HomeMy WebLinkAboutELECTRICAL REVIEW REPORT - 17-00272 - 639 Handcart Ln - Savoye Apartments LLCReview
Report
Current Electrical Review Status: REVISIONS
Application Number: 17-00272Permit Details
Application Received Date: 05/22/2017
Multi-Family Residential
Application Approved Date:
Application Approved Status: APPROVED
05/22/2017
525 Handcart Ln
525 Handcart Ln - Savoye Apartments LLC
Status of Plan Reviews Completed
05/25/2017HVAC Review COMPLETED
05/30/2017Electrical Review REVISIONS
05/31/2017Plumbing Review DENIED
Permit Review Status
Plan Reviews Still in Progress
Building Review
Planning and Zoning Review - Site Plan
Public Works Review - Site Plan
Fire Department Review - Site Plan
Electrical Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Electrical: Service REVISIONSCannot have two services on one building
unless a two hour fire wall is between buildings
to designate as two separate buildings. Panels
in units are noted with main breakers in each, if
this changes, an approval from the engineer
must be provided before rough-in inspections.
*Revisions Response :
Electrical: Wiring Method Reviewed for code compliance.COMPLETED
Electrical: Exit Signs/Emergency Lighting Reviewed for code compliance.COMPLETED
Electrical: Wiring-General All new wiring must meet the 2014 NEC.COMPLETED
Reviewed By: Bret Stoddard
Review Date: 05/30/2017
Plan Review Details
bret.stoddard@rexburg.org
Electrical Review Status: REVISIONS
Page 1 of 1
Approval of plans does not constitue approval of variance from code