HomeMy WebLinkAboutINSPECTION REPORT (07.22.14) - 13-00104 - 538 S 2nd W - The Mountain Lofts Women's Bld; 93 UnitsCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-MFR ELEFINAL-R Permit Number Address: 538 S 2nd W Project 13-00104 The Mountain Lofts - Bldg #1; 93 Units Inspection Date 7/22/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Positioning of boxes intended to be flush with combustible and noncombustible finished surfaces. 314.20 COMPLETED Gaps around boxes in walls. 314.21 COMPLETED Polarity of devices and luminaires. 200.10(B), 200.11, 410.23, 406.9 COMPLETED Unused openings in boxes and other enclosures are closed. 110.12, 314.17(A), 312.5(A) COMPLETED Spacing of receptacles for walls and countertops, including islands and peninsulas. 210.52(A) and (C) COMPLETED Countertop receptacles are provided with GFCI protection. 210.8(A)(6) COMPLETED Bathroom receptacles are GFCI protected. 210.8(A)(1) COMPLETED Arc-fault circuit-interrupter (AFCI) protection on bedroom circuits. 210.12 COMPLETED Proper identification of all overcurrent devices and disconnects. 110.22, 230.70(B), 408.4 COMPLETED Open spaces in panelboard fronts. 110.12 COMPLETED Approved for a final and C.O. in the noted levels. Final for electrical only in units #1104, 1106, 1107, 1109, 1110, 1111, 1118, 1119 and 1120. COMPLETED Inspector: Bret Stoddard