HomeMy WebLinkAboutLOAD SHORT FORM - 17-00182 - 733 S 2275 W - SFRwrightsoft Load Short Form Entire House High Country Heating P.O. Box 627, Rigby, ld 83442 Phone: 208-745.8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com Project• • For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Job: SF11139 Date: 3124117 By: Vince Byram ROOM NAME Area (ft') Design Cig load (Btuh) Htg AVF (cfm) Clg AVF (Cfm) Htg Clg Infiltration 2030 Outside db (°F) -6 89 Method Simplified Inside db (°F) 70 75 Construction quality Average Design TO (°F) 76 14 Fireplaces 0 Daily range - H 96 128 Inside humidity (%) 50 50 562 58 Moisture difference (gr/Ib) 62 -31 2735 575 HEATING EQUIPMENT 63 COOLING EQUIPMENT Make Goodman Mfg. 569 94 Make Goodman Mfg. 10 Trade GOODMAN 154 2180 Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX D....w.0 Nn Cond GSX130241C* AHRI ref 2002183 Coil Capf303Obx AHRI ref 4765510 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input 69000 Btuh Sensible cooling 16100 Btuh Heating output 52440 Btuh Latent cooling 6900 Btuh Temperature rise 62 OF Total cooling 23000 Btuh Actual air flow 920 cfm Actual air flow 767 cfm Air flow factor 0.028 cfm/Btuh Air flow factor 0.110 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area (ft') Htg load (Btuh) Cig load (Btuh) Htg AVF (cfm) Clg AVF (Cfm) Room1 604 12705 2030 355 224 Room2 156 4318 382 121 42 Room3 150 2242 318 63 35 Room4 250 3439 1156 96 128 Room5 242 2074 562 58 62 Room6 156 2735 575 76 63 Room? 45 569 94 16 10 Room8 154 2180 908 61 100 D....w.0 Nn Ocnn vo GV GVJJ U40 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. W'UM "I'I'I-wrightsoft' Rig hhSuiteOUniversal201717.0.10RSU20477 2017 -Mar -24 08:40:51 A GA Page 7 .s\wrightso8wareV(artchner\SF17 B9 Princeton.rup Cale House faces: E Entire House d 1877 32960 6955 920 767 Other equip loads 1780 328 Equip. @ 0.94 RSM 6846 Latent cooling 0 Tn1 Al C I A0, 1 o11An I I ro,I JY/YV VOYV UIV /O/ Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2017 -Mar -2408:40:51 wrightsoft' Right -Suite® Universal 2017 17.0.10 RSU20477 Page At&...s\wnghtsoftware\Kartchner%SF1189Princeton.rup Calc=MJ8 Housefaces: E + wrightsoft Building Analysis Date: 324189 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby. Id 83442 Phone: 208-745-8056 Fax: 208-746-0817 Email: highcouNryhtg@gmail.wm Project For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditic Location: Btu h/12 Indoor: Heating Cooling Idaho Falls, ID, US 10941 Indoor temperature (T) 70 75 Elevation: 4741 It 14.4 Design TD (°F) 76 14 Latitude: 44°N Ceilings Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Drybulb(T) -6 89 Infiltration: Duds Dailyrange (T) - 34 (H ) Method Simplified 0 Mtbulb (T) - 60 Construction quality Average 0 Wind speed (mph) 15.0 7.5 Fireplaces 0 Adjustments Heating Component Btu h/12 Btuh % of load Walls 4.9 10941 31.5 Glazing 23.7 4992 14.4 Doors 22.0 900 2.6 Ceilings 1.5 1731 5.0 Floors 4.0 4509 13.0 Infiltration 4.0 9888 28.5 Duds 0 0 Piping 0 0 Humidification 0 0 Ventilation 1780 5.1 Adjustments 0 Total 1 1 347401 100.0 Cooling Component Btuh/ftz Btuh % of load Walls 0.5 1051 14.4 Glazing 17.4 3654 50.2 Doors 5.4 219 3.0 Ceilings 0.8 957 13.1 Floors 0.1 127 1.7 Infiltration 0.4 947 13.0 Ducts 0 0 Ventilation 328 4.5 Internal gains 0 0 Blower 0 0 Adjustments 0 Total 7283 100.0 Latent Cooling Load = 0 Btuh Overall U -value = 0.064 Btuh/ft' °F Data entries checked. y�Jy wri htsoft, 2017 -Mar -2408:40:51 -1- g Right -Suite® U niversal 2017 17.0.10 RSU20477 Page ...s\wrighlsonware\Kadchner\SF1189 Princeton.rup Calc =MA House faces: E Component Constructions Job: SF71B9 wrightsoft p Date: 3124117 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208745-8056 Fax: 208-745-0817 Email: highcountryhlg@gmail.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Location: Or Indoor: Heating Cooling Idaho Falls, ID, US Loss Indoor temperature (°F) 70 75 Elevation: 4741 ft M Design TD (TF) 76 14 Latitude: 44°N BtuhN Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Dry bulb (°F) -6 89 Infiltration: n 542 Dailyrange (°F) - 34 ( H ) Method Simplified 0.47 Wetbulb(°F) - 60 Construction quality Average 0.065 Wind speed (mph) 15.0 7.5 Fireplaces 0 278 Construction descriptions Or Area Ll -value Insul R Htg HTM Loss Clg HTM Gain 0 24.3 M B 12-'F W'Fr 8MM' 6tuh BtuhN Btuh Walls 18.6 465 s 79 0.320 0 24.3 1921 18.9 Firm wall, vnl and, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int n 542 0.065 22.0 4.94 2676 0.47 257 fnsh, 2"W" wood fret, 16" o.c. stud: Frm wall, vnl ext, 3/8" wood shth, a 585 0.065 22.0 4.94 2890 0.47 278 r-22 cav ins, 1/2" gypsum board int tush, 2"x6" wood firm, 16" o.c. stud s 503 0.065 22.0 4.94 2486 0.47 239 ORO w 585 0.065 22.0 4.94 2890 0.47 278 3 all 2215 0.065 22.0 4.94 10941 0.47 1051 Partitions (none) Windows 61C: 61C; 6.67 ft head ht Doors 11 P0: Door, mtl pur core type Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 cell ins, 5/8" gypsum board int fnsh Floors 19A-30bscp: Part floor, carpel fir fnsh, r-30 ins, frm fir, 12" thkns, 1/2" gypsum board int fnsh 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet fir Man n 56 0.300 0 22.8 1284 10.3 579 n 50 0.320 0 24.3 1216 10.6 528 s 25 0.300 0 22.8 570 18.6 465 s 79 0.320 0 24.3 1921 18.9 1491 all 210 0.320 0 23.7 4992 14.6 3063 5 41 0.290 10.5 22.0 900 5.37 219 1139 0.020 50.0 1.52 1731 0.84 957 319 0.034 30.0 2.17 692 ORO 127 138 0.355 10.0 27.0 3723 0 0 3 0.355 10.0 27.0 94 0 0 all 141 0.355 10.0 27.0 3817 0 0 2017 -Mar -2408:40:51 +� WrightSOft' Right -Suite® U niversal 201717.0.10 RSU20477 Pagel ..s\wrightsoflware\Kartchner\SFl IB9Princelon.rup Calc=MJ8 Housefaces: E Project Summar Job: SF11B9 wrightsoft y Date: 3/24117 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email: highcounlryhlg@gmail.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Design Make Goodman Mfg. Trade GOODMAN Weather: Idaho Falls, ID, US Trade GOODMAN, JANITROL, AMANA DISTI... Winter Design Conditions Summer Design Conditions Cord GSX130241C' Outside db -6 OF Outside db 89 OF Inside db 70 OF Inside db 75 OF Design TD 76 OF Design TD 14 OF Heating input 69000 Daily range H 16100 Btuh Heating output 52440 Relative humidity 50 % Temperature rise 62 Moisture difference -31 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 32960 Btuh Structure 6955 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent (25 cfm) 1780 Btuh Central vent (25 cfm) 328 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 34740 Btuh Use manufacturer's data n Rate/swing multiplier 0.94 Infiltration Equipment sensible load 6846 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure -1316 Btuh Ducts 0 Btuh Heating Cooling Central vent (25 cfm) -456 Btuh Area (ftp 1877 1877 Equipment latent load 0 Btuh Volume (ft) 16893 16893 Air changes/hour 0.50 0.26 Equipment total load 6846 Btuh Equiv. AVF (cfm) 141 73 Req. total capacity at 0.70 SHR 0.8 ton Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX Cord GSX130241C' AHRI ref 2002183 Coil Capf303Obx AHRI ref 4765510 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input 69000 Btuh Sensible cooling 16100 Btuh Heating output 52440 Btuh Latent cooling 6900 Btuh Temperature rise 62 OF Total cooling 23000 Btuh Actual air flow 920 cfm Actual air flow 767 cfm Air flow factor 0.028 cfm/Btuh Air flow factor 0.110 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wri htsoft' 2017 -Mer -2408:40:51 Si Right -Suite® Universal 201717.0.10 RSU20477 Pagel ..s\wdghtsoftwareWaachner\SFll Bg Prinmton.rup Calc=MJS Housefaces: E AED Assessment Job: SF11B9 W rightsoft' Date: 3124/17 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, Itl 83442 Phone: 208-745-8056 Fax: 208-745-0817 Email. highcounlryhlg@gmail com For: Cody Puzey 3758 Yellowslones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location: Cooling Idaho Falls, ID, US 75 Elevation: 4741 ft 14 Latitude: 44°N 50 Outdoor: Heating Cooling Dry bulb (T) -6 89 Dailyrange (TF) - 34 ( H Wet bulb (T) - 60 Wind speed (mph) 15.0 7.5 K.n 0.. • � Indoor: Indoor temperature (TF) Design TD (TF) Relative humidity (%) Moisture difference (gr/Ib) Infiltration: Heating Cooling 70 75 76 14 50 50 61.5 -31.5 ,A ; i ron ai nEo „M Maximum hourly glazing load exceeds average by 44.1%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 591 Btuh (PFG - 1.3*AFG) .� Wti htSOft' 2017 -Mar -2408.40.51 �+— g Right-SuitetJ Universal 2017 17.0.10 RSU20477 Page 1 Alice._s\wrighlsoflware\Kartchner\SFllB9 Princeton rup Calc=MJ8 Housefaces:E +}+ wrightsofr Right -J® Worksheet Job: SF11B9 Entire House Date: 3124117 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-745 0817 Email: highcountryhtg@gmail.com 1 Room name Entire House Roomi 2 Exposed wall 274.0 ft 101.0 ft 3 Room height 9.0 ft d 9.0 ft head/cool 4 Room dimensions 1.0 x 604.0 0 5 Room area 1877.0 ft' 604.0 fl' Ty Construction U -value Or HTM Area (f P) Load Area (f 1') Load number (Btuh/f P -°F (Blah/fly or perimeter (ft) (at uh) or perimeter (ft) (Stuh) Heat Cool Gross WP/S Heat Cool Gross WP/S HealCool 6 Fran wall, vat ext, 3 0.065 n 4.94 0.47 648 542 2676 257 216 160 789 76 61C 0.300 n 22.80 10.28 56 0 1284 579 56 0 1284 579 61 C 0.320 n 24.32 10.56 50 0 1216 528 0 0 0 0 W Fran wall, vat ext. 3 0.065 a 4.94 0.47 585 585 2890 278 180 180 889 85 11 1� Finn wall, vat ext, 3 0.065 s 4.94 0.47 648 503 2486 239 216 170 840 81 61C 0.300 s 22.80 18.60 25 0 570 465 25 0 570 465 61C 0.320 s 24.32 18.88 79 0 1921 1491 0 0 0 0 11P0 0.290 s 22.04 5.36 41 41 900 219 21 21 463 113 W Fan wall. vat ext. 3 0.065 w 4.94 0.47 585 585 2890 278 297 297 1467 141 C 16B.50ad 0.020 - 1.52 0.84 113E 113G 1731 957 22 22 33 18 F 19A-30bscp 0.034 2.17 0.40 319 319 692 127 0 0 0 0 F 228-10cpm 0.355 26.98 0.00 760 138 3723 0 604 101 2725 0 F 228-10cpm 0.355 - 26.98 0.00 60 3 94 0 0 0 0 0 61 c) AED excursion 591 124 Envelope loss/gain 23073 6008 9061 1681 12 a) Infiltration 9888 947 3845 349 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants (A 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 32960 6955 12705 2030 Less external load 0 0 00 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 32960 6955 12705 2030 15 Duct loads 0% 0% 0 0 -0% 0% 0 0 Total Oad329 96 67671 123551 22241 Air's �etl Win) I I I OI Calculations aooroved by ACCA to meet all reauiremenls of Manual J 8th Ed. wr{ahta0it' 2017 -Mar -2408:40:51 Aft -Pp Rig ht -Su ite® U niv at sal 201717.0.10 RSU20477 Page ...s\wdghtsoftwareWaachneASF11B9Princeton.rup Calc=MJ8 Housefaces: E + wrightsoft Right -M Worksheet Entire House High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 206-745-8056 Fax: 208-745-0817 Email: highcountryhtg@gmail.cam Job: SF11139 Date: 3124/17 By: Vince Byram 1 Room name Reom2 Raom3 2 Exposed wall 37.0 ft 25.0 ft 3 Room height 9.0 It heaVcool 9.0 ft heal/cool 4 Room dimensions 12.0 x 13.0 ft 10.0 x 15.0 It 5 Room area 156.0 fl' 150.0 W T Y Construction -value. Or HTM Area fP Load Area tl' Load number (et uh/fP-°F (Bt Stut=) or perimeter (11) (Stuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6Fon wall, vat ext, 3 0.065 n 4.94 0.47 108 108 534 51 90 90 445 43 Bic 0.300 n 22.80 10.28 0 0 0 0 0 0 0 0 81 C 0.320 n 24.32 10.56 0 0 0 0 0 0 0 0 W Fon wall. vat ext. 3 0.065 a 4.94 0.47 117 117 578 58 0 0 0 0 11 Fon wall, vat ext, 3 0.065 a 4.94 0.47 108 88 436 42 0 0 0 0 Bic 0.300 3 22.80 18.60 0 0 0 0 0 0 0 0 61 C 0.320 s 24.32 18.88 0 0 0 0 0 0 0 0 11 PO 0.290 s 22.04 5.36 20 20 437 106 0 0 0 0 W Frm wall. vat ext. 3 0.065 w 4.94 0.47 0 0 0 0 135 135 887 64 C 16B-50ad 0.020 - 1.52 0.84 0 0 0 0 150 150 228 126 F 19A-30bsco 0.034 - 2.17 0.40 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 26.98 0.00 156 37 998 0 0 0 0 0 F 228-10cpm 0.355 - 26.98 0.00 0 0 0 0 0 0 0 0 6i c)AED excursion Envelope loss/gain 2982 254 1 1339 232 12 a) Infiltration 1335 128 902 86 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants ® 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) i 4318 382 i 2242 318 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 4318 382 2242 318 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 41281 3421 22631 18 3351 Alrlrequlred War) I I Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 'Pk wrigh t00ft' 2017 -Mar -2408:40:51 Rig ht -Sinless U niversal 2017 17.0.10 RSU20477 Page 2 ...sWmghlsoftwareXKartchner\SF11 B9 Princelon.rup Calc =MJB House faces: E + wrightsofr Right -JO Worksheet Job: SF11139 Entire House Date: 3/24/17 High Country Heating By: Vince Byram P.O. Box 627, Rigby, Id 83442 Phone: 208-7458056 Fax: 208-745-0817 Email: highcountryhtg@gmail.com 1 Room name Room4 Room5 2 Exposed wall 31.0 fl 14.0 ft 3 Room height 9.0 ft heat/cool 9.0 ft heallcuol 4 Roam dimensions 1.0 x 250.0 ft 1.0 x 242.0 It 5 Room area 250.0 fl2 242.0 ft' Ty Construction U -value Or I HTM I Area (ft') I Load I Area (W) Load number (Btuh/fP-'F (Btuh/fl� or perimeter (ft) (Bluh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Grass N/P/S Heal Cool 6 Frm wall, vnl ext, 3 0.065 n 4.94 0.47 0 0 0 0 126 101 499 48 61C 0.300 n 22.80 10.28 0 0 0 0 0 0 0 0 61C 0.320 n 24.32 10.56 0 0 0 0 25 0 606 264 W Finn wall, vnl ext, 3 0.065 a 4.94 0.47 0 0 0 0 0 0 0 0 11 Fran wall, vnl ext, 3 0.065 s 4.94 0.47 135 106 524 50 0 0 0 0 61C 0.300 a 22.80 18.60 0 0 0 0 0 0 0 0 61C 0.320 s 24.32 18.88 29 0 705 547 0 0 0 0 i1P0 0.290 is 22.04 5.36 0 0 0 0 0 0 0 0 W Fm wall. vnl ext. 3 0.065 w 4.94 0.47 144 144 711 68 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 250 250 380 210 242 242 368 203 F 19A-30bscp 0.034 - 2.17 0.40 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 - 26.98 0.00 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 26.98 0.00 0 0 0 0 60 3 94 0 61 c) AED exwrsion 173 -1 Envelope loss/gain 2320 1049 1568 514 12 a) Infiltration 111 107 505 48 b) Room venlilalion 0 0 0 0 13 Internal gains: Occupants (ov; 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines fi to 13) 3439 115E 2074 582 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3439 115 2074 562 15 Duct loads -0% 0% 0 00 -0% 0% 0 0 34961 -JI 20581 74 5821 1 I Aintrequv d(cfm) I I I 12E1 I I Calculations aooroved by ACCA to meet all reauirements of Manual J 8th Ed. wri htsaft' 2017 -Mar -2408:40:51 laAft 4id Right -Suite® U niversal 201717.0.10 RSU20477 Page ...swmghtsoftware\Kartchma\SF1139 Princelon.mp Calc =Wit; House faces: E + wrightsof , Right -J® Worksheet Entire House High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-7458056 Fax: 208-745-0817 Email: highwuntryhlg@gmall.com Job: SF11B9 Date: 3124117 By: Vince Byram 1 Room name Room6 Room? 2 Exposed wall 25.0 It 5.0 It 3 Room height 9.0 0 heat/cool 9.0 It heat/cool 4 5 Room dimensions Room area 12.0 x 13.0 R 156.0 ft' 9.0 x 5.0 fl 45.0 fl' Ty Construcfion Wvalue Or HTM Area (f 2) I Load I Area (f t') I Load number (Bluh/ft"F (Btuh/fl') or perimeter (H) (Bluh) or perimeter (B) (Bluh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 Fria wall, vat ext, 3 0.065 n 4.94 0.47 108 83 410 39 0 0 0 0 T 61C 0.300 n 22.8010.28 0 0 0 0 0 0 0 0 61C 0.320 n 24.32 10.58 25 0 608 264 0 0 0 0 W Frm wall. vat ext. 3 0.065 a 4.94 0.47 117 117 578 56 45 45 222 21 11 Fran wall, vat ext, 3 0.065 s 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.300 a 22.80 18.60 0 0 0 0 0 0 0 0 61C 0.320 s 24.32 18.88 0 0 0 0 0 0 0 0 11P0 0.290 s 22.04 5.36 0 0 0 0 0 0 0 0 W Fmn wall. vnl ext. 3 0.065 w 4.94 0.47 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 156 156 237 131 45 45 68 38 F 19A-30bsco 0.034 - 2.17 0.40 0 0 0 0 45 45 98 18 F 22B-10cpm 0.355 - 26.98 0.00 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 26.98 0.00 0 0 0 0 0 0 0 0 61 c) AED excursion -1 p Envelope loss/gain 18331 489 388 77 12 a) Infiltration 902 Be 180 17 b) Roomventilalion 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 1 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2735 575 569 94 Less external load 0 0 0 0 Less Banter 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2735 575 569 94 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 Tolal room load 2735 575 569 94 Air requiretl(cfm) 76 63 16 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsOfft" 2017 -Mar -2408:40:51 A561 * Right -Su IIeS Universal 2017 17.0.10 RSU20477 Page 4 ...s\wdghtsoflwareWmatchnenSF1189 Princeton.rup Cale =We House faces: E + wrightsof , Right -J® Worksheet Job: SF11B9 Entire House Date: 3/24/17 By: Vince Byram High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-7458056 Fax: 208-745-0817 Email: highcounlryhlg®gmall.com 1 Room name RoomB Room9 2 Exposed wall 14.0 ft 22.0 It 3 Room height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 11.0 x 14.0 ft 10.0 x 12.0 ft 5 Room area 154.0 fP 120.0 fP Ty Construction U -value Or HTM I Area (f P) I Load Area (f P) I Load number (Blah/fP-°F (Bi uh/f 1� or perimeter (ft) (Bluh) or perimeter (it) (Btuh) Heat Cool Groas WP/S Heat Cool Gross WP/S Heal Cool 6 F wall, vnl ext, 3 0.065 n 4.94 0.47 0 0 0 0 0 0 0 0 �C 61C 0.300 n 22.80 10.28 0 0 0 0 0 0 0 0 �G 61C 0.320 a 24.32 10.56 0 0 0 0 0 0 0 0 W Fmi wall, vnl ext, 3 0.065 a 4.94 0.47 18 18 89 9 108 108 534 51 11 wail, vnl ext, 3 0.065 a 4.94 0.47 99 74 366 35 90 65 321 31 T�Fan 61C 0.300 s 22.80 18.60 0 0 0 0 0 0 0 0 61C 0.320 s 24.32 18.88 25 0 608 472 25 0 608 472 11P0 0.290 s 22.04 5.36 0 0 0 0 0 0 0 0 W Fnn wall, vnl ext. 3 0.065 w 4.94 0.47 9 9 44 4 0 0 0 0 C 16&50ad 0.020 - 1.52 0.84 154 154 234 129 120 120 182 101 F 19A-30bscp 0.034 - 2.17 0.40 154 154 334 62 120 120 260 48 F 228-10cpm 0.355 - 26.98 0.00 0 0 0 0 0 0 0 0 F 22B-10cpm 0.355 26.98 0.00 0 0 0 0 0 0 0 0 61 c) AED excursion 149149 Envelope loss/gain i 1675 860 1 1 1905 852 12 a) Infiltration 505 48 794 78 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2180 908 2899 928 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2180 908 2699 928 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 oad aequvedl(cfm) 2181 99 1 1 Air 1 1 9001 28751 1 9021 Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed. -fk wrightBOft' 2017 -Mar -2408:40:51 Right -Suite® Universal 2017 17.0.10 RSU20477 Page 5 ... s\wnghtsoftware\KanchnenSF11 Be Princeton.rup Calc =MJ8 House faces: E 2nd Story x{/63 cfm 76 cfm �62 cfm Room6 Room3 Room5 76 cfm 163 cfm 74 cfm Room7 16 cfm 102 cfm Room4 100 cf Flhoom9 Room8 0'-64 cfm 0\64 cfm 102 cfm 100 cfm Job #: SF11 139 Performed by Vince Byram for: Cody Pozey 3758 Yellowstones Hwy Idaho Falls, Id 63401 Phone: 208-529-2116 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax 208-745-0817 highcountryhtg@gma il. com Scale: 1 : 68 Page 1 Right -Suite ® Universal 2017 17.0.10 RSU20477 2017 -Mar -24 08:42:04 ... e\Kartchner\SF11 B9 Princeton.rup Main Floor 36'-0" Job #: SF11139 Performed by Vince Byram for: Cody Puzey 3758 Vellowslones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 High Country Heating P.O. Box 627 Rigby, Id 83442 Phone: 208-745-8056 Fax. 208-745-0817 highcountryhtg@gmail. com w Scale: 1 : 68 Page 2 High 4Suite® Universal 2017 17.0.10 RSU20477 2017 -Mar -24 08.42.04 ...e\Kadchner1SF11B9 Princeton.rup WYlghtsOft DatJobe; aDuct System Summary Dae : aani 3n24/17 Entire House By: Vince Byram High Country Heating P.O. Box 627, Rigby, Id 83442 Phone: 208-745-8056 Fax: 208-7450817 Email: hlghcoun1ryhtg@gmai1.com Project Information For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 730 ft Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.424 / 0.276 in H2O 0.096 in/100ft 767 cfm Supply Branch Detail Table Name Heating External static pressure 0.70 in H2O Pressure losses 0 in H2O Available static pressure 0.70 in H2O Supply / return available pressure 0.424 / 0.276 in H2O Lowest friction rate 0.096 in/100ft Actual air flow 920 cfm Total effective length (TEL) 0.105 730 ft Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.424 / 0.276 in H2O 0.096 in/100ft 767 cfm Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mail Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Room1 h 3176 89 56 0.105 6.0 0x0 ShMt 37.0 365.0 st4A Rooms -A h 3176 89 56 0.107 6.0 0x0 ShMt 22.0 375.0 st4 Rooms -B h 3176 89 56 0.096 6.0 0X0 ShMt 55.0 385.0 st4B Rooms -c h 3176 89 56 0.110 6.0 0X0 ShMt 42.0 345.0 st4 Room2 h 720 20 7 0.180 6.0 0x0 ShMt 10.0 225.0 st5 Room2-A h 720 20 7 0.130 6.0 0x0 ShMt 15.0 310.0 st4 Room2-B h 720 20 7 0.131 6.0 0x0 ShMt 13.0 310.0 st4 Room2-c h 64 20 7 0 0 0x0 ShMt 0 0 Room2-o h 64 20 7 0 0 0x0 ShMt 0 0 Room2-E h 64 20 7 0 0 0x0 ShMt 0 0 Room3 h 2242 63 35 0.103 6.0 0x0 ShMt 36.0 375.0 st4A Roomb c 578 48 64 0.096 6.0 0x0 ShMt 47.0 395.0 st4A Room4-A c 578 48 64 0.097 6.0 0x0 ShMt 52.0 385.0 st4A Rooms C 562 58 62 0.112 6.0 0x0 ShMt 23.0 355.0 st4 Rooms h 2735 76 63 0.169 6.0 0x0 ShMt 11.0 240.0 st4 Room7 h 569 16 10 0.244 6.0 0x0 ShMt 14.0 160.0 st1 Rooms C 908 61 100 0.105 6.0 0x0 ShMt 39.0 365.0 st4 Rooms c 928 75 102 0.151 6.0 0x0 ShMt 30.0 250.0 st4 2017 -Mar -24 08:40:52 wrightsoft Right -Suite® Universal 2017 17.0.10 RSU20477 Paget ... s\wdghtsofiware\KanchnenSF11 B9 Princeton.rup Cale =MJB House faces: E Supply Trunk Detail Table Return Branch Detail Table Name Trunk Htg Clg Design Veloc Diam H x W Duct Stud/Joist Opening (in) Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st4A Peak AVF 336 275 0.096 504 9.2 8 x 12 ShtMetl st4 st4 Peak AVF 824 729 0.096 741 12.9 8 x 20 ShtMetl SO st5 Peak AVF 20 7 0.180 30 2.8 8 x 12 ShtMetl st1 st4B Peak AVF 89 56 0.096 133 5.6 8 x 12 ShtMetl st4A st1 Peak AVF 860 746 0.096 774 13.1 8 x 20 ShtMetl 10x9 Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matt Trunk rb4 0x0 61 100 126.0 0.219 317 5.0 3.25x14 10x9 SJSp rt1 rb2 0x0 76 63 126.0 0.219 242 4.5 3.25x14 10x9 SJSp rt1 rb6 0x0 74 72 149.0 0.185 233 4.6 3.25x14 10x9 SJSp rt1 rb1 0x0 475 266 206.0 0.134 501 9.8 3-3.25x14 3-10x27 SJSp rt1 rb5 0x0 159 163 288.0 0.096 515 7.0 3.25x14 10x9 SJSp rt1A rb3 0x0 75 102 0 0 324 0 3.25x14 10x9 SJSp ' 2017 -Mar -2408:4052 wrightsoft' Right -Suite® Universal 201717.0.10 RSU20477 Page 2 s\wnghlsoFlware\Kadchner\SF11 B9 Princeton.rup Cale =MJB House faces: E Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt1 Peak AVF 845 665 0.096 633 13.0 8 x 24 ShtMetl rt1A Peak AVF 159 163 0.096 244 7.0 8 x 12 ShtMetl rt1 ' 2017 -Mar -2408:4052 wrightsoft' Right -Suite® Universal 201717.0.10 RSU20477 Page 2 s\wnghlsoFlware\Kadchner\SF11 B9 Princeton.rup Cale =MJB House faces: E