Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Issued Date: 10/11/2013
Permit Inspection Statistics
180Total Inspections Completed:
138Total Inspections Passed:
Inspection Pass Rate
76.67%
Permit Inspection History *Refer to Individual Inspection Report for more Details
10/10/2013PassBret StoddardElectrical Underground Inspection
Approved for cover-underground conduits for house panels and elevator shaft
from parking structure. (Southeast corner of project).
Inspector Comments:
10/11/2013PassDon AllenPlumbing Underground Inspection
All good on the under groundInspector Comments:
10/8,QO: shear wall inspection under arch. pop-outs. (North & East wall)Inspector Comments:
12/30/2013PassQuinton OwensFraming/Structure Inspection
Partial hold down inspec in mechanical room TEDInspector Comments:
03/12/2014FailTed DyeInsulation Inspection
room 2208 -Fire caulk electrical in west bedroom
fire caulk electrical in east bathroom,and bedroom.
Install missing stud next to drain pipe in east bedroom
Room 2207 -fire caulk electrical across from panel
Room 2209 upper level; Fire blocking needed between double wall located
between hall closet and apt.
-fire caulking needed on bathroom top plate
Room 2206 -OK
Room 2219 upper level;-fire caulk holes above strob
Room 2205 -OK
Room 2220 Fire block above electrical panel.
Insulate around window in east bedroom
Inspector Comments:
03/17/2014PassQuinton OwensInsulation Inspection
Sequence 1, level 2: 2206, 2207, 2208, 2209(upstairs) insulation approved.
Framing re-inspection needed
Inspector Comments:
Sequence 2, level 1 approved. Sequence 3, level 3 & 4 approved.Inspector Comments:
04/23/2014PassDon AllenHVAC Rough-in
section 5 floor 1,2,3 all good to coverInspector Comments:
Page 1 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
08/20/2014FailJoel GrayPublic Works Final Inspection
1. Curb and catch basin on 2nd W needs cleaned.
2. Signs needed to be reinstalled.
3. Raise manholes and water valves to grade.
4. Clean interior catch basins and clean inside edges.
5. Raise fire hydrant on north side of building.
6. Work on 3rd W needs to be completed.
7. Fire hydrant at southeast corner too high as currently graded and nozzles must
be re-oriented.
8. Storz adapter for fire hydrants.
9. Water line can not be connected to backflow in mechanical room.
Inspector Comments:
08/25/2014FailNatalie PowellPlanning and Zoning Final Inspection
1-The dumpster pad along 3rd West will need to be approved, poured and
inspected. Dumpsters will then be delivered.
2-The fence needs to be completely installed.
3-All Signage needs to be put up.
4-Please verify snow storage area is accessible.
5-Please verify bike rack areas are completed and meet CUP requirements.
Inspector Comments:
09/11/2014FailNatalie PowellPlanning and Zoning Final Inspection
Dumpsters must be finished and put in place. All signage must be installed. Fence
must be completed. Bike racks still need to be installed.
Inspector Comments:
03/09/2016PassNatalie PowellPlanning and Zoning Final Inspection
03/09/2016PassJoel GrayPublic Works Final Inspection
Page 2 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
Building Inspection Type
10/15: int. ftg/slab reinforcement as per plans. 2 bars at corners. (next to
elevator at SE corner.
Inspector Comments:
12/30/2013PassTed DyeFooting Inspection
7/24 footings rebar looked good TED
7/29 footings rebar in place and tied TED
Inspector Comments:
12/30/2013PassTed DyeFoundation Inspection
7/24 Section of wall middle level:approved, rebar looked good
7/30 Rebar ties , spaced and overlaped properly as per plans
Inspector Comments:
02/18/2014FailTed DyeSheeting
2/18/14 TD: Sheeting and Huss - under window 2106
missing stud 2108 (two)
missing stud 2109, 2119
North walls seg. 1 inspected areas that need fixed pained with orange.
South walls seg. 1 inspected from center corridor west.
Inspector Comments:
02/24/2014FailTed DyeSheeting
2/18 mailing missed under window in 2106
missing studs 2108 (two
missing studs in 2109 and2119 north walls seq 1 inspected area's that meed fixed
painted w/orange
south walls seq 1 inspected from center corridor west
Inspector Comments:
sheeting on seq 1 building 2, East of west hallway on south side: 2/21 missed
mailing room 2120and 2420
repair stud in2119
missing blocking in room 2420
Inspector Comments:
02/24/2014FailTed DyeSheeting
previous ticket dated 2/18 reinspected and passedInspector Comments:
02/25/2014FailQuinton OwensSheeting
2420 missed blocking & nailing (see orange paint-also stud by mech. closet).2421
missed stud in east bdrm. 2422 replace some blocking and nails missed Stud in
North bdrm. 2319- missing some blocking. 2320 nail edge of sheet (middle bdrm)
2321- blocking in west bdrm. 2322- North bdrm blocking, nails missed studs in
south middle bdrm. 2119 secure cripple stud under large window. 2122 missing
stud in North bdrm. Some places missed vapor barrier behind sheathing.
Blocking at end of mech chase can't block for insulation.
Inspector Comments:
02/26/2014PassTed DyeFraming/Structure Inspection
02/28/2014PassBret StoddardInsulation Inspection
building #2, 4th floor seq. #1.....insulation looks goodInspector Comments:
Page 3 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
02/28/2014FailQuinton OwensSheeting
2/28..sheeting level 1-4 seq 2 N.E. corner not completed
All other rooms complete and passed
Inspector Comments:
03/03/2014FailTed DyeFraming/Structure Inspection
Truss lateral bracing inspection:
Building #2 Seq. #1 Passed
Seq. #2 had some that did not have bracing on: I circled those braces on the
truss spec's of E21, A7B and A7C.
Seq #3 Starting at A5F and working back to Seq.#1
had these bracing missing. D4SA, A6D and A6G.
Call and set up a new inspection when corrections have been made.
Inspector Comments:
03/05/2014PassTed DyeSheeting
north east corner of building #2 seq.2 sheet inspection ....passed off
all of seq 2 passed off
Inspector Comments:
Sequence 1: 4th floor hall approved.Inspector Comments:
03/05/2014FailTed DyeInsulation Inspection
2308 insulation good
2307 insulation missing in bath room ceiling
insulation missing
fire caulk did not stay in place on 4" pipe
fire caulk missing on pipes between utility and bath
fire caulk missing above wash machine box
fire calk missing
2309 repair drywall around sprinkler pipe in furdown
fire block top plates between hall closet and kitchen
firecaulk around waterlines at top plate
insulate cavity where walls meet at a 45 degree angle
floor cavity missing insulation in bathroom
2306 fire caulk around water lines at top plate
***NOTE FIRE BLOCK RIM JOISTS AT CEILING BETWEEN HALL AND
ROOMS***
2305 fire caulk top and bottom plates
fire block between two different levels and repair shear wall
fire caulk around water lines
2319 fire caulk water lines
" " around ducting in east bedroom
" " " low voltage lines
2320 fire caulk around pipe in bath room at bottom plate
repair shear wall
Inspector Comments:
03/06/2014PassTed DyeInsulation Inspection
level 3 seq.#1 approved for coverInspector Comments:
Page 4 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
03/06/2014PassTed DyeSheetrock/Drywall Inspection
2405 drywall approved for taping
2406 " " " "
2407 " " " "
2408 " " " "
upper level of 3309 drywall approved for taping
Inspector Comments:
03/07/2014PassTed DyeSheetrock/Drywall Inspection
LEVEL 4 SEQ. 1
2319: top floor ok to tape
2420: ok to tape
2309 top level : ok to tape
HALL: all but last 20 ' inspected ok to tape..i will check it (20')Later to day.
Inspector Comments:
03/11/2014FailTed DyeSheetrock/Drywall Inspection
2307 screws missing above tub in west bath room/missing screws in closets
2308 not completed
2309 ok
2306 ok
2319 not completed
2305 no completed
2320 not completed
Inspector Comments:
Room 2220 Shear wall wall needs to be finished
Fire caulk above elect. panel
Room 2205 Shear wall east bedroom
fire caulk holes in closet (west bedroom)
Room 2219 fire caulk electrical holes
Room 2209 Elect. fire caulk
fire block double wall between apt. and hall closet
Room 2206 shear sheathing missing and existing nailed insulate
behind sheeting that is existing by and between west bedroom.
Between hall and unit, drain pipe needs fire blocked
Fire caulk pipe from hall to behind tub
Room 2207 Nails missing in shear wall (bedroom east of center)
Top plate cut all the way through, put a proper strap to hold to sides
together.(west ext. wall in bathroom).
Fire block pipe going to bath (Rim joist at west rub)
Room 2208 Elect. wires through top plates
Stud missing in east bedroom by drain pipe.
Inspector Comments:
03/11/2014FailTed DyeFraming/Structure Inspection
2205 stud cut in west bdrm at duct penetration & fireblk waterlines at top plate
by laundry rm. 2220 stud cut at east bdrm duct.
Inspector Comments:
03/13/2014PassQuinton OwensCommercial Sheetrock/Drywall Inspection
2307,2308,2319,2305,2320 approved for tapingInspector Comments:
Page 5 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
03/18/2014PassTed DyeSheetrock/Drywall Inspection
Rooms2208, 2207,and2206 Approved for tapingInspector Comments:
03/18/2014FailTed DyeFraming/Structure Inspection
2108 ok
2107 ok
2109 ok
2106 ok
2119 ok
2105 ok
2120 shear wall sheeting missing on west wall in west bedroom
shear wall sheeting missing on part of east wall in east bedroom and
bathroom.
Inspector Comments:
03/18/2014PassTed DyeInsulation Inspection
rooms 2108, 2107, 2109, 2106, 2119, 2105, and 2120 approved for coverInspector Comments:
03/18/2014PassTed DyeSheetrock/Drywall Inspection
2206 passed
2220 missed screwing of center of closet wings and in living area, missed
screwing off S.E. corner
2220 correction made while i was there Passed
Inspector Comments:
03/20/2014FailQuinton OwensInsulation Inspection
Sequence 2, level 4: 2422 insulation approved (finish shear wall & rough
plumbing). 2421 approved. 2403 finish sealing around upper large window and
north window. 2404 two windows missing (some framework being redone, and
4" PVC pipe to be framed in and fireblocked. ("2401 & 2402" not ready - access
from 3rd floor)
Inspector Comments:
03/20/2014FailQuinton OwensSheeting
Sequence 3,4,&5 all levels: Inspected by Ted & Quinton - insufficient nailing at
locations marked on inside. To be reinspected w/ framing.
Inspector Comments:
03/21/2014PassQuinton OwensCommercial Sheetrock/Drywall Inspection
2108,2107,2109,2120 approvedInspector Comments:
All but west corner unit approved for tapingInspector Comments:
Seq. 1 all but west corner unit approved to tapeInspector Comments:
03/24/2014PassTed DyeSheetrock/Drywall Inspection
Sep 1 level 1; all but west corner unit approved to tapeInspector Comments:
03/24/2014PassTed DyeInsulation Inspection
level 4 seq 2Inspector Comments:
03/25/2014PassTed DyeInsulation Inspection
Insulation in all of level 3, seq.2 good.
All holes fire caulked.
Inspector Comments:
Page 6 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
03/25/2014PassTed DyeInsulation Inspection
-Insulation good.
-All holes filled with fiire caulk or block.
OK to cover.
Inspector Comments:
03/25/2014PassTed DyeInsulation Inspection
l\Level 2 Seq 2Inspector Comments:
03/26/2014PassTed DyeSheetrock/Drywall Inspection
apt. 2404 OK to tape
Apt. 2403 OK to tape
Apt. 2422 Ok to tape
Inspector Comments:
03/26/2014FailTed DyeFraming/Structure Inspection
Apt 2222
Finish shear walls
Round hole in fur downs needs patched
Remove fire block foam around pipes and wires and fire caulk
Fire block rim joist
Apt. 2204
Fire caulk all pipes in concealed spaces
Water lines need fire block removed and replaced with fire caulk
Fire block rim joist
Inspector Comments:
03/26/2014PassQuinton OwensInsulation Inspection
level 3 seq 2Inspector Comments:
03/27/2014FailTed DyeFraming/Structure Inspection
Apartment 2222: Finish shear walls
Round hole in fir down needs to be patched.
Remove fire block foam from around pipes and fire caulk.
Apt. 2204; Fire caulk all popes in concealed spaces.
Waterlines, remove fire block and fire caulk
Fire block rim joist where penetrated.
Inspector Comments:
03/28/2014PassTed DyeFraming/Structure Inspection
Apts 2222 and 2204 have corrections made. OK to sheetrockInspector Comments:
03/31/2014FailTed DyeInsulation Inspection
Level 1, Seq 2
Fire caulk wires and sprinkler lines through pre-rock.
Fire caulk water lines going into corridor.
Check wall cavities in exterior wall, where pre-rock is, to see if insulation has
been pushes to top plate.
Inspector Comments:
04/01/2014PassTed DyeSheetrock/Drywall Inspection
2403,2421,2422,2301,2322,2302,2304,2321,2222 and 2221 all approved to tapeInspector Comments:
Page 7 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
04/01/2014PassTed DyeFraming/Structure Inspection
all corrections made from last framing inspectionInspector Comments:
04/01/2014PassTed DyeInsulation Inspection
all of level 1 seq2Inspector Comments:
04/02/2014PassQuinton OwensInsulation Inspection
Insulation inspection Seq3 units 2410, 2317 and 2318. ApprovedInspector Comments:
04/02/2014PassTed DyeInsulation Inspection
Insulation inspection Seq3 units 2410, 2317 and 2318. ApprovedInspector Comments:
04/04/2014PassTed DyeSheetrock/Drywall Inspection
unit 2101 OK to tape
unit 2103 OK to tape
unit 2104 OK to tape
unit 2121 OK to tape
Inspector Comments:
04/04/2014PassTed DyeFraming/Structure Inspection
Truss inspection for Seq. 3,4 and 5 Passed offInspector Comments:
04/04/2014PassTed DyeInsulation Inspection
2411 Insulation complete
2416 Insulation complete
2410 Remove drywall and attach vapor barrier properly.
2311 Insulation complete
2310 Insulation complete
Ok too install shear walls then call
Inspector Comments:
04/09/2014PassTed DyeInsulation Inspection
04/10/2014PassQuinton OwensSheetrock/Drywall Inspection
units 2310, 2318, 2317, 2311, 2122, and 2416 are approved to tape.
**** Note; check over tubs and complete.
Inspector Comments:
04/10/2014PassQuinton OwensInsulation Inspection
Insulation inspection units #2413, 2412, 2316, 2313, 2312 and2122Inspector Comments:
04/11/2014PassTed DyeInsulation Inspection
Insulation inspection
Units 2210,2211,2218 and 2118 Approved for cover.
Inspector Comments:
insulation inspection for Units: 2210, 2211, 2218 and 2118Inspector Comments:
04/14/2014PassTed DyeInsulation Inspection
insulation inspection for Units: 2210, 2211, 2218 and 2118Inspector Comments:
Page 8 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
04/15/2014FailTed DyeInsulation Inspection
Insulation inspection 4-15-14
2216: Insulate around windows.
2213: Insulate around windows.
2117 Ok for cover.
2116 Fire caulk top plate above electrical panel.
Fire caulk red wires. in top plate in South bedroom.
Fire caulk around exhaust pipes. (dryer vents)
Inspector Comments:
04/17/2014FailTed DyeInsulation Inspection
Insulation in 2110 Approved
UNIT 2111 -Fire caulk holes in top plate in north bathroom.
-Fire caulk hole in top plate in south bathroom that has red wires in it.
-Fire caulk one empty hole in top plate in south bathroom.
-Missing stud in laundry room.
-Work insulation up and around dryer vents in outside wall.
UNIT 2112 Hole on west wall at top plate in living area.
- Work insulation up and around dryer vents in outside wall.
Units 2213 and 2216 insulation reinspect approved.
Inspector Comments:
04/18/2014PassTed DyeSheetrock/Drywall Inspection
Units 1221 OK
Units 1224 OK
Inspector Comments:
04/18/2014PassTed DyeInsulation Inspection
-Insulation inspections2116, 2111,2110, 2112, 2212 all approved for coverInspector Comments:
04/18/2014PassTed DyeSheetrock/Drywall Inspection
drywall inspection; -Units 2211, 2210, 2213, 2316, 2317, 2312, and 2313
Approved to tape and texture.
Inspector Comments:
Page 9 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
Seq 5 level one
1107 S
-Need to finish shear in north bathroom.
-Fire caulk waterline in south bedroom,north wall.
-check insulation around windows
Level 2 Seq. 5 Unit 1207 -Need to finish shear wall in N. bathroom.
-Fire block rim joist (one hole next to door, right).
Unit 1208 -Fire block rim joist.
-Shear wall in north bath room needs finished.
-Fire caulk above electrical panel @ top plate.
-Fire caulk exhaust ducts in fur downs in south bedroom.
-Shear wall needed in south bathroom.
*********Note. discussed the need for the steel special inspection report with
Ryan.***********
Unit 1308 -Insulate around windows.
Unit 1407 -Insulate around windows.
-Insulate around exhaust ducts in fur downs in south bedroom.
-One hole in south hall in top plate needs fire caulked.
Unit 1408 -Insulate around windows.
Haul Fire caulk electrical cables (ceiling and at floor.
Inspector Comments:
Page 10 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
04/21/2014FailQuinton OwensInsulation Inspection
Seq 5 level one
1107 S
-Need to finish shear in north bathroom.
-Fire caulk waterline in south bedroom,north wall.
-check insulation around windows
Level 2 Seq. 5 Unit 1207 -Need to finish shear wall in N. bathroom.
-Fire block rim joist (one hole next to door, right).
Unit 1208 -Fire block rim joist.
-Shear wall in north bath room needs finished.
-Fire caulk above electrical panel @ top plate.
-Fire caulk exhaust ducts in fur downs in south bedroom.
-Shear wall needed in south bathroom.
*********Note. discussed the need for the steel special inspection report with
Ryan.***********
Unit 1308 -Insulate around windows.
Unit 1407 -Insulate around windows.
-Insulate around exhaust ducts in fur downs in south bedroom.
-One hole in south hall in top plate needs fire caulked.
Unit 1408 -Insulate around windows.
Haul Fire caulk electrical cables (ceiling and at floor.
Inspector Comments:
04/23/2014PassTed DyeFraming/Structure Inspection
level 3 seq. #1 structure good
fire caulking and fire blocking are not completed
Inspector Comments:
04/24/2014PassTed DyeInsulation Inspection
Correction
Insulation inspection on Level 4, Seq. 5: Units 2415 and 2414 are approved for
cover.
Inspector Comments:
04/24/2014PassTed DyeInsulation Inspection
2413 insulation Approved
2413 insulation Approved
Inspector Comments:
04/24/2014PassTed DyeInsulation Inspection
insulation inspection Level 4 Seq. 5 Unit 2414 approved for coverInspector Comments:
04/25/2014PassTed DyeInsulation Inspection
2314 and 2315 approved for coverInspector Comments:
Page 11 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
-2115 needs to have hold downs tightened.
-room just north of living room has a Hd-U2 that needs a different bolt, one
spec.out for that hold down. ---also in the same room on the south wall, the hold
down is not located under the studs above. It needs to be moved under the
straps.
Weight Room; Tighten down HD hold downs.
Some slotted washers on Anchor bolts are missing washers .under nuts.
Inspector Comments:
-2115 needs to have hold downs tightened.
-room just north of living room has a Hd-U2 that needs a different bolt, one
spec.out for that hold down. ---also in the same room on the south wall, the hold
down is not located under the studs above. It needs to be moved under the
straps.
Weight Room; Tighten down HD hold downs.
Some slotted washers on Anchor bolts are missing washers .under nuts.
Inspector Comments:
04/25/2014FailTed DyeFraming/Structure Inspection
-2115 needs to have hold downs tightened.
-room just north of living room has a Hd-U2 that needs a different bolt, one
spec.out for that hold down. ---also in the same room on the south wall, the hold
down is not located under the studs above. It needs to be moved under the
straps.
Weight Room; Tighten down HD hold downs.
Some slotted washers on Anchor bolts are missing washers .under nuts.
Inspector Comments:
04/28/2014PassTed DyeInsulation Inspection
Apt. 2201,2202,2204 and 2222 insulation approvedInspector Comments:
04/29/2014FailTed DyeInsulation Inspection
unit 2215 -has insulation missing around dryer duct north bedroom.
-shear wall needs to be finished.
unit 2214 -insulation needed above blocking behind fur down area.
unit 2115 -finish shear walls.
the corridor level 1 Seq.4 caulking and fire blocking approved.
Inspector Comments:
04/30/2014FailTed DyeInsulation Inspection
2115 replace insulation in ceiling in two spots before covering.
2215 approved to hang drywall.
2214 finish shear wall in north bathroom.
Inspector Comments:
04/30/2014PassTed DyeSheeting
Reinspection sheathing for sequence 3,4, & 5. Several Framing inspections
followed up by Ted were passed.
Inspector Comments:
04/30/2014PassTed DyeSheetrock/Drywall Inspection
Units 2414 and 2415 Approved and OK to tapeInspector Comments:
Page 12 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
05/01/2014PassTed DyeInsulation Inspection
insulation on seq 4 level 4 passedInspector Comments:
05/05/2014FailTed DyeInsulation Inspection
mechanical room insulation approved
level 1 seq 4 and 5 approved
Inspector Comments:
mechanical room insulation approved
level 1 seq 4 and 5 approved
Inspector Comments:
05/06/2014PassTed DyeInsulation Inspection
mechanical room insulation approved
level 1 seq 4 and 5 approved
Inspector Comments:
05/09/2014PassQuinton OwensSheetrock/Drywall Inspection
-Level one Seq 5 there is only one room. Approved to tape and texture.Inspector Comments:
05/09/2014PassTed DyeInsulation Inspection
Looked at the 3 stairways for insulation. All three approved.Inspector Comments:
05/09/2014PassTed DyeInsulation Inspection
Weight room insulation in the ceiling ApprovedInspector Comments:
Page 13 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
05/16/2014PassTed DyeInsulation Inspection
exercise; room insulation approved
-2407 whole in wall in first east bath room.
right ice maker supply box broke.
-2406 check furness room for fire caulking
-2405 "
-2420 "
-2408 "
-2308 "
-2307 "
-2309 " both levels.
-2306 "
-2319 " both levels
-2305 "
-2320 "
-2220 "
-2205 "
-2206 "
-2207 seal hole in furness room ceiling and fire caulk.
-2208 fire caulk pipe in furness room
-2120 far east bathroom, fire caulk around toilet supply,
clean out covers needed
seal around drain line on outside wall.
-2105 in east bathroom,fire caulk around supply for toilets and clean out covers
needed.
-2119 in south west bathroom supply for toilet needs fire caulk
check furness room.
-2106 OK
-2109 west main level bathroom, toilet supply needs fire caulked.
check furness room.
-2107 plumbing clean out covers needed.
toilet supply line needs fire caulked.
fire caulk around lines going through ceiling in furness room.
2108 furness room around sprinkler head
clean out covers needed
Inspector Comments:
05/29/2014PassTed DyeFraming/Structure Inspection
fire caulking on level 4, Seq. 4 and 5 are approved to cover.Inspector Comments:
06/02/2014PassTed DyeInsulation Inspection
Fire caulk inspection on Level 3 Seq. 1 and 2 ApprovedInspector Comments:
06/11/2014PassTed DyeSheetrock/Drywall Inspection
Level 3; seq 3. Corridor
Good from hall of see 1 to room 2319
Inspector Comments:
Page 14 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
06/12/2014FailTed DyeInsulation Inspection
Level 4 Seq.s 1-5 fire calling passed.
Level 3 in 2302 there is a hole in the back of a vanity that needs repaired.
All other rooms on the 3rd level passed in all seq's.
Inspector Comments:
06/19/2014FailQuinton OwensCommercial Framing/Structure Inspection
Insufficient caulk around pipes most sealed w/ drywall mud. Intumescent Fire
caulk required.
Inspector Comments:
Framing on east entrance (car drive through)Inspector Comments:
06/26/2014PassTed DyeFraming/Structure Inspection
Framing on east entrance (car drive through)Inspector Comments:
06/26/2014PassTed DyeFraming/Structure Inspection
East entrance is the car entrance.
Framing is approved.
Inspector Comments:
Floor 1 corridor: 3 corrections needed. 1 hole in ceiling, 1 patch with only 1 layer
of drywall, and gaps around sprinkler pipe. See attached pictures.
Inspector Comments:
07/01/2014FailQuinton OwensFraming/Structure Inspection
7/3: Additional work at west end of sequence 1 needs to be fire caulked (orange
foam is not rated).
Inspector Comments:
Corridors on level 1 approved to hang ceiling drywall. EXCEPT by Boiler room at
west end of sequence one (Gas line to be fire caulked and re-inspected).
Inspector Comments:
07/07/2014PassQuinton OwensFraming/Structure Inspection
Level 1 by boiler room: Re-inspected while on other inspection. Removed drywall
and found penetrations not sealed & rated. Completed fire caulk on hall side and
corridor approved. Boiler room side not done.
Inspector Comments:
07/10/2014FailTed DyeFraming/Structure Inspection
2210 furnuss room F.C. around sprinkler head.
2211urnuss room F.C. around sprinkler head.
2212. OK
2213 OK.
2214. Ok.
2215 OK
2216. furnuss room F.C. around sprinkler head.
Inspector Comments:
07/16/2014FailQuinton OwensCommercial Framing/Structure Inspection
1st Floor Sequence 1 & 2 completed and approved
Sequence 3-5 not ready.
Inspector Comments:
07/18/2014FailQuinton OwensCommercial Building Final
2416 hall detectors no signal & none of the unit strobe lights working, ADA
cabinets 27" min clearance & grab bars needed, 2413 entry door catches on
treshold.
Approved units: 2404, 05, 06, 07, 08, 10, 11, 14, 15, 20, 22.
Inspector Comments:
Page 15 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
3rd floor apartment interiors: Sequence 4 & 5 - 2313 west bath fan not working,
2314 sprinkler in furnace closet.
Inspector Comments:
2308 OK
2307 fire caulk hole around sprinkler head in mechanical closet.
2309 smoke detectors are not working on the bottom floor.
2306. Ok
2319. Touch up fire caulk around the drain line in south bathroom under vanity.
UPSTAIRS. Light covers missing in the East bathroom.
2305the transition strip under the entrance door won't let the door close.
Touch up the fire caulk around the drain in the west bathroom.
Fire caulk around the sprinkler head in the mechanical closet. Touch up fire
caulk around drain line in the East bathroom under the vanity.
230 fire caulk around the sprinkler head in the mechanical closet.
2321. Touch up fire caulk around the drain line in the west bathroom on the
bottom floor.
Inspector Comments:
23 11 entrance door won't close because of rubbing on transition strip.
Smoke detector in kitchen is not communicating with others.
2317 under up stairs kitchen sink, fire caulking missed.cut out drywall around
drain line and then fire caulk. Fire caulk around supply lines uunder vanity in
North upstairs bathroom.
2310 repair hole cut in wall under vanity sink in North bathroom
2318 smoke detector in north bedroom is not working.
UPSTAIRS smoke detector in north bedroom is not communicating with
others. Cross through vent grill missing on stairs
Inspector Comments:
07/21/2014FailQuinton OwensCommercial Building Final
2303 sprinkler head missing headi the east bedroom.
UPSTAIRS. Fire caulk around drain line under the kitchen sink, remove the
netting and fill the position cavity
Fire caulk around drain line in theEast bathroom, and remove the mess and fill
the cavity.
2302. OK
2322. Finish fire caulk around the drain line under the vanity in the north
bathroom.
2301 smoke detectors not working
UPSTAIRS fire caulk around the drain line under the kitchen sink.
Inspector Comments:
07/21/2014FailQuinton OwensCommercial Framing/Structure Inspection
1st floor fire caulking: little to no annular space around pipe for fire caulk in 2118
(up north & up center), 2117 (lower south), 2115 north & south, 2112 lower east.
Fire caulk also needed at following locations: 2110 & 2111 wire penetration in
furnace closet ext. wall, 2115 sprinkler in furnace closet.
PARKING ENTRANCE fire caulking approved for insulation in pipe chase and
cover.
Inspector Comments:
Page 16 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
07/29/2014FailQuinton OwensCommercial Framing/Structure Inspection
Level 2 Fire caulking plumbing penetrations in rated walls approved in sequence
1 & 2 only. Other units not fire caulked properly (little or no annular space filled
around drain pipes). Protection on wall surface should be done with fire collars if
drywall is tight around pipes.
Inspector Comments:
07/30/2014FailQuinton OwensCommercial Building Final
2311 entry drawing on threshold
2310 hole under vanity in North bathroom
2305 entry drawing on exterior threshold.
2313 fan in west bathroom is not working.
Inspector Comments:
07/31/2014PassTed DyeCommercial Building Final
Units that passed are Numbers 2208, 2207, 2206, 2205, 2220, 2204, 2222,
2210, 2211, 2216, 2218, 2215, and 2214. Corner units to be approved with those
on level 1.
Inspector Comments:
08/06/2014FailQuinton OwensCommercial Building Final
Fire rate all PVC penetrating exterior walls under furnaces. 2120 Seal at Tub
base. 2121 south upper bdrm sprinkler (patch slightly oversized hole). 2111 HC
grab bars toilet and 1 missing in shower. 2115 Metal clean out covers, Fire caulk
drain at North bath sink & under furnace. 2117 & 2118 Tempered windows.
Approved units: 2101, 2102, 2103, 2104, 2112
REINSPECTED: 2416, 2413, 2313, 2305, 2310, 2311.
Inspector Comments:
08/08/2014PassQuinton OwensCommercial Building Final
1st floor all apartment interiors approvedInspector Comments:
08/13/2014FailQuinton OwensCommercial Building Final
safety glazing by stairs in the west tower and south east tower. seal penetrations
on first floor and fourth floor of Southwest stair tower.
Inspector Comments:
08/20/2014PassQuinton OwensCommercial Building Final
Final on stairs & corridors. ramp handrails are not in.Inspector Comments:
08/21/2014FailTed DyeCommercial Building Final
08/22/2014FailQuinton OwensCommercial Building Final
Interior corridor ramps missing handrails (all levels). Fire caulking not done in
maintenance room (south of east parking entry). Expansion joints not completed
at doors between garage and buildings for proper fire blocking with mineral wool.
Exterior landing outside of door to East stairs cannot be more than 2%. Some
portions of finish grade are up to or covering framed portions of building (code
requires 8" clearance). Handicap parking access aisle in Northeast corner must
have 3 ft min of its width in front of access ramp.
Inspector Comments:
09/10/2014FailQuinton OwensCommercial Building Final
Level identification signs and mineral wool seal around doors to garage need
corrections made. See permit 13-00199. Cannot give full C.O. for until these
items are completed as part of exit enclosure.
Inspector Comments:
Page 17 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
03/11/2016PassQuinton OwensCommercial Building Final
Previous items completed. Final C.O. complete for this building, 13-00105 (1 of 3)Inspector Comments:
Page 18 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
Electrical Inspection Type
02/26/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
03/04/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/07/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/11/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
03/13/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/19/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/20/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/21/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/26/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
04/01/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
04/03/2014PassBret StoddardCommercial Electrical Rough-in
04/07/2014PassBret StoddardCOM & MFR Electrical Service Inspection
04/07/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
04/10/2014PassBret StoddardCommercial Electrical Rough-in
04/14/2014PassBret StoddardCommercial Electrical Rough-in
04/15/2014PassBret StoddardCommercial Electrical Rough-in
04/16/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
04/21/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
04/23/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
05/05/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
05/19/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
05/29/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
05/30/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
05/30/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
06/06/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
06/09/2014PassBret StoddardCommercial Electrical Rough-in
Partial approval for drywall on bldg #2, 3rd floor sequence 3 corridor LID, per
Gabe Madrid.
Inspector Comments:
06/16/2014PassBret StoddardCommercial Electrical Rough-in
06/17/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Page 19 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
06/20/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
06/20/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
06/23/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
07/02/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
07/07/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
07/08/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
07/08/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
07/15/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
07/17/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
07/22/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
07/24/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
08/05/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
08/14/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
08/14/2014PassBret StoddardCOM & MFR Electrical Service Inspection
08/15/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
08/20/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
08/28/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Fire Inspection Type
02/24/2014PassDale PickeringFire Sprinkler Rough-in
06/18/2014PassDale PickeringFire Sprinkler Rough-in
08/20/2014PassBret StoddardFire Alarm Final Inspection
08/26/2014PassDale PickeringFire Sprinkler Rough-in
08/26/2014PassDale PickeringFire Sprinkler Final Inspection
08/26/2014PassDale PickeringFire Department Final Inspection
08/28/2014PassBret StoddardFire Alarm Final Inspection
Page 20 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
Mechanical Inspection Type
03/05/2014PassQuinton OwensHVAC Rough-in
Sequence 1: 4th floor approved. 3rd floor: HVAC approved except 2319 (not
ready) and bearing studs were cut for ducts as noted 2308-in west & east bdrm.
2307 in east bdrm. 2309 approved. 2306 -in lvng rm & west bdrm. 2305 -in west
& east bdrm also need to finish fire blocking. 2320 approved.
Inspector Comments:
03/07/2014PassQuinton OwensHVAC Rough-in
Sequence 1, level 2 approved, level 3 finished & approved.Inspector Comments:
03/11/2014FailQuinton OwensHVAC Rough-in
Sequence 2, level 4: 2422 missing supply vent in middle bedroom. "2421"
approved, "2403" approved, 2404 approved.
Inspector Comments:
04/03/2014PassDon AllenHVAC Rough-in
section 3 all good to coverInspector Comments:
06/23/2014PassDon AllenHVAC Final Inspection
everything for jm mechanical looks good.Inspector Comments:
Page 21 of 22
(Continued)
Permit Details Permit Number: 13-00105
The Mountain Lofts Men's Bld; 68 Units
538 S. 2nd W.
Multi-Family Residential
Permit Status of (Expired) as of Report Date: 02/02/2017 10:15 am
Permit
Inspection
Summary
Plumbing Inspection Type
02/20/2014PassDon AllenPlumbing Rough-in
all good to cover rough inInspector Comments:
02/25/2014PassDon AllenPlumbing Rough-in
good to cover the south roomsInspector Comments:
02/26/2014PassDon AllenPlumbing Rough-in
03/03/2014PassDon AllenPlumbing Rough-in
all good in section 1Inspector Comments:
03/05/2014PassDon AllenPlumbing Rough-in
all good to cover the 3rd floorInspector Comments:
03/06/2014PassDon AllenPlumbing Rough-in
all good to cover the 2nd floor section 1Inspector Comments:
03/20/2014PassDon AllenPlumbing Rough-in
all good on the section 2Inspector Comments:
03/31/2014PassDon AllenPlumbing Water
all good to cover rough inInspector Comments:
04/12/2014PassDon AllenPlumbing Rough-in
All good to cover rough inInspector Comments:
04/29/2014PassDon AllenPlumbing Rough-in
All good to cover rough north east apt. on section 5Inspector Comments:
04/30/2014PassDon AllenPlumbing Water
All good to cover section 5Inspector Comments:
07/16/2014PassDon AllenPlumbing Final Inspection
3rd and 4th floor are all good for the c/o on the plumbing
Still need to look at the condensate lines on the furnace
Inspector Comments:
07/16/2014PassDon AllenPlumbing Final Inspection
need look at the furnacesInspector Comments:
08/29/2014PassDon AllenPlumbing Final Inspection
Page 22 of 22