HomeMy WebLinkAboutINSPECTION REPORT 1 (08.20.14) - 13-00105 - 538 S 2nd W - The Mountain Lofts Men's Bld; 68 UnitsCommunity Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
FIRE BLD-MFR FA-FINAL
Permit Number:
Address: 538 S. 2nd W.
Project:
13-00105 The Mountain Lofts II - 68 Units
Inspection Date
8/20/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Verify listing of power-limited source and
that the power
circuit is not protected by GFCI or AFCI
devices.760.41(B)
COMPLETED
Signaling devices placed to meet minimum
code compliance db or visual notification.
IFC, NFPA 72
COMPLETED
Witnessed 24 Hour/5 minute test with
system fully functional-verify with
monitoring station times if not logged in
panel event logger(LCD screen).
COMPLETED
Verify two lines of communication with
monitoring station.
COMPLETED
All valves on sprinkler system that could
hinder the performance of sprinkler system
tied into fire alarm system-monitored
(tamper switches) and labeled as
supervisory in panel.
COMPLETED
Address of site accurate on
report-monitoring station.
COMPLETED
Witnessed operation of signaling devices.COMPLETED
Witnessed operation of manual pull
station(s).
COMPLETED
Witnessed flow switch operation with
water gong (outside) and fire alarm panel
initiation-must operate within 30 to 90
second operation. *Make sure flow orifice
is sized to the smallest sprinkler head in
the system such as inspectors test or
actual head installed in discharge orifice.
COMPLETED
Witnessed operation of supervisory
devices such as tamper switches, etc.
COMPLETED
Remote annunciator functional and
located as per approved location-plans.
COMPLETED
Page 1 of 2
Fire Alarm panel labeled with electrical
panel and circuit number.
COMPLETED
Electrical panel circuit painted red.COMPLETED
Fire alarm system control functions
operational-door holders.
COMPLETED
Resistors not installed on circuits in panel.COMPLETED
Witnessed monitoring functional with
monitoring station.
COMPLETED
Batteries marked with date installed.COMPLETED
Copy of report from NICET fire alarm
contractor upon completion and put in file
at office-scanned.(For each individual
system-multiple buildings or systems)
Fire alarm contractor report not submitted
to us yet.
COMPLETED
FACP label on door of room fire alarm
panel is located.
Label not installed on doors of building
one or two.
COMPLETED
As built plan in FACP for fire department.As built plans not done yet for building 1
or 2.
COMPLETED
Approved for a final and C.O.Approved for a final and TEMPORARY
C.O. only-need to finish labeling units,
meters and fire alarm devices. Also need
to finish up loose ends throughout-Jack
has list of these items. This does not give
consent that people can move into the
units to live. This will be done later this
week or first part of next.
COMPLETED
Inspector: Bret Stoddard
Page 2 of 2