HomeMy WebLinkAboutCOMCHECK - 17-00097 - 415 W 6th S - Falls Pointe Apt - 42 UnitsCOMcheck Software Version 4.0.5.1
Envelope Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Vertical Glazing / Wall Area:
Construction Site:
Rexburg, ID
Building Area
2012 IECC
Liljenquist Apartments
Rexburg, Idaho
6b
New Construction
22%
Owner/Agent: Designer/Contractor:
Dwayne Sudweeks
Engineered Systems Assoc., Inc.
1355 E. Center St.
Pocatello, ID 83201
208-233-0501
dcs@engsystems.com
Floor Area
1 -Multifamily : Nonresidential 30860
Additional Efficiency Package
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Envelope Assemblies
Assembly
Gross Area
Cavity Cont.
Proposed
Budget U -
or
R -Value R -Value
U -Factor
Factor(.)
Perimeter
Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Multifamily]
10289
38.0 0.0
0.027
0.021
Exterior Wall 1: Wood -Framed, 16" o.c., [Bldg. Use 1 - Multifamily]
5640
19.0 0.0
0.067
0.051
Window 1: Vinyl/Fiberglass Frame:Operable, Perf. Type: Energy code
908
--- ---
0.550
0.430
default, Double Pane, Clear, SHGC 0.70, [Bldg. Use 1 - Multifamily]
Door 1: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf. Type:
120
--- ---
0.800
0.770
Energy code default, Double Pane, Clear, SHGC 0.70, [Bldg. Use 1 -
Multifamily]
Door 2: Insulated Metal, Swinging, [Bldg. Use 1 - Multifamily]
24
--- ---
0.130
0.370
Exterior Wall 2: Wood -Framed, 16" o.c., [Bldg. Use 1 - Multifamily]
9716
19.0 7.5
0.043
0.051
Window 2: Vinyl/Fiberglass Frame:Operable, Perf. Type: Energy code
2273
--- ---
0.550
0.430
default, Double Pane, Clear, SHGC 0.70, [Bldg. Use 1 - Multifamily]
Floor 1: Slab -On -Grade: Unheated, Vertical 3 ft., [Bldg. Use 1 -
564
--- 10.0
0.510
0.540
Multifamily] (b)
(a) Budget U -factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Slab -On -Grade proposed and budget U -factors shown in table are F -factors.
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 1 of 9
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 2 of 9
COMcheck Software Version 4.0.5®1.
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Plan Review
�
Complies?
Comments/Assumptions
L
& Req.lD
C103.2
Plans and/or specifications provide all
❑Complies
[PRI]1
information with which compliance
❑Does Not
can be determined for the building
envelope and document where
❑Not Observable
exceptions to the standard are
❑Not Applicable
claimed.
C406
Plans, specifications, and/or
❑Complies
[PR9]1
calculations provide all information
❑Does Not
with which compliance can be
determined for the additional energy
❑Not Observable
efficiency package options.
❑Not Applicable
pp e
C402.3.1
The vertical fenestration area <= 30
❑Complies
i [PR10]1
percent of the gross above -grade wall
❑Does Not
area.
❑Not Observable
❑Not Applicable
C402.3.1
The skylight area <= 3 percent of the
❑Complies
[PR1111
gross roof area.
❑Does Not
❑Not Observable
❑Not Applicable
C402.3.2.
Skylights in office, storage,
❑Complies
2
automotive service, manufacturing,
❑Does Not
[PR15]1
non -refrigerated warehouse, retail
❑Not Observable
store, and distribution/sorting area
have a measured haze value > 90
❑Not Applicable
percent unless designed to exclude
direct sunlight.
Additional Comments/Assumptions:
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Lilienquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 3 of 9
Section
#
Footing / Foundation Inspection
Complies?
Comments/Assumptions
& Req.ID
C402.2.6
Slab edge insulation R -value.
❑Complies See the Envelope Assemblies table for values.
[FO3]2
❑Does Not
❑Not Observable
[]Not Applicable
C303.2
Slab edge insulation installed per
❑Complies
[FO412
manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
C402.2.6
Slab edge insulation depth/length.
❑Complies See the Envelope Assemblies table for values.
[FO5]z
Slab insulation extending away from
❑Does Not
building is covered by pavement or
❑Not Observable
>= 10 inches of soil.
❑Not Applicable
C403.2.8.
Exterior insulation protected against
❑Complies
1
damage, sunlight, moisture, wind,
❑Does Not
[FO611
landscaping and equipment
❑Not Observable
maintenance activities.
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 1 2 Medium Impact (Tier - - 3 Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 4 of 9
Section
o
Framing / Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C402.4.1,
The building envelope contains a
❑Complies
f C402.4.2
continuous air barrier that is sealed in
❑Does Not
[FR16]1
an approved manner and either
❑Not Observable
constructed or tested in an approved
❑Not Applicable
manner. Air barrier penetrations are
sealed in an approved manner.
C402.4.3,
Factory -built fenestration and doors
❑Complies
C402.4.4
are labeled as meeting air leakage
❑Does Not
[FR18]3
requirements.
❑Not Observable
❑Not Applicable
C402.4.7
Vestibules are installed on all building
❑Complies
[FR17]3
entrances. Doors have self-closing
❑Does Not
devices.
❑Not Observable
❑Not Applicable
C402.3.3,
Vertical fenestration U -Factor.
❑Complies See the Envelope Assemblies table for values.
C402.3.4
❑Does Not
[FR8]1
❑Not Observable
❑Not Applicable
C402.3.3
Vertical fenestration SHGC value.
❑Complies See the Envelope Assemblies table for values.
[FR10]'
❑Does Not
❑Not Observable
❑Not Applicable
' C303.1.3
Fenestration products rated in
❑Complies
[FR12]2
accordance with NFRC.
❑Does Not
i
❑Not Observable
❑Not Applicable
C303.1.3
Fenestration products are certified as
❑Complies
[FR13]1
to performance labels or certificates ❑Does Not
provided.
❑Not Observable
❑Not Applicable
11-4u z. z. i u -tactor of opaque doors associated UComplies See the Envelope Assemblies table for values.
[FR14]2 with the building thermal envelope ❑Does Not
meets requirements. ❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 1 2 !Medium Impact (Tier 2) 3 ,Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 5 of 9
Section
# Mechanical Rough -in inspection Complies? Comments/Assumptions
& Req.ID ,
C402.4.5. Stair and elevator shaft vents have ❑Complies
1 motorized dampers that automatically ❑Does Not
[ME3]3 close.
❑Not Observable
❑Not Applicable
C402.4.5. Outdoor air and exhaust systems have ❑Complies
2 motorized dampers that automatically ❑Does Not
[ME58]3 shut when not in use and meet
maximum leakage rates. Check ❑Not Observable
gravity dampers where allowed. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier Z) 3 1 Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 6 of 9
Section
Roof R -value. For some ceiling
❑Complies See the Envelope Assemblies table for values.
1
#
Insulation Inspection
Complies?
Comments/Assumptions
& Req.ID
.
❑Not Applicable
C402.4.1.
All sources of air leakage in the
❑Complies
1
building thermal envelope are sealed,
❑Does Not
[IN1]1
caulked, gasketed, weather stripped
❑Not Observable
or wrapped with moisture vapor-
❑Not Applicable
permeable wrapping material to
❑Not Applicable
C303.2
minimize air leakage.
❑Complies
C402.4.2.
Roof R -value. For some ceiling
❑Complies See the Envelope Assemblies table for values.
1
systems, verification may need to
❑Does Not
[IN2]1
occur during Framing Inspection.
❑Not Observable
❑Not Applicable
C303.2
Roof insulation installed per
❑Complies
[IN3]1
manufacturer's instructions. Blown or
❑Does Not
poured loose -fill insulation is installed
❑Not Observable
only where the roof slope is <=3 in
12.
❑Not Applicable
C303.2
Above -grade wall insulation installed
❑Complies
[IN7]1
per manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
C402.2.5
Floor insulation R -value.
❑Complies See the Envelope Assemblies table for values.
[IN8]2
❑Does Not
❑Not Observable
❑Not Applicable
C303.1
Building envelope insulation is labeled
❑Complies
[IN10]2
with R -value or insulation certificate
❑Does Not
providing R -value and other relevant
❑Not Observable
data.
❑Not Applicable
C303.2.1
Exterior insulation is protected from
❑Complies
[IN14]2
damage with a protective material.
❑Does Not
Verification for exposed foundation
❑Not Observable
insulation may need to occur during
❑Not Applicable
Foundation Inspection.
C402.2.1
Insulation intended to meet the roof
❑Complies
[IN17]3
insulation requirements cannot be
❑Does Not
installed on top of a suspended
❑Not Observable
ceiling. Mark this requirement
❑Not Applicable
compliant if insulation is installed
accordingly.
Additional Comments/Assumptions:
rl 1 High Impact (Tier l) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 7 of 9
Section
# Final Inspection Complies?
& Req.ID
C402.4.6
Weatherseals installed on all loading
❑Complies
[FI3711
dock cargo doors.
❑Does Not
❑Not Observable
❑Not Applicable
C402.4.8
Recessed luminaires in thermal
❑Complies
[FI2613
envelope to limit infiltration and be IC
❑Does Not
rated and labeled. Seal between
❑Not Observable
interior finish and luminaire housing.
❑Not Applicable
C406
Efficient HVAC performance, efficient
❑Complies
[F13411
lighting system, or on-site supply of
❑Does Not
renewable energy consistent with
what is shown the approved plans.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
Comments/Assumptions
a
1High Impact (Tier 1) 2 1 Medium Impact (Tier 2)J 3 i Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 8 of 9
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist Arch.cck Page 9 of 9
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
Rexburg, ID
Additional Efficiency Package
Unspecified
Mechanical Systems List
Quantity System Type & Description
42 HVAC System 1 (Single Zone)
2012 IECC
Liljenquist Apartments
Rexburg, Idaho
6b
New Construction
Owner/Agent: Designer/Contractor:
Dwayne Sudweeks
Engineered Systems Assoc., Inc.
1355 E. Center St.
Pocatello, ID 83201
208-233-0501
dcs@engsystems.com
Heating: 1 each - Central Furnace, Gas, Capacity = 36 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Single Package DX Unit, Capacity = 18 kBtu/h, Air -Cooled Condenser, No Economizer, Economizer exception: Low
Capacity Residential
Proposed Efficiency = 13.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 600 CFM, 0.3 motor nameplate hp
42 Water Heater 1:
Gas Storage Water Heater, Capacity: 50 gallons, Input Rating: 75 Btu/h
Proposed Efficiency: 0.80 EF, Required Efficiency: 0.53 EF
1 Water Heater 2:
Electric Storage Water Heater, Capacity: 20 gallons
No minimum efficiency requirement applies
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.0.5.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Dwaqpe
Name - Titl Signature I Date
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist mech.cck Page 1 of 9
COMcheck Software Version 4.0.5®1
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
& Req.iD
Plan Review
Complies?
t—Com—plies
— -
Comments/Assumptions
C103.2
Plans, specifications, and/or
[PR2]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the mechanical
systems and equipment and
❑Not Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
C103.2
Plans, specifications, and/or
❑Complies
[13113]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the service water
heating systems and equipment and
❑Not Applicable
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C406
Plans, specifications, and/or
❑Complies
[PR9]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the additional energy
❑Not Applicable
efficiency package options.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 j Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liijenquist mech.cck Page 2 of 9
# I Footing / Foundation inspection Complies? Comments/Assumptions
Req.ID
C403.2.4. Freeze protection and snow/ice ❑Complies
5 melting system sensors for future ❑Does Not
[Fog]3 connection to controls.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist mech.cck Page 3 of 9
Section
#
I Plumbing Rough -in inspection
Complies?
Comments/Assumptions
& Req.ID
C404.3
Temperature controls installed on
❑Complies
[PL5]3
service water heating systems (110 F
❑Does Not
for dwelling units and lavatories in
❑Not Observable
public restrooms and 90 F for other
occupancies.)
❑Not Applicable
C404.3
Temperature controls installed on
❑Complies
[PL5]3
service water heating systems (110 F
❑Does Not
for dwelling units and lavatories in
public restrooms and 90 F for other
[]Not Observable
occupancies.)
❑Not Applicable
C404.2
Heat traps installed on non -circulating
❑Complies
I: [PL4]3
storage water tanks.
❑Does Not
❑Not Observable
❑Not Applicable
eC404.2
Heat traps installed on non -circulating
❑Complies
[PL4]3
storage water tanks.
❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
Li I High Impact (Tier 1) 2 ct (Tier 2) 3 Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist mech.cck Page 4 of 9
Section
_
#Mechanical
Rough -In Inspection
I Complies?
Comments/Assumptions
& Req.ID
C403.2.3
HVAC equipment efficiency verified.
❑Complies See the mechanical systems list for values.
(ME55]2
❑Does Not
❑Not Observable
❑Not Applicable
C403.2.5.
Demand control ventilation provided
❑Complies
1
for spaces >500 sq.ft. and >25
❑Does Not
(ME591I
people/1000 scift occupant density
❑Not Observable
and served by systems with air side
❑Not Applicable
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
C403.2.7
HVAC ducts and plenums insulated.
❑Complies
[ME60]2
Where ducts or plenums are installed
[]Does Not
in or under a slab, verification may
❑Not Observable
need to occur during Foundation
Inspection.
❑Not Applicable
C403.2.8.
Piping Insulation exposed to weather
❑Complies
1
is protected from damage (due to sun,
❑Does Not
1[ME713
f❑Not
moisture, wind, etc.).
Observable
_
❑Not Applicable
C403.2.8
Thermally ineffective panel surfaces of
❑Complies
[ME41]3
sensible heating panels have
❑Does Not
insulation >= R-3.5.
❑Not Observable
❑Not Applicable
�_
403.3.1.
Total cooling capacity without
— _ -
❑Complies
a
economizers must be less than
❑Does Not
[NA]0
%varMaxKBtuPerH%.
❑Not Observable
❑Not Applicable
C403.2.7
Ducts and plenums sealed based on
❑Complies
�[ME10]2
static pressure and location.
❑Does Not
i
❑Not Observable
--- _ -_
❑Not Applicable-
C403.2.7.
11.3
Ductwork operating >3 in. water
_--
❑Complies
column requires air leakage testing.
❑Does Not
[ME1I]3
❑Not Observable
❑Not Applicable
C408.2.2.
Air outlets and zone terminal devices
❑Complies
i 1
have means for air balancing.
[]Does Not
s [ME53]3
❑Not Observable
❑Not Applicable
6403.4.2
VAV fan motors >=7.5 hp to bed
❑Complies
[ME66]2
by variable speed drive, have a vane-
❑Does Not
axial fan with variable pitch blades, or
❑Not Observable
have controls to limit fan motor
demand.
❑Not Applicable
C403.4.2
VAV fan motors >=7.5 hp to be driven ❑Complies
[ME66]2
by variable speed drive, have a vane-
❑Does Not
I
axial fan with variable pitch blades, or
❑Not Observable
have controls to limit fan motor
❑Not Applicable
demand.
IC403.4.2
VAV fan motors >=7.5 hp to be driven ❑Complies
(ME66]2
by variable speed drive, have a vane-
❑Does Not
axial fan with variable pitch blades, or
❑Not Observable
have controls to limit fan motor
❑Not Applicable
demand.
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) j 3 I Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist mech.cck Page 5 of 9
# Mechanical Rough -in Inspection
& Req.ID
Complies? Comments/Assumptions
C403.2.6 Exhaust air energy recovery on
❑Complies
(ME57]1 systems meeting Table C403.2.6
❑Does Not
❑Not Observable
❑Not Applicable
C403.2.11 Unenclosed spaces that are heated
❑Complies
JME71]2 use only radiant heat.
❑Does Not
j
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) i 2Medium Impact (Tier 2) 3 ;Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist mech.cck Page 6 of 9
Section
#
FinallnspectionComplies?
Comments/Assumptions
& Recl.ID
I
C403.2.4.
Heating and cooling to each zone is
❑Complies
j 1
controlled by a thermostat control.
❑Does Not
[FI47]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
j
system.
C403.2.4.
Thermostatic controls have a 5 °F
❑Complies
12
deadband.
❑Does Not
+[FI38]3
❑Not Observable
❑Not Applicable
C403.2.4.
Temperature controls have setpoint
❑Complies
2
overlap restrictions.
❑Does Not
I [F120]3
❑Not Observable
❑Not Applicable
C403.2.4.
Each zone equipped with setback
❑Complies
3
controls using automatic time clock or
❑Does Not
[FI39]3
programmable control system.
❑Not Observable
❑Not Applicable
l C403.2.4.
Automatic Controls: Setback to 55°F
❑Complies
3
(heat) and 85°F (cool); 7 -day clock, 2-
❑Does Not
[F140]3
hour occupant override, 10 -hour
❑Not Observable
backup
❑Not Applicable
0403.2.4.
Systems include optimum start
❑Complies
3.3
controls.
❑Does Not
[FI41]3
❑Not Observable
❑Not Applicable
C408.2.5.
Furnished HVAC as -built drawings
❑Complies
1
submitted within 90 days of system
❑Does Not
[F17]3
acceptance.
❑Not Observable
❑Not Applicable
IC303.3,
Furnished O&M manuals for HVAC
❑Complies
C408.2.5.
13
systems within 90 days of system
❑Does Not
�[F181 3
acceptance.
❑Not Observable
❑Not Applicable
C408.2.5.
An air and/or hydronic system
❑Complies
3
balancing report is provided for HVAC
❑Does Not
JFI43I1
systems.
❑Not Observable
❑Not Applicable
;!C408.2.3.
HVAC control systems have been
❑Complies
2
tested to ensure proper operation,
❑Does Not
[FI10]1
calibration and adjustment of controls.
❑Not Observable
❑Not Applicable
C404.3
Public lavatory faucet water
❑Complies
[FI11]3
temperature <=110°F.
❑Does Not
❑Not Observable
❑Not Applicable
C404.3
Public lavatory faucet water
❑Complies
[FI11]3
temperature <=110'F.
❑Does Not
❑Not Observable
❑Not Applicable
1THigh Impact (Tier 1) 2 1Medium Impact (Tier 2) 3 ILow Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist mech.cck Page 7 of 9
Section
#
Final Inspection
Complies? Comments/Assumptions
& Req.ID
C404.5
First 8 ft of outlet piping is insulated
❑Complies
[FI45]2
❑Does Not
❑Not Observable
❑Not Applicable
C404.5
First 8 ft of outlet piping is insulated
❑Complies
[F145]2
❑Does Not
❑Not Observable
f
❑Not Applicable
C403.2.2
HVAC systems and equipment
❑Complies
[FI27]3
capacity does not exceed calculated
❑Does Not
loads.
❑Not Observable
❑Not Applicable
tC408.2.1
Commissioning plan developed by
❑Complies
[F128]1
registered design professional or
❑Does Not
approved agency.
❑Not Observable
j
❑Not Applicable
C408.2.4
Preliminary commissioning report
❑Complies
[FI29]1
completed and certified by registered
❑Does Not
design professional or approved
❑Not Observable
agency.
❑Not Applicable
I C408.2.5.
Final commissioning report due to
❑Complies
14
building owner within 90 days of
❑Does Not
[F130]1
receipt of certificate of occupancy.
❑Not Observable
❑Not Applicable
jC408.2.3.
HVAC equipment has been tested to
❑Complies
1
ensure proper operation.
❑Does Not
[FI31]1
❑Not Observable
❑Not Applicable
C406
Efficient HVAC performance, efficient
❑Complies
[FI34]1
lighting system, or on-site supply of
❑Does Not
renewable energy consistent with
❑Not Observable
what is shown the approved plans.
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 I Medium Impact (Tier 2) 13 j Low Impact (Tier 3)
Project Title: Liljenquist Apartments Report date: 03/03/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\liljenquist mech.cck Page 8 of 9
Project Title: Liljenquist Apartments Report date: 03/03/17