�(J Compliance Certificate
Project FS3B3 "FRAHM"
Energy Code:
2012 IECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Orientation:
Unspecified
Conditioned Floor Area:
3,386 ft2
Glazing Area
23%
Climate Zone:
6 (8693 HDD)
Permit Date:
Permit Number:
60
Construction Site:
Owner/Agent:
1081 WASHINGTON BLVD
19
FOUNDERS SQUARE SUBD.
REXBURG. ID
Designer/Contractor:
KARTCHNER HOMES
LOGAN, UT
JOHN@KARTCHNERHOMES.COM
Compliance: 3.4% Better Than Code Maximum UA: 293 Your UA: 283
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Ceiling 1: Flat Ceiling or Scissor Truss
1,693
50.0
0.0
0.026
44
Main Level - Front: Wood Frame, 16" o.c.
528
22.0
0.0
0.056
24
Orientation: Front
Window 1: Vinyl/Fiberglass Frame:Double Pane with low -E
60
0.320
19
Orientation: Front
Door 1: Solid
40
0.170
7
Orientation: Front
Main Level - Right: Wood Frame, 16" o.c.
205
22.0
0.0
0.056
9
Orientation: Right side
Window 9: Vinyl/Fiberglass Frame:Double Pane with Low -E
40
0.320
13
Orientation: Right side
Main Level - Rear: Wood Frame, 16" o.c.
416
22.0
0.0
0.056
16
Orientation: Back
Window 1: Vinyl/Fiberglass Frame:Double Pane with Low -E
120
0.320
38
Orientation: Back
Door 2: Solid
15
0.150
2
Orientation: Back
Main Level - Left: Wood Frame, 16" o.c.
316
22.0
0.0
0.056
16
Orientation: Left side
Window 7: Vinyl/Fiberglass Frame:Double Pane with Low -E
38
0.320
12
Orientation: Left side
Project Title: FS3B3 "FRAHM"
Report date: 04/13/17
Data filename: C:\Users\j hoe Ilei n.MAI N\Documents\REScheck\FS3B3
- AUSTIN.rck
Page 1
of 9
Basement Wall 1: Solid Concrete or Masonry 528 0.0 15.0
0.042 21
Orientation: Front
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 8: Vinyl/Fiberglass Frame:Double Pane with Low -E 20
0.320 6
Orientation: Front
Basement Wall 2: Solid Concrete or Masonry 204 0.0 15.0
0.042 9
Orientation: Right side
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Basement Wall 3: Solid Concrete or Masonry 416 0.0 15.0
0.042 15
Orientation: Back
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 5: Vinyl/Fiberglass Frame:Double Pane with Low -E 60
0.320 19
Orientation: Back
Basement Wall 4: Solid Concrete or Masonry 316 0.0 15.0
0.042 13
Orientation: Left side
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in
REScheck Version 4.6.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name - Title Signature
Project Title: FS3133 "FRAHM" Report date: 04/13/17
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\FS3B3 - AUSTIN.rck Page 2 of 9
CREScheck Software Version 4.6.2
�J( Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
becxion Plans Verlfled Field Verified
^# •^ Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions
103.1.
Construction drawings and
fg�,
103.2
:documentation demon!
:building envelope.
�
A2
1031,
'Construction drawings and
1'documentation4�
p'i s
q,z �E, sF �Y,e,r�
" 3 r • -
403.7
energy code complianc
�N'•`
a,
;fighting and mechanical systems.
t"
.,pyx"!dwelling
.s `" x red` 3�*s
■ • • • . • '
units must demonstrate
compliance with the IECC
,Commerciali ••
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12':1 Medium Impact (Tier 2) 1 3 ILow Impact (Tier 3)
Project Title: FS3B3 "FRAHM" Report date: 04/13/17
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\FS3B3 - AUSTIN.rck Page 3 of 9
Section
#
Plans Verified
Foundation Inspection Value
Field Verified
Value
Complies?
Comments/Assumptions
& Re .ID
402.1.1
{Conditioned basement wall R- R -❑Complies
'.See the envelope assemblies
(F0411
!insulation R -value. Where interior: R- ! R-
❑Does Not table for values.
:Insulation is used, verification
may need to occur during
;❑Not Observable
I Insulation Inspection. Not
;❑Not Applicable
;required in warm -humid locations;
:in Climate Zone 3.
303.2
;Conditioned basement wall
❑Complies
[F0511
!insulation installed per
❑Does Not
;manufacturer's instructions.
[]Not Observable I
!
❑Not Applicable
402.2.8
;Conditioned basement wall It ft❑Complies
See the Envelope Assemblies
[FO611
insulation depth of burial or
UDoes Not ;table for values.
-;distance from top of wall.
❑Not Observable
❑Not Applicable
303.2.1
IA protective covering Is Installed '..
❑Complies
[FO1111
oto protect exposed exterior
❑Does Not
U� insulation and extends a
',❑Not Observable
minimum of 6 in. below grade..
;❑Not Applicable
403.8
;Snow- and ice -melting system
;❑Complies
[F01212
controls installed.❑Does
Not
,4❑Not
Observable
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2] Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: F53133 "FRAHM" Report date: 04/13/17
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\F53B3 - AUSTIN.rck Page 4 of 9
Section
#
Framing / Rough -In Inspection
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
& Re .ID
402.1.1,
;Door U -factor.
U- U-
❑complies j See the Envelope Assemblies
402.3.4
❑Does Not ;table for values.
[FRl]1
;❑Not Observable
❑Not Applicable
402.1.1,
;Glazing U -factor (area -weighted
U-_ U -❑Complies
;See the Envelope Assemblies
402.3.1,
:average).❑Does
Not ;table for values.
402.3.3,
402.3.6,
❑ Not Observable
402.5❑Not
Applicable
[FR211
:
303.1.3;U
-factors of fenestration products❑Complies
[FR411
:are determined in accordance❑Does
Not
;with the NFRC test procedure or
;taken from the default table.
❑Not Observable
❑Not Applicable
402.4.1.1
;Air barrier and thermal barrier
❑Complies
[FR2311
:installed per manufacturer's❑Does
Not
I !Instructions.❑Not
Observable
❑Not Applicable
402.4.3
(Fenestration that is not site built
:
j❑Complies
[FR20]1
pis listed and labeled as meeting❑Does
Not
IAAMA /WDMA/CSA 101/I.S.2/A440❑Not
j
W has infiltration rates per NFRC
Observable
1400 that do not exceed code❑Not
Applicable
;limits.
402.4.4"
]IC -rated recessed lighting fixtures.
I❑Complies
[FR16F2
;sealed at housing/interior finish
❑Does Not
U
;and labeled to indicate s2.0 cfm
Observable
:leakage at 75 Pa.❑Not
❑Not Applicable
403.2.1
;Supply ducts in attics are
R- R -❑Complies
[FR12]1
;insulated to >_R-8. All other ducts
R- R -❑Does
Not
,J
jin unconditioned spaces or
[]Not Observable I
outside the building envelope are
:insulated to z:R-6.
;❑Not Applicable
403.2.2
:All joints and seams of air ducts,
❑Complies
[FR13]1
:air handlers, and filter boxes are
❑Does Not
;sealed.
❑Not Observable
❑Not Applicable
403.2.3
Building cavities are not used as
❑Complies
[FR15]3
.ducts or plenums.
❑Does Not
❑Not Observable
❑Not Applicable
403.3
HVAC piping conveying fluids
R-_ R -❑Complies
[FR17]'
:above 105 OF or chilled fluids❑Does
Not
below 55 OF are Insulated to aR-
0,
13
;❑Not Observable
j❑Not Applicable
403.3.1
Protection of insulation on HVAC
-
❑Complies
[FR24]1
I piping.
❑Does Not
❑Not Observable
❑Not Applicable
403.4.2
;Hot water pipes are insulated to
R-_ R-_
;❑Complies
[FR18]2
I>R-3.
❑Does Not
❑Not Observable
j❑Not Applicable
111 High Impact (Tier 1) 12.1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: FS3B3 "FRAHM" Report date: 04/13/17
Data filename: CAUsers\jhoe Ilei n.MAI N\Documents\REScheck\FS3B3 - AUSTIN.rck Page 5 of 9
# Framing /Rough -In Inspection Value Plans Verified Value Field Verified Complies? Comments/Assumptions
403.5 :Automatic or gravity dampers are
[FR19]2 linstalled on all outdoor air
M f intakes and exhausts.
Additional Comments/Assumptions:
s Not
Observable
1 1 High Impact (Tier 1) _. Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: FS3B3 "FRAHM" Report date: 04/13/17
Data filename: C:\Users\jhoellain.MAIN\Documents\REScheck\FS3B3 - AUSTIN.rck Page 6 of 9
Section
#
Insulation Inspection
Plans Verified Field Verified
Value Value
Complies?
Comments/Assumptions
& Req.ID
303.1
'.. All installed insulation is labeled
❑Complies
[IN13]'
or the installed R-values
❑Does Not
provided.
❑Not Observable
❑Not Applicable
402.1.1,
''..Wall insulation R-value. if this isa'.
R- R-❑Complies
;See the Envelope Assemblies
402.2.5,
I mass wall with at least 1k of the
❑ Wood, ❑ Wood❑Does
Not :table for values.
402.2.6
;wall insulation on the wall
❑ Mass '., ❑ Mass❑Not
Observable
[IN311
exterior, the exterior Insulation
:requirement applies (FR10).
i
j ❑ Steel ❑ Steel
❑Not Applicable
303.2
:Wall insulation is installed per
❑Complies
[IN411
:manufacturer's instructions.❑Does
Not
❑Not Observable
i -
;❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) r4,,j Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: FS3B3 "FRAHM" Report date: 04/13/17
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\FS3B3 - AUSTIN.rck Page 7 of 9
Section
#
Final Inspection Provisions
plans Verified Field Verified
value Value
Complies? Comments/Assumptions
& Req.ID
- ❑Does Not
-^' - -
[]Does Not
402.1.1,
;Ceiling insulation R -value.
R- ; R -❑Complies
;See the Envelope Assemblies
402.2.1,
1
❑ Wood ; ❑ Wood
ODoes Not ;table for values.
402.2.2,
402.2.6
- ❑Does Not
❑ Steel ❑ Steel
'[]Not Observable
[Fill'
;fixtures or 75% of permanent
�`u;[�,t
;❑Not Applicable
403.4.1
;Circulating service hot water
❑Complies
[Fl11]2
303.1.1.1,
;Ceiling insulation installed per
_
❑Complies
303.2
:manufacturer's instructions.
[]Does Not
[FI211
Blown insulation marked every
UO
1300 W.
❑Not Observable
I
I,E3Not
❑Not Applicable j
402.2.3 i`
Vented attics with air permeable
❑Complies
[FI22]2
insulation include baffle adjacent
❑Does Not
;to soffit and eave vents that
❑Not Observable
!extends over insulation.
-
Applicable
402.2.4
;Attic access hatch and door
; R-_ R -_❑Complies
[FI311
!insulation zR-value of the❑Does
Not
jadJacent assembly.
:❑Not Observable
❑Not Applicable
402.4.1.2
;Blower door test @ 50 Pa. <=5
ACH 50 =_ ACH 50 =_❑Complies
[FI17]1
Tach In Climate Zones 1-2, and
Does Not
<=3 ach in Climate Zones 3-8.❑Not
Observable
'❑Not
Applicable
403.2.2
;Duct tightness test result of <=4
; cfm/100 cfm/100❑Complies
[FI4]1
:cfm/100 ft2 across the system or
ft' ft'❑Does
Not
!<=3 cfm/100 ft2 without air❑Not
;handler @ 25 Pa. For rough -in
Observable
;tests, verification may need to
;❑Not Applicable
;occur during Framing Inspection.
403.2.2.1
;Air handler leakage designatedEUWMIII_F-Ui.a
..
❑Complies
[FI2411
Iby manufacturer at <=2% of
❑Does Not
;design airflow.❑Not
Observable
A,...n—nie
403.1.1
Programmable thermostats
❑Complies
[FI9]2
;installed on forced airfurnaces. --3,
- ❑Does Not
-^' - -
[]Does Not
❑Not Observable
HVAC equipment meet efficacy
-
❑Not Applicable
403.1.2
l Heat pump thermostat installed
❑Complies
[FI10]2
Ion heat pumps.
- ❑Does Not
,J
❑Complies
❑Not Observable
;fixtures or 75% of permanent
�`u;[�,t
❑Not Applicable j
403.4.1
;Circulating service hot water
❑Complies
[Fl11]2
'.. systems have automatic or
- ❑Does Not
_
;accessible manual controls.
_
.. ❑Not Observable
403.5.1
-'All mechanical ventilation system
.❑Complies
[FI25]1
!fans not part of tested and listed
-^' - -
[]Does Not
HVAC equipment meet efficacy
-
[]Not Observable
and air flow limits.
>�_
❑Not Applicable
404.1
'75% of lamps in permanent
alll
❑Complies
[FI6]1
;fixtures or 75% of permanent
�`u;[�,t
- ❑Does Not
;fixtures have high efficacy lamps
!Does not apply to low -voltage
_�
- . �'�' a ,k
[]Not Observable
lliahtina.
; ax
_ ❑Not Applicable
1 IHigh Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: FS383 "FRAHM" Report date: 04/13/17
Data filename: CAUsers\jhoellei n.MAI N\Documents\REScheck\FS3B3 - AUSTIN.rck Page 8 of 9
Section
#
Final Inspection Provisions
Plans Verified Field Verified
Value Value Complies?
Coin me nts/Assumptions
& Req.ID
404.1.1 :,Fuel
gas lighting systems have
,❑Complies
[FI23]3 '!no
continuous pilot light.
]❑Does Not
❑Not Observable
i❑Not Applicable
401.3 ;Compliance
certificate posted. ',
i❑Complies
[FI7]2
i>
-!❑Does Not
'J
][]Not Observable
- ;❑Not Applicable
303.3 ,Manufacturer
manuals for
,❑Complies
[FI18]3 !mechanical
and water heating '
❑Does Not
U ;systems
have been provided.
1
--❑Not Observable
.I❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) -J Medium Impact (Tier 2) 1 3 IlLow Impact (Tier 3)
Project Title: FS3B3 "FRAHM" Report date: 04/13/17
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\FS3B3 - AUSTIN.rck Page 9 of 9
2012 IECC Energy
Efficiency Certificate
Above -Grade Wall 22.00
Below -Grade Wall 15.00
Floor 0.00
Ceiling / Roof 50.00
Ductwork (unconditioned spaces):
Window 0.32
Door 0.17
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments