5641
LH
X
X
X
X
X
X
X
Sidewall
4 (102)
Recessed
GL5642
LH
X
X
X
X
X
--
X
to
6(l.8)
Horizontal12
(305)
Sidewall
GL8141
I LH/OH
X
I X
X
X
X
---
X
18PRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPAI3 AND ANY OTHER RELATED DOCUMENTS.
'HORIZONTAL SIDEWALL STYLE - FM APPROVED 155-F (68°C), 200-F (93°C), AND 286•F (141°C)
'RECESSED HORIZONTAL SIDEWALL STYLE - FM APPROVED 155•F (68°C) AND 200-F (93°C)
LH: LIGHT HAZARD: OH: ORDINARY HAZARD
CROSS SECTIONS
EXTENDED RECESSED
SLEEVE & SKIRT SURFACE MOUNT
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
GL68E
FIRE SPRINKLER CORPORATION
DEC 2016 PRINTED U.S.A.
IMPORTANT INSTALLATION DATA
Globe GL Series Dry Pendent Sprinklers should be
installed in accordance with the requirements set
forth in NFPA 13. These sprinklers are to be installed
using a pipe wrench applied to the outer tube. When
this is not possible, the proper sprinkler head wrench
may be used with extreme care for lengths up to
approximately 18". Excessive force may distort the
frame thus destroying the unit.
When Installed in a wet system extending into a
freezing area see chart on Dry Caution Sheet for
minimum exposed barrel length to prevent ice
plugs. Please refer to our Dry Caution Sheet for further
important installation data.
ORDERING INFORMATION
SPECIFY
• Quantity • Model Number • Style • Orifice • Temperature
• Finishes desired • Quantity - Wrenches - PIN 333010
Quantity Recessed Wrenches - PIN 337014
Quantity - Protective Caps - PIN 327109 -cap (Faction Fit Recessed)
Escutcheons Desired
• "A" Dimension - Distance from face of fitting to the finished
ceiling line regardless of escutcheon used.
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
GFS -520a (Formerly A-58)
Bulletin 135 Rev. M
UO
® Model F1
l
� � Residential Sprinklers for
Design Density of .05 gpmfft2
Model F1 Res Sprinklers engineered for the lowest flows
to meet the minimum design density of .05 gpm/ftz
Types:
1. F1 Res 30 Pendent
2. F1 Res 30 Recessed Pendent/F2
3. F1 Res 30 Recessed Pendent/FP
4. F1 Res 49 Pendent
5. F1 Res 49 Recessed PendenVF1
6. F1 Res 49 Recessed PendenUFP
7. F1 Res 58 Pendent
8. F1 Res 58 Recessed PendenVF1
9. F1 Res 58 Recessed Pendent/FP
10. F1 Res 76 Pendent
11. F1 Res 76 Recessed PendenVF1
12. F1 Res 76 Recessed Pendent/FP
13. F1 Res 30 CCP Pendent
14. F1 Res 49 CCP Pendent
15. F1 Res 58 CCP Pendent
16. F1 Res 76 CCP Pendent
17. F1 Res 44 HSW
18. F1 Res 44 Recessed HSW/F2
19. Ft Res 58 HSW
20. F1 Res 58 HSWX
21. KRes58 HSWX
22. F1 Res 58 HSW Recessed HSW/F2
23. F1 Res 44 SWC
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
TW
Ft Res 30, 49, 58 & 76
Recessed Pendent/F1
F1 Res 30, 49, 58 & 76
CCP Pendent
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the Model F1 Res 49
& 58 Pendent Sprinklers
US Patent No. 7,353,882 applies to Model F1 Res 44 & 58
HSW Sprinklers
US Patent No. 7,784,555 applies to Model F1 Res 44 SWC
Sprinklers
Product Description
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast
response sprinklers combining excellent durability, high sensitiv-
ity glass -bulb and low profile decorative design. The F1 Res
F1 Res 30, 49, 58 &T6
Recessed Pendent/FP
� ' P
F1 Res 44 & 58
Recessed HSW/F2
F1 Res 44
Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac-
tive when above ceiling piping cannot be used.
The 3mm glass -bulb pendent sprinklers permit the efficient use
of residential water supplies for sprinkler coverage in residential
fire protection design.
The low flow F1 Res sprinklers are specially engineered for fast
thermal response to meet the sensitive fire protection applica-
tion needs of the latest residential market standards (UL 1626
Standard). Upon fire conditions, rising heat causes a sprinkler's
heat -sensitive element, glass bulb or link to actuate, releasing the
waterway for water flow onto the deflector, evenly distributing the
discharged water to control a fire.
Technical Data:
• Thermal Sensor: Soldered Element (Link) or Nominal
3mm glass -bulb
• Sprinkler Frame : Brass Casting
• Sprinklers' Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: 1/2" NPT (R1/2)
• K -Factor: 3.0 (43.2) (Actual) - F1 Res 30 Pendent Sprinkler
4.9 (70.6) (Actual) - F1 Res 49 Pendent Sprinkler
5.8 (83.5) (Actual)- Ft Res 58 Pendent & HSW Sprinkler
7.6 (109)(Actual) - F1 Res 76 Pendent Sprinkler
4.4 (63) (Actual) - F1 Res 44 HSW Sprinkler
• Density: Minimum 0.05 gpm/ft2
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Model F1 Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*. For ceiling types:
Smooth Flat Horizontal, or beamed, or sloped, in accordance
with NFPA 13D, 13R, or 13 2013 editions. Be sure that orifice
size, temperature rating, deflector style and sprinkler type are
in accordance with the latest published standards of The Na-
tional Fire Protection Association or the approving authority
having jurisdiction.
Installation
Models F1 Res sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith, are
Escutcheon*, F1 or F2, Data:
the only recessed escutcheons to be used with Model 171 Res
sprinklers. Use of any other recessed escutcheon will void all
approvals and warranties. For installing Model F1 Res Pen-
dent sprinklers use only the Model D sprinkler Wrench; for
installing Models F1 Res Recessed Pendent, CCP & SWC
sprinklers use only the Model GFR2 sprinkler wrench; for in-
stalling Model Ft Res Recessed HSW sprinklers use only the
Model GFR2 Sprinkler Wrench. Use of wrenches other than
those specified may damage these sprinklers. Install F1 Res
44 with a ceiling to deflector distance of 4" - 12". Flow arrow
on deflector must point away from near wall and "Top" mark-
ing must face ceiling.
Type
Adjustment
"A"
o t
to
Face of fitting ceiling
e
Deflector Distance below bottom of beam
Sprinkler Length
Inch (mm)
Inch (mm)
Inch (g
Inch mm
F1
3/4(19,0)
Min. Recessed = 15/a (41.3)
/a (9.5)
13/4(44.4)
'12" NPT
R /z
2,/z4' (8.2)
Max. Recessed =%3 22.2
11/,(28.6)
1 25.4
F2
'/,(12.7)
Min. Recessed = 15/a (41.3)
3/,(9.5)
13/,(44.4)
Max. Recessed =1'/e 28.6
'/,(22.2)
1'/a 31.7
' Note: Escutcheons Fl or F2 may be used with Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler
Model F1 Res 30, 49, 58 & 76 Pendent
usr.°n
Model F1 Res 30 Recessed Pendent / F2
58 & 76 Recessed Pendent / F1
Fig. 1 Fig. 2
Technical Data: F1 Res 30 Pendent and Recessed Pendent (SIN R3511)
Thread
Nominal Orifice
Max. Pressure
Sprinkler Temp. Ratin Max. Ambient Tem .
Actual K
Sprinkler Length
°F °C °F
°C
Size
Inch mm
psi bar
Factor
Inch mm
'12" NPT
R /z
2,/z4' (8.2)
175 (12)
155 68 100
175 79
38
3.0 (43.2)
2.25(57)
Max
Ordinary Temp. Rating
Intermediate Temp. Rating
Minimum
Max, Coverage area
Spacing
Pressure
76°F/7
Top of Dnf h (m ,Ceiling
Spacing
Ft x Ft (m x i
Ft (m)
Flow Pressure
Flow Pressure
Ft (m)
GPM Umin PSI(bar).GPM
Umin PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
8(30.3) 7.0 (0,48)
8 (30,3)
(0,48)
Smooth Ceilings 11/4 to 4(31.7 to 102)
using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
10(37,8) 11(0,76)
10 (37,8)
;7.0
(0,76)
Beamed Ceilings per NFPA 13D, 13R
or 13 installed in beams 1'/4 to 13/416
8(2,4)
x 16 (4,9 x 4,9)
16(4,9)
13(49) 18.8(1,3)
13 (49)
.8 (1,3)
31.7 to 44.4 usina F2 escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
2.
Technical Data: F1 Res 49 Pendent and Recessed Pendent (SIN R3516)
Thread
Nominal Orifice
Max.
Sprinkler Max.
Actual
Sprinkler
Size
Inch (mm)
Pressure
Ten . Ratina Ambient Temp.
K
Length
°F
°C °F
°C
Pressure
Fl x Fl (m x m)
Ds! bar
Factor
Inch mm
''/2" NPT
7/16" (11)
175 (12)
155
68 100
38
4.9 (70.6)
2.25 (57)
R''/z
12(3,6)
13 (49)
175
1 79 150
66
Smooth Ceilings 11/4 to 4 (31.7 to
102) using F2 escutcheon.
For Ceiling types refer to NFPA 13, 13R or 13D
Nominal Orifice
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector
Minimum
Max. Coverage area
Max. Spacing
155°FMOC
175°F/790C
to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Fl x Fl (m x m)
Ft (m)
Flow
Pressure
'/z" NPT
1/z" (13)
GPM L/min
PSI bar
GPM L/min
PSI bar
Inch (mm)
Ft (m)
12 x 12 (3,6 x 3,6)
12(3,6)
13 (49)
7.0 (0,48)
13 (49)
7.0 (0,48)
Smooth Ceilings 11/4 to 4 (31.7 to
102) using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4.3)
13 (49)
7.0 (0,48)
13 (49)
7.0 (0,48)
1 to 4 (25.4 to 102) using Fl
escutcheon.
16(4,9)
16 x 16 (4,9 x 4,9)
16(4,9)
13 (49)
7.0 (0,48)
131
7.0 (0,48)
Beamed Ceilings per NFPA
13D, 13R or 13 installed in
8(2,4)
18x 18(5,5x 5,5)
18(5,5)
18 x 18 (5,5 x 5,5)
18(5.5)
17 (64,3)
12 (0,83)
17 (64,3)
12 (0,83)
beams 1'/4 to 13/4 (31.7 to
20 x 20 (6,1 x 6,1)
20(6.1)
44.4) using F2 escutcheon, 1
20.2 (1,4)
20 x 20(6,1 x6,1)
20(6,1)
20(75,7)
16.7(1,14)
20(75,7)
16,7(1,14)
to 13/4(25.4 to 44.4) using Fl
escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513)
Thread
Nominal Orifice
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector
Minimum
Max. Coveregearea
Max. Spacing
155°11
175°F/79°C
K Factor
Length
Ft x Ft (m x m)
Ft (m)
to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
'/z" NPT
1/z" (13)
GPM Wim
PSI bar
GPM L/min
PSI bar
Inch (mm)
Ft
12 x 12 (3,6 x 3,6)
12(3,6)
15 (57)
9.4 (0,65)
15 (57)
9.4 (0,65)
Smooth Ceilings 4 to 8 (100 to
203) using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
16(60,S)
10.6 (0,73)
16 (60,5)
10.6 (0,73)
4 to 8 (100 to 203) using F1
escutcheon.
16 x 16 (4,9 x 4,9)
16(4,9)
17 (64,3)
12.0 (0,83)
17 (64,3)
12.0 (0,83)
Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
8(2,4)
18x 18(5,5x 5,5)
18(5,5)
19(72)
15.0(1,0)
19(72)
15.0(1,0)
4'/4 to 8(108 to 203) using F2
escutcheon, 4 to 8 (100 to 203)
20 x 20 (6,1 x 6,1)
20(6.1)
22 (83,2)
20.2 (1,4)
22 (83,2)
20.2(l.4)
using F1 escutcheon
Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513)
Thread
Nominal Orifice
Max.
Sprinkler Max.
Actual
Sprinkler
Size
Inch (mm)
Pressure
Temp. RatinAmbient Temp.
K Factor
Length
°F
°C °F
°C
Pressure
Ft x Ft (m x m)
psi bar
Inch mm
'/z" NPT
1/z" (13)
175 (12)
155
68 100
38
5.8 (83.5)
2.25 (57)
R''/z
12(3,6)
16 (61)
175
79 150
66
Smooth Ceilings 1'/4 to 4 (31.7 to
102) using F2 escutcheon.
For Ceiling types refer to NFPA 13, 13R or 13D
w
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector
Minimum
Max. Coverage area
Max. Spacing
1550111 C
175°F/790C
to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
GPM L/min
PSI bar
GPM L/min
PSI bar
Inch (mm)
R(m)
12 x 12 (3,6 x 3,6)
12(3,6)
16 (61)
7.6 (0,53)
16 (61)
7.6 (0,53)
Smooth Ceilings 1'/4 to 4 (31.7 to
102) using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
16 (61)
7.6 (0,53)
16 (61)
7.6 (0,53)
1 to 4 (25.4 to 102) using F1
escutcheon.
16 x 16 (4,9 x 4,9)
16(4,9)
16 (61)
7.6 (0,53)
16 (61)
7.6 (0,53)
Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
8(2.4)
18 x 18 (5,5 x 5,5)
18(5,5)
19 (72)
10.8 (0,75)
19 (72)
10.8 (0,75)
11/4 to 13/4 (31.7 to 44.4) using
F2 escutcheon, 1 to 13/4 (25.4 to
20 x 20 (6,1 x 6,1)
20(6,1)
22 (83,3)
14.4 (1,0)
22 (83,3)
14.4 (1,0)
44.4) using F1 escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
w
Technical Data: F1 Res 76 Pendent and Recessed Pendent (SIN R7618)
Thread
Nominal Orifice
Max.
Sprinkler Max.
K
Sprinkler
[58.7,m]
Size
Inch (mm)
Pressure
Temp. Ratina Ambient Temp.
Factor
Length
°F
°C °F
•C
CEILING
si bar
"A"
FP Position
Inch mm
3/4" NPT
x'/22" (13.5)
175 (12)
155
68 100
38
7.6 (109)
2.25 (57)
R'/4
W
175
79 150
66
HEIGHT
'h (12.7)
3 5/16" OM.
6/i6 7.9 3/4 19)
135FG04E
[84. Imm]
Min. Recessed 16/,6 24
F1 RES 30,
49. 58 &
76 CCP PEND.
3 and Fig. 4 are not suitable
for installation in ceilings which have positive pressure in
the space above.
Ordinary Temp. Rating
Intermediate Temp. Rating
Max. Coverage area
Max. Spacing
1550F)WC
175°F/790C
Top of Deflector to Ceiling
Minimum
Ft x Ft (m x m)
Ft (m)
Inch (mm)
ming
Flow
Pressure
Flow GPM
Pressure
GPM Umin
PSI bar
Umin
PSI bar
Ft (m)
12 x 12 (3,6 x 3,6)
12(3,6)
21 (79,5)
7.6 (0,53)
21 (79,5)
7.6 (0,53)
Smooth Ceilings 41/4 to 8 (108
to 203) using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
21 (79,5)
7.6 (0,53)
21 (79,5)
7.6 (0,53)
4 to 8 (100 to 203) using F1
escutcheon.
16 x 16 (4,9 x 4,9)
16(4,9)
21 (79,5)
7.6 (0,53)
21 (79,5)
7.6 (0,53)
Beamed Ceilings per NFPA
13D, 13R or 13 installed in
8(2.4)
18 x 18 (5,5 x 5,5)
18(5.5)
21 (79,5)
7.6 (0,53)
21 (79,5)
7.6 (0,53)
beams 4'/4 to 8 (108 to 203) us-
ing F2 escutcheon, 4 to 8 (100
20 x 20 (6,1 x 6,1)
20(6.1)
23 (87,1)
9.2 (0,63)
23 (87,1)
9.2 (0,63)
to 203) using F1 escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
Model F1 Res 30.49.58 & 76 CCP Pendent*
* Not listed for corrosion resistance.
Model F1 Res 30, 49, 58 & 76
Recessed Pendent/FP
rr pusn-on/inreaa-on esculcneon
2 5/8" DIA. [66.7mm]
2 5/8° [56.7mm] DIA.
2 5/16' DIA.
2 5/16" DIA.
HOLE IN CEILING
[58.7,m]
C P
CUP
r
1 2112" REDUCER
CUP
\I � II/
CEILING
1 1/2" [38. imm] MAX.
"A"
FP Position
FACE OF FITTING
3
AA
1 "J
D MENSION
FAC F FTI
MAX. FACE OF FITTING
TO FACE OF CEILING
A. "B"
FP ADJUSTMENT
DIMENSION
F1 RES 49 PENDENT/FP
W
1/2(12.7) 15/16 (24)
COVER ADJUSTMENT
HEIGHT
'h (12.7)
3 5/16" OM.
6/i6 7.9 3/4 19)
135FG04E
[84. Imm]
Min. Recessed 16/,6 24
F1 RES 30,
49. 58 &
76 CCP PEND.
3 and Fig. 4 are not suitable
for installation in ceilings which have positive pressure in
the space above.
Model F1 Res 30, 49, 58 & 76
Recessed Pendent/FP
rr pusn-on/inreaa-on esculcneon
2 5/8" DIA. [66.7mm]
HOLE IN CEILING
4
2 5/16" DIA.
[58.7mm]
C P
r
i
i" N 1/2" REDUCER
\I � II/
CEILING L j
1 1/2" [38. imm] MAX.
"A"
FP Position
FACE OF FITTING
TO FACE OF CEILING
of beam
D MENSION
1/2" [I3mm] MAX.
A. "B"
FP ADJUSTMENT
F1 RES 49 PENDENT/FP
Fig. 3
Fig.
4
Note: The F1 Res 76 will use a 1"x Y4" reducer.
CCP Cover Plate Data:
FP Escutcheon Data:
Deflector Distance below bottom
Cover Adjustment CCP Height
"A"
FP Position
Deflector Distance below bottom
Inch (mm) Inch (mm)
of beam
Inch ("
of beam
Inch mm
Inch mm
1/2(12.7) 15/16 (24)
1/2 (13) - 1 (25.4)
Max. Recessed —,/,6(11)
'h (12.7)
6/i6 7.9 3/4 19)
1/2 (13) - 1 (25.4)
Min. Recessed 16/,6 24
1 25.4)
Note: Sprinklers shown in Fig.
3 and Fig. 4 are not suitable
for installation in ceilings which have positive pressure in
the space above.
4.
Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent/FP (SIN R351 1)
Thread
Nominal
Max.
CCP Assembly
Max.
K
Sprinkler
Size
Orifice
Pressure
Temp. atin
Ambient Temp.
Factor
Length
°F
°C
°F
°C
GPM in)
Inch mmpsi
bar
Ratin
Inch (mm)
1/z" NPT
(R 1/2)
21f64" (8.2)
175 (12)
135
57
100
38
3.0 (43.2)
2.25 (57)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516)
Nominal
Ordinary Temp. Rating
CCP Max.
Minimum
Max. Coverage area
Max. Spacing
155°F/68°C
Top of Deflector to Ceiling
Spacing
g
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft
Factor
Length
GPM in)
PSI bar
psi (bar)
Ratin
12 x 12 (3,6 x 3,6)
Inch (mm)
OF °C OF
°C
Smooth Ceilings "1/2 to 1 (13 to 25.4) using CCP.
12 x 12 (3,6 x 3,6)
12(3,6)
8(30.3)
7.0 (0,48)
1/2 to 1 (13 to 25.4) using FP escutcheon.
175 (12)
135 57 100
38
4.9 (70.6)
2.25 (57)
Beamed Ceilings per NFPA 13D, 13R or 13 installed in
8(2,4)
Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 112 to
1 (13 to 25.4) using CCP.
8(2,4)
16 x 16 (4,9 x 4,9)
16(4,9)
14 x 14 {4,3 x 4,3)
14(4,3)
1 i (37,8)
13.4 (0,92)
beams 1/2 to 1 (13 to 25.4) using CCP.
10.8 (0,75)
%z to 1 (13 to 25.4) using FP escutcheon.
18 x 18 (5,5 x 5,5)
18(5,5)
1/210 1 (13 to 25.4) using FP escutcheon.
13.5 (0,93)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513)
Nominal Max. CCP Assembly Max, Sprinkler
Thread Orifice Pressure Temp. RatingAmbient Tem K Length
Size Inch mm psi bar OF °C OF °C Factor Inch mm
'/2" NPT '12' (13) 175 (12) 135 57 100 38 5 8 (83.5) 2.25 (57)
R'/2)
Max. Coverage
Nominal
Ordinary Temp. Rating
CCP Max.
Minimum
Max. Coverage
Thread
Orifice
Max.
Assembly Ambient
K
Sprinkler
Size
Inch
Pressure
Temp. Temp.
Factor
Length
GPM Vmin
(mm)
psi (bar)
Ratin
12 x 12 (3,6 x 3,6)
Inch (mm)
OF °C OF
°C
Smooth Ceilings 1/2 to 1 (13 to 25.4) using
14 x 14 (4,3 x 4,3)
14(4,3)
16 (61)
%z" NPT
(R/2)
'lie" (11)
175 (12)
135 57 100
38
4.9 (70.6)
2.25 (57)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513)
Nominal Max. CCP Assembly Max, Sprinkler
Thread Orifice Pressure Temp. RatingAmbient Tem K Length
Size Inch mm psi bar OF °C OF °C Factor Inch mm
'/2" NPT '12' (13) 175 (12) 135 57 100 38 5 8 (83.5) 2.25 (57)
R'/2)
Max. Coverage
Ordinary Temp. Rating
Minimum
Max. Coverage
Max. Spacing
155°F/68°C
Top of Deflector to Ceiling
Minimum
area
Ft (n1)
Inch (mm)
Spacing
Flow
Pressure
Ft x Ft (m x m)
GPM Vmin
PSI bar
Ft (m)
12 x 12 (3,6 x 3,6)
12(3,6)
13 (49)
7.0 (0,48)
Smooth Ceilings 1/2 to 1 (13 to 25.4) using
14 x 14 (4,3 x 4,3)
14(4,3)
16 (61)
7.6 (0,53)
14 x 14 (4,3 x 4,3)
14(4,3)
13 (49)
7.0 (0,48)
CCP.
'/2 to 1 (13 to 25.4) using FP escutcheon.
16(4,9)
16 (61)
7.6 (0,53)
Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 112 to
1 (13 to 25.4) using CCP.
8(2,4)
16 x 16 (4,9 x 4,9)
16(4,9)
14 (53)
8-20.66)
Beamed Ceilings per NFPA 13D, 13R or 13
installed in beams 112 to 1 (13 to 25.4) using
8(2,4)
19 (72)
10.8 (0,75)
%z to 1 (13 to 25.4) using FP escutcheon.
18 x 18 (5,5 x 5,5)
18(5,5)
18 (68,1)
13.5 (0,93)
CCP.
112 to 1 (13 to 25.4) using FP escutcheon.
20x20(6,1x6,1)
1 20(6,1)
20(75,7)
16.7(1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513)
Nominal Max. CCP Assembly Max, Sprinkler
Thread Orifice Pressure Temp. RatingAmbient Tem K Length
Size Inch mm psi bar OF °C OF °C Factor Inch mm
'/2" NPT '12' (13) 175 (12) 135 57 100 38 5 8 (83.5) 2.25 (57)
R'/2)
Max. Coverage
Ordinary Temp. Rating
Minimum
areat
Max. Spacing
(1550 80C)
Top of Deflector to Ceiling
Spacing
Flow
Pressure
Ft x (m x m)
Ft (m)
Inch (mm)
GPM Umin
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
16 (61)
7.6 (0,53)
Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCP.
%z to 1 (13 to 25.4) using FP escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
16 (61)
7.6 (0,53)
16 x 16 (4,9 x 4,9)
16(4,9)
16 (61)
7.6 (0,53)
Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 112 to
1 (13 to 25.4) using CCP.
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
19 (72)
10.8 (0,75)
%z to 1 (13 to 25.4) using FP escutcheon.
20x20(6,1x6,1)
20(6,1)
22(83,3)
14.4(1,0)
For Ceiling types refer to NFPA 13, 13R or 13D
H
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618)
Thread
Nominal
Max.
CCP Assembly Max.
K
Sprinkler
Thread
Size
Orifice
Pressure
Mo. atin Ambient Temp.
Factor
Length
S-2n:mj
OF °C OF
°C
Factor
Inch mm
psi (bar)
Inch (mm)
Inch (mm)
3/+1" NPT
(RIM
17/32' (13.5)
175 (12)
135 57 100
150
38
66
7.6(109)
2.25 (57)
155
175
68 100
79 150
38
66
4.4(63)
2.45 (62)
Max. Coverage
Ordinary Temp.
Rating
Minimum
Max. Spacing
155'F/68°C
Top of Deflector to Ceiling
area
Ft x Ft (m x m}
Ft (m)
Inch (mm)
Spacing
(m)
Flow
Pressure
GPM Vmin
PSI(bar)Ft
12 x 12 (3,6 x 3,6)
12(3,6)
21 (79,5)
7.6 (0,53)
Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCP.
112 to 1 (13 to 25.4) using FP escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
21 (79,5)
7.6 (0,53)
16 x 16 (4,9 x 4,9)
16(4,9)
21 (79,5)
7.6 (0,53)
Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1/2
to 1 (13 to 25.4) using CCP.
8(2,4)
18 x 18 (5,5 x 5,5)
18(5.5)
22 (83,3)
8.4 (0,58)
1/210 1 (13 to 25.4) using FP escutcheon,
20 x 20 (6,1 x 6, 1)
20(6,1)
25(94,6)
10.8(0,74)
For Ceiling types refer to NFPA 13, 13R or 13D
fACF Fr f11Ti1W 7C7 ....
WALL P'VENOON
.. NOLE OM
(57-2o-1
1
1"!2" NE£UCE:?
4 rm c7
T ;PN C+JL LA,, ;rout
FiGH.T 'ICA 'NST
�SP,StrofiL€R
DYNE^;CH 0 055
,-rrca�-n
F1 RES 58 & 44 HSW/F2
Fig. 5
Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531)
• Model F1 Res 44 & 58 HSW
• Model F1 Res 44 & 58 Recessed HSW/F2
Max.
Thread
Nominal
Max.
Sprinkler
Ambient
K
Sprinkler
�.I
E,
S-2n:mj
Pressure
Temp. Rating
Temp.
Factor
Length
Inch (mm)
psi (bar)—
inch (mm)
i
C F
C
" NPT316„
(R 1/2)
F1 RES 58 & 44 HSW/F2
Fig. 5
Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531)
• Model F1 Res 44 & 58 HSW
• Model F1 Res 44 & 58 Recessed HSW/F2
1
F2 escutcheon,
1/2" (13mm) adjustment
Escutcheon, F2, Data:
T Adjustment Facto f Fiitting
Type
Inch (mm)
Inch (mm)
F2 112 (13) 3116. 11'16
(47-17.4)
Max.
Thread
Nominal
Max.
Sprinkler
Ambient
K
Sprinkler
Size
Orifice
Pressure
Temp. Rating
Temp.
Factor
Length
Inch (mm)
psi (bar)—
inch (mm)
F —F—
C F
C
" NPT316„
(R 1/2)
(10)
175 (12)
155
175
68 100
79 150
38
66
4.4(63)
2.45 (62)
1
F2 escutcheon,
1/2" (13mm) adjustment
Escutcheon, F2, Data:
T Adjustment Facto f Fiitting
Type
Inch (mm)
Inch (mm)
F2 112 (13) 3116. 11'16
(47-17.4)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing155-F/68°G
Ft (m)
Ordinary Temp. Rating
Intermediate Temp. Rating
175°F/79°C
Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (Umin)
Pressure
PSI bar
Flow
GPM Umin
Pressure
PSI bar
12 x 12 (3,6 x 3,6)
12 (3,6)
12 (45,4)
7.5 (0,52)
12 (45,4)
7.5 (0,52)
4 to 6 (100 to 152);
1/2 (13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
14 (53,0)
10.2 (0,71)
14 (53,0)
10.2 (0,71)
16 x 16 (4,9 x 4,9)
16(4,9)
16 (60,6)
13.3 (0,92)
16 (60,6)
13,3(0,92)
16 x 18 (4,9 x 5,5)
16(4,9)
18 (68,1)
16.8 (1,16)
18 (68,1)
16.8 (1,16)
18 x 18 (5,5 x 5,5)
18(5.5)
19 (72,0)
18.7 (1,29)
19 (72,0)
18.7 (1,29)
16 x 20 (4,9 x 6,1)
16(4.9)
23 (87,1)
27.4 (1,89)
23 (87,1)
27.4 (1„89)
12 x 12 (3,6 x 3,6)
12(3.6)
14 (53,0)
10.2 (0,71)
14 (53,0)
10.2 (0,71)
6 to 12 (152 to 305);
1/2 (13) recessed
using F2 escutcheon
%2 (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3)
14(4.3)
16 (60,6)
13.3 (0,92)
16 (60,6)
13.3 (0,92)
16 x 16 (4,9 x 4,9)
16(4,9)
17 (64,4)
15.0 (1,04)
17 (64,4)
15.0 (1 „04)
16 x 18 (4,9 x 5,5)
16(4,9)
20 (75,7)
20.7 (1,43)
20 (75,7)
20.7 (1,43)
16 x 20 (4,9 x 6,1)
16(4,9)
23 (87,1)
27.4 (1,89)
23 (87,1)
27.4 (1,89)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: Mes 58 HSW & HSW7F2TSIN 83533)
Escutcheon, F2, Data:
Adjustment Factawof all
Type Inch (mm) o wll
Inch (mm)
F2 '/,(13) 3/1e _iris
(4.7. 17.4)
Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum
Max. Coverage area Max. Spacing 155°F/68°C 175°FC79°C Ceiling Spacing
m
Ft x Ft (m x m) Ft (m) Flow Pressure Flow Pressure Inch ling(mmFt (in
GPM V i PSI b GPM V' PSI b
12 x 12 (3,6 x 3,6)
Nominal
Max.
Max.
Sprinkler
mrn
16 (60,6)
Sprinkler
Thread
Orifice
Pressure
Ambient
Temp. Rating
K
Length
Size
Inch
16 x 16 (4,9 x 4,9)
Temp.
Factor
Inch
21 (79,5)
mm
Psi (bac)
16 x 18 (4,9 x 5,5)
mm
'F
°C °F
°C
%z" NPT
'/2" (13)
175 (12)
155
68 100
38
5.8 (83.5)
2.45 (62)
R''/2
12 x 12 (3,6 x 3,6)
12 (3,6)
175
79 150
66
14.4 (1,0)
Adjustment Factawof all
Type Inch (mm) o wll
Inch (mm)
F2 '/,(13) 3/1e _iris
(4.7. 17.4)
Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum
Max. Coverage area Max. Spacing 155°F/68°C 175°FC79°C Ceiling Spacing
m
Ft x Ft (m x m) Ft (m) Flow Pressure Flow Pressure Inch ling(mmFt (in
GPM V i PSI b GPM V' PSI b
12 x 12 (3,6 x 3,6)
12(3,6)
n
16 (60,6)
ar
7.6 (0,53)
mrn
16 (60,6)
ar
7.6 (0,53)
14 x 14 (4,3 x 4,3)
14(4,3)
18 (68,2)
9.7 (0,69)
18 (68,2)
9.7 (0,69)
16 x 16 (4,9 x 4,9)
16(4,9)
21 (79,5)
13.2 (0,91)
21 (79,5)
13.2 (0,91)
4 to 6 (100 to 152);
1/2 (13) recessed
16 x 18 (4,9 x 5,5)
16(4,9)
25 (94,7)
18.6 (1,28)
25 (94,7)
18.6 (1,28)
using F2 escutcheon
16 x 20 (4,9 x 6,1)
16(4.9)
29 (109,8)
25.0 (1,73)
29 (109,8)
25.0 (1,73)
12 x 12 (3,6 x 3,6)
12 (3,6)
22 (83,3)
14.4 (1 10)
22 (83,3)
14.4 (1,0)
14 x 14 (4,3 x 4,3)
14(4.3)
22 (83,3)
14.4 (1,0)
22(83,3)
14.4 (1,0)
6 to 12 (152 to 305);
16 x 16 (4,9 x 4,9)
16(4,9)
26 (98,4)
20.1 (1,39)
26 (98,4)
20.1 (1,39)
%2 (13) recessed
using F2 escutcheon
16 x 18 (4,9 x 5,5)
16(4,9)
31 (117,4)
28.6 (1,97)
31 (117,4)
28.6 (1,97)
Ceiling types refer to NFPA 13, 13R or 13D
N
8(2,4)
Model F1 Res 44 SWC*
" Not listed for corrosion resistance.
Y, N- 4 d 5
]
T FN CGLL4.9 IINRL
nCYT 4L�If."T iFR1MF'LTn
Tar_hniral rata- FiRPc 44 SWr (GIN PIR111
Max. Spacing
Ft (m)
Ordinary Temp. Rating
1355°F/68°C
Cover
14
Flow
GPM L/min
Pressure
PSI bar
t
Nominal
Max.
Temp,
Ambient
" Not listed for corrosion resistance.
Y, N- 4 d 5
]
T FN CGLL4.9 IINRL
nCYT 4L�If."T iFR1MF'LTn
Tar_hniral rata- FiRPc 44 SWr (GIN PIR111
f1
_1
(C1 n%mnv]
- r.'.' • � , +. Damm]
F -I- RES ._44_ SWC
Fig. 6
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
1355°F/68°C
Cover
Max.
Flow
GPM L/min
Pressure
PSI bar
Thread
Nominal
Max.
Temp,
Ambient
K
Sprinkler
Size
Orifice
Pressure
Ratin
Temp
Factor
Length
16 x 18 (4,9 x 5,5)
Inch (mm)
psi (bar)
18.7 (1,13)
Inch (mm)
of
°C
OF
°C
%2" NPT
R'/2)
1/81,00)
175 (12)
135
57
100
38
4.4(63)
2.45 (62)
f1
_1
(C1 n%mnv]
- r.'.' • � , +. Damm]
F -I- RES ._44_ SWC
Fig. 6
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
1355°F/68°C
Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM L/min
Pressure
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
13 (49,2)
8.7 (0,60)
410 6 (100 to 152);
1/2 (13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
14 (53,0)
10.2 (0,71)
16 x 16 (4,9 x 4,9)
16(4,9)
17 (64,3)
15.0 (1,1)
16 x 18 (4,9 x 5,5)
16(4.9)
19 (71,8)
18.7 (1,13)
16 x 20 (4,9 x 6,1)
16 (4,9)'
23 (87,1)
27.4(l.89)
12 x 12 (3,6 x 3,6)
12(3.6)
14 (52,9)
10.2 (0,71)
6 to 12 (152 to 305);
'/2 (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3)
14(4,3)
15 (56,7)
11.7 (0,81)
16 x 16 (4,9 x 4,9)
16(4.9)
18 (68,1)
16.8 (1,16)
18 x 18 (4,9 x 5,5)
16(4.9)
20 (75,6)
20.7(l.43)
For Ceiling types refer to NFPA 13, 13R or 13D
NO
Technical Data: F1 Res 58 HSWX (SIN RA3533)
Max. Coverage area
Ft x Ft (m x m)
Thread
Nominal
Max.
Sprinkler
Max.
Ambient
K
Sprinkler
Sprinkler
Pressure
PS!(bar)Inch
Size
Orifice
Pressure
Temp. Rating
Temp.
Factor
Length
Identification
20 x20(6,1 x6, 1)
20(6,1)
Inch (mm)
psi (bar)
30(114)
Inch (mm)
Number (SW)
'F
oC
OF
,C
Bulb
%2" NPT
(R%2)
112" (13)
175 (12)
155
175
68
79
100
150
38
66
5.8 (83.5)
2.45 (62)
RA3533
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
155°F/Fr8°C
Intermediate Temp. Rating
175OF/79°C
Top of Deflector to
Ceiling
(mm)
Minimum
Spacing
Ft (m)
Flow
GPM in)
Pressure
PSI bar
Flow
GPM Vmin
Pressure
PS!(bar)Inch
18 x 20 (5,5 x 6,1)
18(5.5)
30 (114)
26.8 (1,85)
30 (114)
26.8 (1,85)
4 to 6 (100 to 152);
1/2 (13) recessed
using F2 escutcheon
8(2.4)
20 x20(6,1 x6, 1)
20(6,1)
30(114)
26.8(1,85)
30(114)
26.8(1,85)
16 x 22 (4,9 x 6,7)
16(4.9)
33 (125)
32.4 (2,23)
33 (125)
32.4 (2,23)
16 x 24 (4,9 x 7,3)
16(4,9)
38 (144)
42.9 (2,96)
38 (144)
42.9 (2,96)
14 x 26 (4,3 x 7,9)
14(4,3)
42 (160)
52.4 (3,75)
42 (160)
52.4 (3,75)
18 x 20 (5,5 x 6,1)
18(5,5)
35 (133)
36.4 (2,5)
35 (133)
36.4 (2,5)
6 to 12 (152 to 305);
1/2 (13) recessed
using F2 escutcheon
16 x 22 (4,9 x 6,7)
16(4.9)
38 (144)
42.9 (2,96)
38 (144)
42.9 (2,96)
16 x 24 (4,9 x 7,3)
16(4.9)
42(1 0)
52.4 (3,6)
42 (160)
52.4 (3,6)
14 x 26 (4,3 x 7,9)
14(4,3)
46 (174)
62.9 (4,34)
46 (174)
62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
FACE OF RTTING TO
WALL DIMENSION
1 11/16" MIN.
1.8mm]
2 1%4" HOLE DIA. ,
(57.2mm] 1CEILING TO
2m j3A
j3.2mm] DEFLECTOR
I - X r/2" REDUCER ----7 DIMENSION
r
15/16" DIA. 1.11 ' I
49.2mm —
j 2 27/32" DIA.
[72.2mm]
T!/RN COLLAR UNTIL
�1
TIGHT AGAINST SPRINKLER\'+
WRENCH BOSS.
�3sFcoe 1/2" (1.3mm]
ADJUSTMENT
F1 RLS 58 HSWX
Fig. 7
0
• Model F1 Res 58 HSWX (Bulb)
• Model KRes58 HSWX (Link)
Technical Data; KRes58 HSWX (RA3593)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Nominal
Max.
Max.
Flow
GPM Vmin
Sprinkler
Sprinkler
18(5,5)
Thread
Orifice
Pressure
Ambient
K
Length
Identification
26.8(1,85)
Size
Inch (mm)
psi (bar)
32.4 (2,23)
Factor
Inch (mm)
Number (SIN)
oFem
ac
14(4.3)
42 (160)
52.4 (3,75)
18 x 20 (5,5 x 6,1)
18(5.5)
35 (133)
36.4 (2,5)
Link
1/2° NPT
(R/2)
112" (13)
175 (12)
100
38
5.8 (83.5)
2.45 (62)
RA3593
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
166°Fll4°c
Top of Deflector to
Ceilingling
Inch
Minimum
Spa cin g
Ft cin
Flow
GPM Vmin
Pressure
PSI bar
18 x 20 (5,5 x 6, 1)
18(5,5)
29(109)
25(1,72)
4 to 6 (100 to 152);
'/2 (13) recessed
using F2 escutcheon
8(2.4)
20x20(6,1 x6,1)
20(6,1)
30(114)
26.8(1,85)
16 x 22 (4,9 x 7,3)
16(4,9)
33 (125)
32.4 (2,23)
16 x 24 (4,9 x 7,3)
16(4.9)
38 (144)
42.9 (2,96)
14 x 26 (4,3 x 7,9)
14(4.3)
42 (160)
52.4 (3,75)
18 x 20 (5,5 x 6,1)
18(5.5)
35 (133)
36.4 (2,5)
6 to 12 (152 to 305);
'/2 (13) Recessed
using F2 escutcheon
16 x 22 (4,9 x 6,7)
16(4,9)
38 (144)
42.9 (2,96)
16 x 24 (4,9 x 7,3)
16(4.9)
42 (160)
52.4 (3,6)
14 x 26 (4,3 x 7,9)
14(4,3)
46 (174)
62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res
44 Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D,
and 13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non -operation.
Model F1 Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft' over the listed coverage area. Listed flows
as specified by the manufacturer's technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer's installation guide-
lines and the applicable installation standard. Deflector -
to -ceiling distance listing shall be 1" to 8" maximum, only
for F1 Res 49. Sprinkler frame and deflector shall be of
bronze frame construction having a'/2" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top -loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (680C)]
[175°F (791C)]. Sprinklers shall have a nominal K -factor
of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome -
plated] [White Polyester] [Special finish- specify]. Resi-
dential pendent sprinklers shall be Reliable Model F1 Res
30, 49 & 58, SIN R3511, R3516 & R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/F1,
Model F1 Res 30, 49 & 58 Recessed Pendent/
F2, Model F1 Res 30,49 & 58 Recessed Pendent/
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's in-
stallation guidelines and the applicable installation stan-
dard. Deflector -to -ceiling distance listing shall be 1" to 8"
maximum, only for F1 Res 49. Sprinkler frame and deflec-
tor shall be of bronze frame construction having a'/2" NPT
thread. Water seal assembly shall consist of a Teflon"
coated Belleville spring washer with top -loaded extruded
"DuPont Registered Trademark
10.
or cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)j [175°F (790C)]. Sprinklers shall have a nomi-
nal K -factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze]
[Chrome -plated] [White Polyester] [Special finish- spec-
ify]. Recessed escutcheon assembly shall be a steel,
two-piece escutcheon [with '/z" adjustment (Model F2)]
[with 3/4" adjustment (Model F1)] [of push -on and thread
off design with 112" adjustment (Model FP)]. Standard fin-
ish shall be [brass][bright chrome] [white painted]. Resi-
dential recessed pendent sprinklers shall be Reliable
[Model F1 Res 30, 49 & 58 Recessed Pendent/F1 ] [Model
F1 Res 30, 49 & 58 Recessed Pendent/F2] [Model F1 Res
30, 49 & 58 Recessed Pendent/FP] SIN 83511, R3516 &
R3513 (Bulletin 135).
Model F1 Res 30, 49 & 58 CCR Pendent
(Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design den-
sity of 0.05 gpm/ft2 over the listed coverage area. Listed
flows as specified by the manufacturer's technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer's installa-
tion guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
construction having a '/z" NPT thread. Water seal as-
sembly shall consist of a Teflon* coated Belleville spring
washer with top -loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of 155°F (680C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push -on and thread -off design
allowing a'/z" cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (570C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color- specify]. ]. Concealed pendent sprinklers shall
be Reliable Model F1 Res 30, 49 & 58 CGP, SIN R3511,
R3516 & R3513 (Bulletin 135).
Model F1 Res 44, F1 Res 58 Horizontal
Sidewall, F1 Res 58 HSWX & KRes58 HSWX
Residential Sprinkler Specifications
Sprinklers shall be [cULus Listed] low flow residential
horizontal sidowall sprinklers engineered to provide a
minimum design density of 0.05 gprn/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a'/21° NPT thread.
Water seal assembly shall consist of a Teflon* coated Bel -
*DuPont Registered Trademark
leville spring washer with top -loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155QF (680C)]
[175°F (79°C)]. The solder element (Link) version, the
water seal consist of a cap with a bellville spring washer
and a temperature rating of 165*F (74°C). The recessed
assembly forthe HSWX (Bulb & Link) should be a steel
two pieces escutcheon with 1/2" adjustment (Model F2)
standard finish should be Bright Chrome and white paint-
ed. The F1 Res 58 HSW is also available with low lead
frame. F1 Res 58 HSW and HSWX sprinklers shall have a
nominal K Factor of 5.8 and F1 Res 44 a nominal K factor
of 4.4. Standard finish: [Bronze] [Chrome -plated] [White
Polyester] [Special finish- specify]. Residential horizontal
sidewall sprinklers shall be Reliable Model F1 Res 44, F1
Res 58, F1 Res 58 HSWX & Model KRes58 HSWX, SIN
R3531, RA3533 & RA3593 (Bulletin 135).
Model F1 Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 44 horizontal side-
wall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with 1/2" adjustment (Model
172). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish- specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model F1
Res 44/F2, SIN P3531 (Bulletin 135).
Model F1 Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 3/a" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of [155°F (68°C)] [175°F (790C)]
Sprinklers shall have a nominal K -factor of 7.6. Standard
finish: [Bronze] [Chrome -plated] [White Polyester] [Spe-
cial finish- specify]. Residential pendent sprinklers shall
be Reliable Model F1 Res 76, SIN R7618 (Bulletin 135).
11.
Model F1 Res 76 Recessed Penderi l ,
Model F1 Res 76 Recessed Penderil
Model F1 Res 76 Recessed Penderil
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a 3/a" NPT thread.
Water seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of [155°F (68°C)] [175°F (790C)].
Sprinklers shall have a nominal K -factor of 7.6. Standard
finish: [Bronze] [Chrome -plated] [White Polyester] [Spe-
cial finish— specify]. Recessed escutcheon assembly
shall be a steel, two-piece escutcheon [with t/2" adjust-
ment (Model F2)] [with 3/a" adjustment (Model F1)] [of
push -on and thread off design with'/2" adjustment (Mod-
el FP)]'. Standard finish shall be [brass][bright chrome]
[white painted]. Residential recessed pendent sprinklers
shall be Reliable [Model F1 Res 76 Recessed Pendent/
F11 [Model F1 Res 76 Recessed Pendent/F2] [Model F1
Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model F1 Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are t0 be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 3/4" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
'DuPont Registered Trademark
a temperature rating of 155°F (680C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push -on and thread -off design
allowing a'/2" cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (570C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color— specify]. ]. Concealed pendent sprinklers shall be
Reliable Model F1 Res 76 CCfP, SIN 87618 (Bulletin 135).
Finishes (1)
Other finishes and colors are available on special order.
Consult factory for details.
c2 cULus listed Corrosion Resistant
ll Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4, Sprinkler Finish
5. Escutcheon Finish
6. Cover Plate Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fre Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries..
Manufactured by
Reliable Automatic Sprinkler Co., Inc. AM Recycled
0 (800) 431-1588 Sales Offices Paper
liabi
118 ($00) $4$-6051 Sales Fax Revision Imes indicate updated or new data.
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U,S.A. 06/15 PIN 9999970235
Standard Finishes
Sprinkler
F1, F2, FP
Cover Plates
Escutcheons
Bronze
Brass
White Painted
Chrome Plated
Bright Chrome Plated
Chrome
White and Black
White Painted
Polyester(2) Coated
Special Application Finishes
Sprinkler
F1, F2, FP
Escutcheons
Electroless Nickel PTFE(Teflon®)«)
Electroless Nickel PTFE (Teflon®)
Bright Brass
Bright Brass
Black Plated
Black Plated
Black Paint
Black Paint
Off White
Off while
Chrome Dull
Chrome Dull
Other finishes and colors are available on special order.
Consult factory for details.
c2 cULus listed Corrosion Resistant
ll Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4, Sprinkler Finish
5. Escutcheon Finish
6. Cover Plate Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fre Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries..
Manufactured by
Reliable Automatic Sprinkler Co., Inc. AM Recycled
0 (800) 431-1588 Sales Offices Paper
liabi
118 ($00) $4$-6051 Sales Fax Revision Imes indicate updated or new data.
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U,S.A. 06/15 PIN 9999970235
tqcoFire & Building
Products
Technical Services: Tel: (800) 381-93121 Fax: (800) 791.5500
Model 513 (1
1-112 thru 61
For NFPA 13
General
Description
3) Riser M
nch (DN40
Sprinkler
The Figure 513 (13) Riser Manifolds
described in this technical data sheet
provide the necessary waterflow
alarm, pressure gauge, alarm test ori-
fice, drain, and sight glass equipment
in a single assembly for use in NFPA
13 sprinkler systems as follows:
NFPA 13`
• 1-112 Inch (DN40)
Male Thread x Female Thread
• 1-112 thru 6 Inch (DN40 thru DN150)
Groove x Groove
`Although the Riser Manifold described in
this data sheet is intended for NFPA 13
sprinkler systems, it may be used for NFPA
13D or 13R residential sprinkler systems,
where a test orifice of 5.6K (80K) is accept-
able.
The variety of sizes and grooved end
connections allow cost effective and
easy transition to check valves, control
valves, and system piping. The Riser
Manifolds may be installed in either the
horizontal (flow switch on top) or verti-
cal (flow going up) for both single
sprinkler rises and floor control in high
rises,
WARNING
The Riser Manifolds described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
anifold
thru DN150)
Systems
Technical
Data
Approvals
The Figure 513 (13) Riser Manifolds
with a cover tamper switch for the wa-
terflow alarm switch are UL Listed,
ULC Listed, and FM Approved,
The Figure 513 (13) Riser Manifolds
without a cover tamper switch for the
waterflow alarm switch are UL Listed
and FM Approved.
Maximum Working Pressure
175 psi (12,1 bar)
Test Orifice
5.6K (80K)
Assembly
The manifold body of the Figure 513 is
ductile iron, whereas the manifold
body of the Figure 13 is cast iron. The
two assemblies are completely inter-
changeable in function, application,
and end-to-end laying length.
Finish
Red painted.
Installation
The Riser Manifolds may be installed
in either the horizontal (flow switch on
top) or vertical (flow going up). The
inlet of the Riser Manifold may be di-
rectly connected to a shut-off control
valve,
NOTES
Where applicable pipe thread sealant
is to be applied sparingly. Use of a
non -hardening pipe thread sealant is
recommended.
Never remove any piping component
nor correct or modify any piping defi-
ciencies without first depressurizing
and draining the system.
Step 1. Install the manifold body with
the flow arrow pointing in the down-
stream position using threaded con-
nections and/or listed mechanical
grooved connections, as applicable
Step 2. Connect the drain line, and
then close the drain valve.
Step 3. Refer to Figure 3 for wiring
guidance. All wiring must be per-
formed in accordance with the Author-
ity Having Jurisdiction and/or the Na-
tional Electrical Code,
Step 4. Refer to Figure 4 for optional
relief valve.
Step 5. Place the system in service by
filling the system with water. When fill-
ing the system, partially open the con-
trol valve to slowly fill the system. Fill-
ing the system slowly will help avoid
damaging the waterflow alarm switch
After the system is fully pressurized,
completely open the control valve.
Step 6. Secure all supply valves
open.
Page 1 of 6 APRIL, 2006 TFP962
Page 2 of 6
NO. DESCRIPTION QTY. P/N
1 1-112" Manilold Body,
Male x Female NPT..... 1
NIA
Groove x Groove ....... 1
NIA
2 WatedbwAlarm Switch:
VSR-SF with Paddle,
UL/FM ............... 1
971-096-00
VSR-SF with Paddle and
Cover Tamper Switch,
ULCJFM .............. 1
976-519-02
3 300 psi12000 kPa
Water Pressure Gauge .. 1
2341
NOTES:
1. Approximate weight, 11.2 lbs. (5,1 kg).
2. ULC Listed Manifolds are equipped with
Cover Tamper SwRches installed internal
to the Waterflow Alarm Switches,
3. CH: Common Hardware
tacv,r 1111111
FIGURE 1
1.112 INCH (DN40) RISER MANIFOLD ASSEMBLY AND DIMENSIONS
3-112"
(88,9 mm)
TFP962
TFPS62
2 INCH (DN50) MANIFOLD
NO. DESCRIPTION QTY. PIN
1 2" Manifold Body,
Groove x Groove ....... 1 N/A
2 Waterflow Alarm Switch:
VSC with Paddle,
ULIFM ......... 1 976-357-01
VSC with Paddle and
Cover Tamper Switch,
ULC/FM .............. 1 976-520-01
3 300 psG2000 kPa
Water Pressure Gauge .. 1 2341
2.112 INCH (DN65) MANIFOLD
NO. DESCRIPTION
QTY. PIN
1 2-172" Manifold body,
Weight
Groove x Groove .......
1 NIA
2 Waterflow Alarm Switch:
D
VSC with Paddle,
I F
UUFM ...............
1 976-357-02
VSC with Paddle and
2Inch
Cover Tamper Swkch,
13
LEC/FM ..............
1 976-520-02
3 300 psV2000 kPa
13-1116
Water Pressure Gauge
.. 1 2341
3 INCH (DN80) MANIFOLD
NO. DESCRIPTION
QTY PIN
1 3" Manifold Body,
Weight
Groove x Groove .......
1 NIA
2 Waterflow Alarm Switch:
D
VSC with Paddle,
I F
UUFM ...............
1 976-357-03
VSC with Paddle and
2Inch
Cover Tamper Switch,
13
ULCIFM ..............1
976-520-03
3 300 psY2000 kPa
13-1116
Water Pressure Gauge ..
1 2341
NOTES:
1, ULC Listed Manifolds are equipped with
Cover Tamper Switches installed internal
to the Waterflow Alarm Switches.
2. CH: Common Hardware
4INCH (DN100) MANIFOLD
NO. DESCRIPTION
QTY, PIN
1 4" Manifold body,
Weight
Groove x Groove .......
1 NIA
2 Waterflow Alarm Switch:
D
VSC with Paddle,
I F
ULIFM ...............
1 976-357-04
VSC with Paddle and
2Inch
Cover Tamper Switch,
13
U LCIFM ..............
1 976-520-04
3 300 psi/2000 kPa
13-1116
Water Pressure Gauge
.. 1 2341
Page 3 of 6
6 INCH (DN150) MANIFOLD
NO. DESCRIPTION
QTY. PIN
1 6" Manifold Body,
Weight
Groove x Groove .......
1 NIA
2 Waterflow Alarm Switch:
D
VSC with Paddle,
I F
ULIFM ...............
1 976-357-05
VSC with Paddle and
2Inch
Cover Tamper Switch,
13
ULCIFM ..............
1 976-520-05
3 300 pst12000 kPa
13-1116
Water Pressure Gauge
.. 1 2341
Manifold
Nominal Installation
Dimensions in Inches and (min) Drain Size
Weight
A
B
C
D
E
I F
G H
Size
lbs. (kg)
2Inch
16-314
13
9116
5-318
6-318
13-1116
3-1121" NPT
13.5
(DN50)
(425,5)
(330,2)
(14,3)
(136,5)
(161,9)
(331,8)
(88,9)
(6,1)
2-112 Inch
17-3/16
13
1
5-314
6-718
13-314
3-112 1-114" NPT
16.8
(DN65)
(436,6)
(330,2)
(25,4)
(146,1)
(174,6)
(349,3)
(88,9)
(7,6)
3 Inch
17-3116
13
1
6
7-1/8
14-114
3-1121-114" NPT
18.7
(DN80)
436,6)
330,2)
25,4
152,4
181,0
362,0
88,9)
(8,5)
4 Inch
20-112
13
4-5116
7-9116
9-1116
16.518
4-1122" NPT
32.7
(DN100)
(520,7)
(330,2)
(109,5)
(192,1)
(230,2)
(422,3)
(114,3)
(14,8)
6Inch
20-112
13
4-5116
B-112
10
18-112
6-5182" NPT
41.6
DN150
520,7
330,2
109,5
215,9
254,0
469,9
168,3
18,9
1
Drain Valve
(Normally
Closed)
A
B
3
i
uo -114
�I Test
C D & Drain Valve V
(Normally set
E to "Drain")
H
F
FIGURE 2
2 thru 61NCH (011150 thru DN150) RISER MANIFOLD ASSEMBLY AND DIMENSIONS
Page 4 of 6
TFP962
SWITCH TERMINAL CONNECTIONS
UNINSULATED CLAMPING
SEVERED
LOOPED SECTION CAUTION: PLATE
STRIPPED
SINGLE An uninsulated section of a TERMINAL
ENDS
CONDUCTOR single conductor is not
SEPARATE
permitted to be looped around
CONDUCTORS
CLAMPING the terminal and serve as two
PLATE separate connections. The
TERMINAL wire must be severed to serve
INCOMING
as two separate connections,
thereby providing supervision
of the connection in the event
that the wire becomes
dislodged from the terminal.
OUTGOING
IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD
WATERFLOW SWITCH TYPICAL ELECTR ICA CONNECTIONS
CONTACTS .......... SPDT (Farm C)
LOCAL
END OF LINE
CONTACT RATING .... 5A 0 125 VAC SIGNAL
2.5A e 30 VDC DEVICE
RESISTOR
NC_
NO NC
NO
NOD /� NC
COM
f!/
COM
COM
CONTROL
POWER
PANEL
NO FLOW NON -SUPERVISED
STYLE BICLASS B
CONDITION CIRCUIT
SUPERVISED CIRCUIT
(SEE NOTE)
NOTE:
For supervised circuits, see "Switch Terminal Connections" above. The Waterflow Alarm
Switch has two switches, one can be used to operate a central station, proprietary or remove
signaling unit, while the other contact is used to operate a local audible or visual
annunciator.
COVER TAMPER SWITCH (ULC ASSEMBLIES ONLY)
CONTACTS ...... ... SPDT (Form C)
CONTACT RATING .... 3A C 250 VAC
5AOe 125 VAC
1 mA @ 5 VDC min.
NO % S NC
COM
CONTACTS SHOWN
WITH COVER IN PLACE
FIGURE 3
WIRING GUIDANCE
TFP962 Page 5 of 6
NO. DESCRIPTION QTY. PIN NO. DESCRIPTION QTY. PIN 1-112" ll opts ManifoldPess Only;
To install optional Pressure Relief Trim on
1 318" Copper Tubing, 2 Pressure Relief Valve, a 1-112" (ON40) Manifold, a 112" NPT outlet
2" (DN50) Manifolds .... 1 971-124-01 175 psi, Nonadjustable .. 1 198-066-00 must be provided by the installer on the
2-112" (DN65) and 3 90° Compression Fitting system outlet piping, and a connection back
3" (DN80) Manifolds .... 1 971-124-02 Fitting... , .... .... 2 CH to the manifold drain trim must be fabricated
4" (DN 100) and 4 1" x 112" Reducing Hex with installer supplied 318" copper tubing.
6" (DN150) Manifolds ... 1 971.124-03 Bushing .... 1 CH Discard unused trim components.
CH: Common Hardware
3 112" NPT Installer
Outlet Provided
1 3 4 System Outlet
Piping
Installer
Fabricated 2
�j 318" Copper
2 Q Tubing
3
2" (DN50), 2.1/2" (DN65), T Q
3" (DN80), 4" (DN100), or Y
6" (DN150) Manifold q P
3
Manifold
Drain Trim
1-112" (DN40)
® Manifold Li
FIGURE 4
OPTIONAL PRESSURE RELIEF VALVE
Care and
Maintenance
The following inspection procedure
must be performed as indicated, in ad-
dition to any specific requirements of
the NFPA, and any impairment must
be immediately corrected.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stalling contractor or product manufac-
turer should be contactedrelative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
NOTES
No attempt is to be made to repair any
Riser Manifold component in the field.
Only the pressure gauge, waterflow
alarm switch, or relief valve can be
replaced. if any other problems are
encountered the entire riser manifold
must be replaced.
The alarm/flow test procedure will re-
sult in operation of the associated
alarms. Consequently, notification
must be given to the owner and the fire
department, central station, or other
signal station to which the alarms are
connected, and notification must be
given to the building occupants.
Before closing a fire protection system
control valve for inspection or mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut
down the effected fire protection sys-
tem must first be obtained from the
proper authorities and all personnel
who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central sta-
tion alarms..
Alarm/Flow Test Procedure
Step 1. Place the test & drain Valve in
the "test" position.
Step 2. Fully open the drain valve.
Make certain that drainage water will
not cause any damage or injury.
Step 3. Verify operation of associated
alarms.
Step 4. Close the drain valve.
Step 5. Place the test & drain Valve in
the "drain" position.
Step 6. Verify that the residual (flow-
ing) pressure Indicated by the pres-
sure gauge is no less that originally
recorded for the system when it was
first installed.
Step 7. Close the drain valve.
Step 8. Verify that the static (not flow-
ing) pressure indicated by the pres-
sure gauge is no less that originally
recorded for the system when it was
first installed.
Page 6 of 6
TFP962
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The fnregniog warranty is made in lieu
of any and all other warranf(C,a, ex-
nress_or implied. including warranties
of merchantability and fitness for a fL
titularur}� Dose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the fullex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Information
Riser Manifold:
Specify; Size (specify), Figure 513,
(specify connection type Inlet x outlet)
Riser Manifold (specify - without or
with) a cover tamper switch for the
waterflow, alarm switch, PIN (specify).
NOTES
Orders for Figure 513 may be filled
with a Figure 13. The two assemblies
are completely interchangeable in
function, application, and end-to-end
laying length.
If a ULC Listing is required, the Riser
Manifold must be ordered with a cover
tamper switch for the waterflow alarm
switch.
UUULCIFM Assemblies
PIN 4055
With Cover Tamper Switch
1-112 Inch (DN40)
PIN 4056
MT x FT ..............
PIN 4086
1-112 Inch (DN40)
PIN 4060
MT x MT ..............
PIN 4087
2 Inch (DN50)
PIN 4061
G x G ................
PIN 4090
2.112 Inch (DN65)
PIN 4062
G x G ................
PIN 4091
3 Inch (DN80)
PIN 4065
G x G ................
PIN 4092
4 Inch (DN100)
PIN 4066
G x G ................
PIN 4095
6 Inch (DN150)
G x G ................
PIN 4096
UL/FM Assemblies
Without Cover Tamper Switch
1-112 Inch (DN40)
MT x FT ..............
PIN 4055
1-112 Inch (DN40)
MT x MT ..............
PIN 4056
2 Inch (DN50)
G x G ................
PIN 4060
2-112 Inch (DN65)
G x G ................
PIN 4061
3 Inch (DN80)
G x G ................
PIN 4062
4 Inch (DN100)
G x G ................
PIN 4065
6 Inch (DN150)
G x G ................
PIN 4066
Optional Pressure Relief Valve:
Specify: Operational Pressure Relief
Valve and Trim for use with (specify
size) Figure 513 or 13 Series Riser
Manifold, PIN (specify).
1.112' or 2' ............... PIN 4063
2-112" or 3' ............... PIN 4072
4" or 6' .................. PIN 4073
Replacement Parts:
Specify: (description) for use with Fig-
ure 513 or 13 Riser Manifold, PIN (Ref.
Figure 1 or 2, as applicable).
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446