INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELECOMSERV
Permit Number:
Address: 538 S 2nd W
Project:
13-00104 The Mountain Lofts - Bldg #1; 93
Units
Inspection Date
8/13/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Each building has only one service or
justified for more than one. 230.2
COMPLETED
Underground fed services have proper
strapping and expansion fittings.
352.30(A)(B), 352.44
COMPLETED
Services are grouped together and limited
to six disconnects. 230.71, 230.72
COMPLETED
Unused openings have been closed. (K.O.
seals, etc.) 110.12(A), 408.7
COMPLETED
Proper clearances about electrical
equipment indoors and outdoors. 110.26
(A), (E),(E)(2) and (F)
COMPLETED
Proper labeling of panels, switchgear, and
similar equipment. 110.22, 408.4
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc.
250.52(A)(4-7)
COMPLETED
Grounding electrode system conductors
sized and protected appropriately. 250.66,
250.64(F), 250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved
methods. 250.64(C)(F)
COMPLETED
Main bonding jumper sized to 250.28(D),
and all panels bonded together using an
equipment bonding conductor sized in
accordance with 250.122 or 250.66 as
appropriate.
COMPLETED
Approved to be energized for permanent
power (will send permit to utility).
To remain energized for permanent
power.
COMPLETED
Inspector: Bret Stoddard