HomeMy WebLinkAboutINPSECTION REPORT 1 (08.13.14) - 13-00104 - 538 S 2nd W - The Mountain Lofts Women's Bld; 93 UnitsCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-MFR ELECOMSERV Permit Number: Address: 538 S 2nd W Project: 13-00104 The Mountain Lofts - Bldg #1; 93 Units Inspection Date 8/13/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Each building has only one service or justified for more than one. 230.2 COMPLETED Underground fed services have proper strapping and expansion fittings. 352.30(A)(B), 352.44 COMPLETED Services are grouped together and limited to six disconnects. 230.71, 230.72 COMPLETED Unused openings have been closed. (K.O. seals, etc.) 110.12(A), 408.7 COMPLETED Proper clearances about electrical equipment indoors and outdoors. 110.26 (A), (E),(E)(2) and (F) COMPLETED Proper labeling of panels, switchgear, and similar equipment. 110.22, 408.4 COMPLETED Grounding electrode system installed-ufer, ground rods, metal water piping, etc. 250.52(A)(4-7) COMPLETED Grounding electrode system conductors sized and protected appropriately. 250.66, 250.64(F), 250.64(A)(B) COMPLETED Grounding electrode conductor is either un-spliced or spliced using approved methods. 250.64(C)(F) COMPLETED Main bonding jumper sized to 250.28(D), and all panels bonded together using an equipment bonding conductor sized in accordance with 250.122 or 250.66 as appropriate. COMPLETED Approved to be energized for permanent power (will send permit to utility). To remain energized for permanent power. COMPLETED Inspector: Bret Stoddard