HomeMy WebLinkAboutTOWER PLANS - 16-00046 - 525 S 2nd E - AT&T Tower AdditionDate: September 03, 2015 Amber Puckett Crown Castle 5350 North 48th Street Suite 305 Chandler, AZ 85226 (480) 734-2420 Subject., Carrier Designation: Crown Castle Designation: Engineering Firm Designation: Site Data: Dear Amber Puckett, Structural Analysis Report AT&T Mobility Co -Locate Carrier Site Number: Carrier Site Name: GPD GROUP Professional Corporation 520 South Main Street, Ste 2531 Akron, OH 44311 (614) 859-1607 dpalkovic@gpdgroup.com 10129865 Rexburg WT Crown Castle BU Number: 857594 Crown Castle Site Name: REXBURG_WT Crown Castle JOE Job Number: 344780 Crown Castle Work Order Number: 1112271 Crown Castle Application Number: 307869 Rev. 1 GPD Project Number: 2015777.857594.01 525 South 2nd East, Rexburg, ID 83440, Madison County Latitude 430 48'53" Longitude -111* 46'37" 60 Foot - Self Support Tower GPD is pleased to submit this "Structural Analysis Report" to determine the structural integrity of the above mentioned tower. This analysis has been performed in accordance with the Crown Castle Structural 'Statement of Work' and the terms of Crown Castle Purchase Order Number 820835, in accordance with application 307869, revision 1. The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have determined the tower stress level for the structure and foundation, under the following load case, to be: LC5: Existing + Proposed Equipment Sufficient Capacity Note: See Table I and Table II for the proposed and existing/reserved loading, respectively. This analysis has been performed in accordance with the 2012 International Building Code based upon an ultimate 3 -second gust wind speed of 115 mph converted to a nominal 3 -second gust wind speed of 89 mph per section 1609.3.1 as required for use in the TIA-222-G Standard per Exception #5 of Section 1609.1.1. Exposure Category C and Risk Category II were used in this analysis. We at GPD appreciate the opportunity of providing our continuing professional services to you and Crown Castle. If you have any questions or need further assistance on this or any other projects please give us a call. Structural analysis prepared by: Eric SO Respectfully submitted by: Christopher J. Scheks, P. E. Idaho #: 16108 520 South Main Street. Suite 2531 . Akron, Ohio 44311 . 330-572-2100. Fax 330-572-2101 . w .GPDGroupxom GPD Group, Professional Corporation 60 It Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594.01, Application 307869, Revision 1 CCI BU No 857594 Page 2 TABLE OF CONTENTS 1) INTRODUCTION 2) ANALYSIS CRITERIA Table 1 - Proposed Antenna and Cable Information Table 2 - Existing and Reserved Antenna and Cable Information Table 3 - Design Antenna and Cable Information 3) ANALYSIS PROCEDURE Table 4 - Documents Provided 3.1) Analysis Method 3.2) Assumptions 4) ANALYSIS RESULTS Table 5 - Section Capacity (Summary) Table 6 - Tower Components vs. Capacity 4.1) Recommendations 5) DISCLAIMER OF WARRANTIES 6) APPENDIX A tnxTower Output 7) APPENDIX B Base Level Drawing 8) APPENDIX C Additional Calculations tnxTower Report - version 6.1.4.1 60 ft Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594.01, Application 307869, Revision 1 CCI BU No 857594 Page 3 1) INTRODUCTION The existing tower is supported on three legs and has three major sections. It has a triangular cross section made of bolted connections with an "X" bracing configuration. The tower is fabricated with solid round legs and angle diagonals and girts. The structure is galvanized and does not have aviation lightning. The tower geometry is modeled based on a tower mapping completed by GPD (Job #: 2012833.43, dated 02/20/2013). The original tower drawings, design load and design code were unavailable for this site. 2) ANALYSIS CRITERIA This analysis has been performed in accordance with the 2012 International Building Code based upon an ultimate 3 -second gust wind speed of 115 mph converted to a nominal 3 -second gust wind speed of 89 mph per section 1609.3.1 as required for use in the TIA-222-G Standard per Exception #5 of Section 1609.1.1. Exposure Category C and Risk Category II were used in this analysis. Table 1 - Proposed Antenna and Cable Information Center Mounting Line Number Antenna Number Feed Level (ft) Elevation of Manufacturer Antenna Model of Feed Line Note . (ft) Antennas Number Linen Size (in) 3 Alcatel Lucent RRH2x60-1900A-4R Manufacturer 60.0 63.0 1 Powerwave LGP18601 (ft) , -Antennas Technologies Lines 61.0 3 Andrew SBNHH-1D65C 1 Table 2 - Existina and Reserved Antenna and Cable Information Notes: 1) Existing Equipment to be removed; not considered in this analysis. tnxTower Report - version 6.1.4.1 Center Mounting Line Number Antenna Number Feed Level (ft) Elevation Of Manufacturer Antenna Model of Feed Line Note (ft) , -Antennas Lines Size (in) 1 Powerwave LGP18601 1 Technologies 3 Powerwave 7762.00 63.0 Technologies 2 Powerwave LGP18601 Technologies 1 Raycap DC6-48-60-18-8F 20 7/8 3 Powerwave 7722.00 60.0 3 3/8 Technologies 1 1/2 62.0 3 Powerwave 8110.10 Technologies 3 Alcatel Lucent RRH 700 MHZ 61.0 3 Alcatel Lucent RRH AWS 3 KMW AM -X -CD -17 -65 -OOT -RET 1 Communications 60.0 1 Platform Mount [LP 712-1]1 1 — Notes: 1) Existing Equipment to be removed; not considered in this analysis. tnxTower Report - version 6.1.4.1 60 It Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594.01, Application 307869, Revision 1 CCI BU No 857594 Page 4 Table 3 - Design Antenna and Cable Information Mounting Center - Line ;Number Antenna Tower Mapping Number 'Feed Level (ft) Elevation of Manufacturer Antenna Model of Feed Line 4724510 (ft),Antennas 01/17/2013 Lines Size (in) Unavailable 3) ANALYSIS PROCEDURE Table 4 - Documents Provided Document ( Remarks Reference Source Tower Mapping GPD Project #: 2012833.43, dated D. Palkovic GPD 02/20/2013 Foundation Mapping GPD Project A 2012833.43, dated 4724510 CCISITES 01/17/2013 Geotechnical Report Harper -Leavitt Site #: ID252, 4571357 CCISITES dated 09/14/2005 3.1) Analysis Method tnxTower (version 6.1.4.1), a commercially available analysis software package, was used to create a three-dimensional model of the tower and calculate member stresses for various loading cases. Selected output from the analysis is included in Appendix A. 3.2) Assumptions 1) Tower and structures were built in accordance with the manufacturer's specifications. 2) The tower and structures have been maintained in accordance with the manufacturer's specification. This analysis may be affected if any assumptions are not valid or have been made in error. GPD should be notified to determine the effect on the structural integrity of the tower. tnxTower Report - version 6.1.4.1 60 ft Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594. 01, Application 307869, Revision I M BU No 857594 Page 5 4) ANALYSIS RESULTS Table 6 - Section CaDacitv (Summarv) SectionCritical 4 -No. E Elevation Component Type size Element P (K) SF*P_suow � (K) % capacity Pass I Fall T1 60-40 Leg 23/4 3 -15.72 186.96 8.4 Pass T2 40-20 Leg 3 39 -29.87 198.96 15.0 Pass T3 20-0 Leg 3 66 -43.85 198.96 22.0 Pass T1 60-40 Diagonal -2x2x3/16 9 -1.54 12.01 12.8 22.4 (b) Pass T2 40-20 Diagonal -2x2x3/16 42 -1.86 7.91T-135 1 26.8� (b) Pass T3 20-0 Diagonal L21/2x21/2x1/4 69 -2.06 15.01 13.7 1 Pass Tl 60-40 Top Girt L2x2x3/16 4 F755 I 9.178.0 7.b) 4 ( pass Su LC5 Leg (T3) Diagonal (T2) 22.0 26.8 Pass Pass Top Girl (Tl) 7.4 Pass T -F I Bolt Checks I 26-8F--Pa­ss- I I I Rating = 1 26.8 1 Pass Table 6 - Tower Component Stresses vs. Caoacitv - LC5 Notes Component Elevation (ft) % Capacity Pass i Fall Anchor Rods 0 21.4 Pass Base Foundation 0 7.2 Pass FiRise,-dation SoilinterFoun. action 0 23.4 Pass Structure Rating (max from all components) 26.8% Notes: 1) See additional documentation in "Appendix C - Additional Calculations" for calculations supporting the % capacity consumed. 4.1) Recommendations The existing tower and its foundation are sufficient for the proposed loading and do not require modifications. tnxTower Report - version 6.1.4.1 60 it Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594.01, Application 307869, Revision 1 CCI BU No 857594 Page 6 5) DISCLAIMER OF WARRANTIES GPD has not performed a site visit to the tower to verify the member sizes or antenna/coax loading. If the existing conditions are not as represented on the tower elevation contained in this report, we should be contacted immediately to evaluate the significance of the discrepancy. This is not a condition assessment of the tower or foundation. This report does not replace a full tower inspection. The tower and foundations are assumed to have been properly fabricated, erected, maintained, in good condition, twist free, and plumb. The engineering services rendered by GPD in connection with this Structural Analysis are limited to a computer analysis of the tower structure and theoretical capacity of its main structural members. No allowance was made for any damaged, bent, missing, loose, or rusted members (above and below ground). No allowance was made for loose bolts or cracked welds. This analysis is limited to the designated maximum wind and seismic conditions per the governing tower standards and code. Wind forces resulting in tower vibrations near the structure's resonant frequencies were not considered in this analysis and are outside the scope of this analysis. Lateral loading from any dynamic response was not evaluated under a time -domain based fatigue analysis. GPD does not analyze the fabrication of the structure (including welding). It is not possible to have all the very detailed information needed to perform a thorough analysis of every structural sub -component and connection of an existing tower. GPD provides a limited scope of service in that we cannot verify the adequacy of every weld, plate connection detail, etc. The purpose of this report is to assess the capability of adding appurtenances usually accompanied by transmission lines to the structure. It is the owner's responsibility to determine the amount of ice accumulation in excess of the code specified amount, if any, that should be considered in the structural analysis. The attached sketches are a schematic representation of the analyzed tower. If any material is fabricated from these sketches, the contractor shall be responsible for field verifying the existing conditions, proper fit, and clearance in the field. Any mentions of structural modifications are reasonable estimates and should not be used as a precise construction document. Precise modification drawings are obtainable from GPD, but are beyond the scope of this report. Miscellaneous items such as antenna mounts, etc., have not been designed or detailed as a part of our work. We recommend that material of adequate size and strength be purchased from a reputable tower manufacturer. Towers are designed to carry gravity, wind, and ice loads. All members, legs, diagonals, struts, and redundant members provide structural stability to the tower with little redundancy. Absence or removal of a member can trigger catastrophic failure unless a substitute is provided before any removal. Legs carry axial loads and derive their strength from shorter unbraced lengths by the presence of redundant members and their connection to the diagonals with bolts or welds. If the bolts or welds are removed without providing any substitute to the frame, the leg is subjected to a higher unbraced length that immediately reduces its load carrying capacity. If a diagonal is also removed in addition to the connection, the unbraced length of the leg is greatly increased, jeopardizing its load carrying capacity. Failure of one leg can result in a tower collapse because there is no redundancy. Redundant members and diagonals are critical to the stability of the tower. GPD makes no warranties, expressed and/or implied, in connection with this report and disclaims any liability arising from material, fabrication, and erection of this tower. GPD will not be responsible whatsoever for, or on account of, consequential or incidental damages sustained by any person, firm, or organization as a result of any data or conclusions contained in this report. The maximum liability of GPD pursuant to this report will be limited to the total fee received for preparation of this report. tnxTower Report - version 6.1.4.1 60 It Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594.01, Application 307869, Revision 1 CCI BU No 857594 Page 7 APPENDIX A TNXTOWER OUTPUT tnxTower Report - version 6.1.4.1 fl 00ft I DESIGNED APPURTENANCE LOADING TYPE N WIRE ELEVATION 6Li9hwite Rod Plaffon MOM ILP 712-1] 63 60 RRH700MHZ N RRHAWS 60 77200 w/Mount Pipe 60 RRHAWS 60 7]22.00 W/ NOW Pipe 60 RRHAWS 60 n 60 8110.10 60 7762.00 W/ Mount Pipe 80 8110.10 TO 7762.00 w/ MOM Pipe 60 0110.10 60 7762.00 w/ Mount Pipe 60 LGP18601 60 S13NHH-1D65Gwl Mourn Pipe 60 LGP16 01 60 8BNHH-1D00wl Mourn Pipe 60 LGP18WI 60 S13NHH-1D650w1Mourn Pipe fig DC648-60.16 BF SLrge Suppression 60 Unit p 60 RRH 700 MHZ fig � 0 a � N � c 0 � fl 00ft I DESIGNED APPURTENANCE LOADING TYPE ELEVATION WIRE ELEVATION 6Li9hwite Rod Plaffon MOM ILP 712-1] 63 60 RRH700MHZ N RRHAWS 60 77200 w/Mount Pipe 60 RRHAWS 60 7]22.00 W/ NOW Pipe 60 RRHAWS 60 7722.00 W/ Mount Pipe 60 8110.10 60 7762.00 W/ Mount Pipe 80 8110.10 TO 7762.00 w/ MOM Pipe 60 0110.10 60 7762.00 w/ Mount Pipe 60 LGP18601 60 S13NHH-1D65Gwl Mourn Pipe 60 LGP16 01 60 8BNHH-1D00wl Mourn Pipe 60 LGP18WI 60 S13NHH-1D650w1Mourn Pipe fig DC648-60.16 BF SLrge Suppression 60 Unit RRH 700 MHZ 60 RRH 700 MHZ fig (3) RRIAWO-19 VA:4ARGrWe) 60 IOWA 4A11*ilcli!VIs) i* - 1. Tower is located in Madison County, Idaho. 2. Tower designed for Exposure C to the TIA-222-G Standard. 3. Tower designed for a 89 mph basic wind in accordance with the TIA-222-G Standard. 4. Deflections are based upon a 60 mph wind. 5. Tower Structure Class If. 6. Topographic Category 1 with Crest Height of 0.00 it 7. TOWER RATING: 26.8% 011 ALL REACTIONS AREFACTORED MAX. CORNER REACTIONS AT BASE: DOWN: 46 K SHEAR: 5 K UPLIFT: -37K SHEAR: 4 K AXIAL 12K SHEAR MOMENT 9 K 361 kip -ft TOROUE2kip-R REACTIONS- 89 mph WIND GPD eb: Rexbur i RT • BU #: 857594 South main treet, Ste 2531 ®A&A Akron, OH GPo Phone: (330) 572-2100 FAX: 330 572-2101 Pmlw- cliem: Crown Castle 0r nby:ESchnaus Apr& Cotla' TIA-222-G Da'e: 09/03/15 scale: NTS Patb'\NKPNe 40KMLEOO Omn 575%i01\WAeersNq D,V9 NO. E-1 c 0 :a m w w Feed Line Distribution Chart 0'- 60' Round Flat App In Face App Out Face Truss Lep Face A Face B Face C GPD oo Rexbur WT - BU #: 857599 South atn treet, to "MA Akron, OH GPD Phone: (330) 572-2100 FAX: 330 572-2101 P'"1"e2Qf577Tes7 cllem: Crown Castle Drawn by,. ESchnaus ^pye: tea' TIA-222-G Dare: 09/03/15 �d1a NTS ""': % AN0s wmtreLFwunuom„asrssa rwxanssa,a De" Ne --7 Tower Job Page G*nxl Rexburg—WT - BU #: 857594 1 of 8 GPD Project Date 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, OH Client Designed by Phone: (330) 572-2100 Crown Castle ESchnaus FAX: (330) 572-2107 Tower Input Data The main tower is a 3x free standing tower with an overall height of 60.00 ft above the ground line. The base of the tower is set at an elevation of 0.00 ft above the ground line. The face width of the tower is 4.58 ft at the top and 10.00 ft at the base. This tower is designed using the TIA-222-G standard. The following design criteria apply: Tower is located in Madison County, Idaho. Basic wind speed of 89 mph. Structure Class B. Exposure Category C. Topographic Category 1. Crest Height 0.00 ft. Deflections calculated using a wind speed of 60 mph. A non-linear (P -delta) analysis was used. Pressures are calculated at each section. Stress ratio used in tower member design is 1. Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered. Consider Moments - Legs Consider Moments - Horizontals Consider Moments - Diagonals Use Moment Magnification Use Code Stress Ratios Use Code Safety Factors - Guys Escalate Ice Always Use Max Kz Use Special Wind Profile Include Bolts In Member Capacity Leg Bolts Are At Top Of Section Secondary Horizontal Braces Leg Use Diamond Inner Bracing (4 Sided) Add IBC .6D+W Combination Options Distribute Leg Loads As Uniform Assume Legs Pinned Assume Rigid Index Plate Use Clear Spans For Wind Area Use Clear Spans For IGJr Retension Guys To Initial Tension Bypass Mast Stability Checks Use Azimuth Dish Coefficients Project Wind Area of Appurt. Autocalc Torque Ann Areas SR Members Have Cut Ends Sort Capacity Reports By Component Triangulate Diamond Inner Bracing Use TIA-222-0 Tension Splice Capacity Exemption Treat Feedline Bundles As Cylinder Use ASCE 10 X -Brace Ly Rules J Calculate Redundant Bracing Forces Ignore Redundant Members in PEA SR Leg Bolts Resist Compression 4 All Leg Panels Have Same Allowable Offset Girt At Foundation J Consider Feedline Torque J _Include Angle Block Shear Check , Include Shear -Torsion Interaction Always Use Sub -Critical Flow Use Top Mounted Sockets Tower Section Geometry Tower Tower Assembly Description Section Number Section Section Elevation Database Width of Length Sections T2 40.00-20.00 T3 20.00-0.00 6R➢1 Tower Section Geometry cont'd KIX031l Tower Tower Diagonal Bracing Has Has Top Gin Bottom Girt Section Elevation Spacing Type KBrace Horizontals Offset Offset End ft ft Panels in in Tl 60.00-40.00 4.00 X Brace No Steps 0.0000 0.0000 Tower Job Page brf.M Rexburg -WT - BU #: 857594 2 of 8 GPD Project Date 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, OH Client Designed by Phone: (330)572-2100 Crown Castle ESchnaus FAX: (330) 572-2101 A36 Tower Tower Diagonal Bracing Has Has Top Gin Bottom Girt Section Elevation Spacing Type KBrace Horizontals Offset Offset End 12 40.00-20.00 5.00 X Brace No Steps 0.0000 0.0000 T3 20.00-0.00 5.00 XBrace No Steps 0.0000 0.0000 Tower Section Geometry cont'd Tower Leg Leg Leg Diagonal Diagonal Diagonal Elevation h Type Size Grade Type Size Grade Tl 60.00-40.00 Solid Round 23/4 A572-50 Equal Angle L2x2x3/16 A36 (50 ksi) (36 ksi) 12 40.00-20.00 Solid Round 3 A572-50 Equal Angle L2x2x3/16 A36 (50 ksi) (36 ksi) T3 20.00-0.00 Solid Round 3 A572-50 Equal Angle L2 1/2x21/2xl/4 A36 (50 ksi) (36 ksi) Tower SectionGeometry cont'd Tower Top Gin Top Girt Top Girt Bottom Gin Bottom Girt Bottom Gin Elevation Type Size Grade Type Size Grade ft TI 60.00-40.00 Equal Angle L2x2x3/16 A36 Solid Round A36 (36 ksi) (36 ksi) Tower Section Geometry cont'd Tower Gusset Gusset Gusset Grade Adjust. Factor Adjust. Weight Mult. Double Angle Double Angle Elevation Area Thickness Ar Factor Stitch Bolt Stitch Bolt (perface) A, Spacing Spacing Diagonals Horizontals ft ft' in in in T160.00-40.00 0.00 0.0000 A36 1 1 1 36.0000 36.0000 (36 ksi) T2 40.00-20.00 0.00 0.0000 A36 I 1 1 36.0000 36.0000 (36 ksi) T3 20.00-0.00 0.00 0.0000 A36 I 1 1 36.0000 36.0000 (36 ksi) Tower Section Geometry cont'd K Factors Tower Calc Calc Legs X K Single Girts Hartz. Sec. Inner Elevation K K Brace Brace Diags Ho HL Brace Single Solid Diags Diags Angles Rounds X X X X X X X ft Y Y Y Y Y Y Y TI No No 1 1 1 1 1 1 1 1 60.00-40.00 1 1 1 1 1 1 1 T2 No No 1 1 1 1 1 1 1 1 40.00-20.00 1 1 1 1 1 1 1 T3 20.00-0.00 No No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Note: Kfactors are applied to member segment lengths. K -braces without inner supporting members will have the K factor in the out -of -plane direction applied to the overall length. h"Tower Job Page Top Girt Rexburg -WT - BU #: 857594 3 of 8 GPD Project Date 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, OH Client Designed by Phone: (330)572-2100 Crown Castle ESchnaus FAX: (330) 572-2101 Net U Tower Section Geometry cont'd Tower Elevation ft Leg Diagonal Top Girt Bottom Girt Mid Gin Long Horizontal Short Horizontal Long Horizontal Net Width U Net Width U Net Width U Net U Net U Net U Net U in Deduct Deduct in Deduct Width in Width T1 60.00-40.00 Width 0.8750 Width 0.6250 1 0.6250 1 in in 0.6250 0 in Deduct 0.6250 Deduct 3 Deduct A325N Deduct A325N A325N A325N No A325N A325N in A325N in T2 40.00-20.00 in 1.2500 in 0.6250 1 TI 60.00-40.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T2 40.00-20.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T3 20.00-0.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 Tower Section Geometry cont'd Tower Elevation ft Leg Connection 7'pe Leg Bolt Size No. Diagonal Top Girt Bottom Gin Mid Girt Long Horizontal ShortHorizontal Bok Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Offset Offset in Per in in in 2.00 in in in in T1 60.00-40.00 Flange 0.8750 4 0.6250 1 0.6250 1 0.6250 0 0.6250 0 0.6250 0 0.6250 0 3 3 A325N 0.0000 A325N A325N A325N No A325N A325N 2,5000 A325N 1 T2 40.00-20.00 Flange 1.2500 6 0.6250 1 0.6250 0 0.6250 0 0.6250 0 0.6250 0 0.6250 0 1.0900 1.0900 A325N Feedline Ladder (At) A325N A325N A325N 60.00-8.00 A325N A325N 1 A325N 3.0000 T3 20.00-0.00 Flange 0.7500 0 0.7500 1 0.6250 0 0.6250 0 0.6250 0 0.6250 0 0.6250 0 4.81 Safetv Line (3/8') A325N No A325N A325N A325N 0 A325N A325N 0.3750 A325N 0.22 Feed Line/Linear Appurtenances - Entered As Round Or Flat Description Face Allow Component Placement Face Lateral # # Clear Width or Perimeter Weight CAAA Weight or Shield Type or Offset Offset Side Per Spacing Diameter 2.00 Leg ft in (Frac FW) ft, K Row in in in alf LDF2-50A (3/8 FOAM) B No At (CaAa) 60.00-8.00 2.5000 -0.05 3 3 0.4400 0.0000 0.08 LDF4-50A (1/2 FOAM) B No At (CaAa) 60.00-8.00 2,5000 -0.1 1 1 0.6300 0.0000 0.15 LDF5-50A (7/8 FOAM) B No At (CaAa) 60.00-8.00 0.0000 0 20 14 1.0900 1.0900 0.33 Feedline Ladder (At) B No At (CaAa) 60.00-8.00 0.0000 0 1 1 3.0000 3.0000 8.40 Climbing Ladder (At) C No Af (CaAa) 60.00-0.00 0.0000 0 1 1 3.8400 3.8400 4.81 Safetv Line (3/8') C No At (CaAa) 60.00-0.00 0.0000 0 1 1 0.3750 0.3750 0.22 Platform Mount [LP 712-1) Discrete Tower Loads 0.0000 60.00 No Ice 24.53 24.53 1.34 7722.00 w/ Mount Pipe A From Leg 4.00 0.0000 CAAA Weight Description Face Offset Offsets: Azimuth Placement CAAA or Type Harz Adjustment Front Side Leg Lateral 2.00 Vert ft ft ft, ft, K 0.0000 ft k No Ice 5.80 5.39 0.06 6' Lightning Rod C From Leg 0.00 0.0000 63.00 No Ice 0.45 0.45 0.01 0.00 0.00 Platform Mount [LP 712-1) C None 0.0000 60.00 No Ice 24.53 24.53 1.34 7722.00 w/ Mount Pipe A From Leg 4.00 0.0000 60.00 No Ice 5.80 5.39 0.06 0.00 2.00 7722.00 w/ Mount Pipe B From Leg 4.00 0.0000 60.00 No Ice 5.80 5.39 0.06 0.00 2.00 tnxTower Job Page Offsets: Rexburg-WT - BU #: 857594 4 of 8 GPD Project Date 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, OR Client Designed by Phone: (330)572-2100 Crown Castle ESchnaus FAX:(330)572-2101 Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight or Type Harz Adjustment Front Side Leg Lateral Vert N ft .f2 .ft, K ft h 7722.00 w/ Mount Pipe C From Leg 4.00 0.0000 60.00 No Ice 5.80 5.39 0.06 0.00 2.00 7762.00 w/ Mount Pipe A From Leg 4.00 0.0000 60.00 No Ice 6.81 3.16 0.06 0.00 3.00 7762.00 w/ Mount Pipe B From Leg 4.00 0.0000 60.00 No Ice 6.81 3.16 0.06 0.00 3.00 7762.00 w/ Mount Pipe C From Leg 4.00 0.0000 60.00 No Ice 6.81 3.16 0.06 0.00 3.00 SBNHH-1D65C w/ Mount Pipe A From Leg 4.00 0.0000 60.00 No Ice 11.35 9.08 0.07 0.00 1.00 SBNHH-1D65C w/ Mount Pipe B From Leg 4.00 0.0000 60.00 No Ice 11.35 9.08 0.07 0.00 1.00 SBNHH-1D65C w/ Mount Pipe C From Leg 4.00 0.0000 60.00 No Ice 11.35 9.08 0.07 0.00 1.00 RRH 700 MHZ A From Leg 4.00 0.0000 60.00 No Ice 2.49 2.21 .0.05 0.00 1.00 RRH 700 MHZ B From Leg 4.00 0.0000 60.00 No Ice 2.49 2.21 0.05 0.00 1.00 RRH 700 MHZ C From Leg 4.00 0.0000 60.00 No Ice 2.49 2.21 0.05 0.00 1.00 RRH AWS A From Leg 4.00 0.0000 60.00 No Ice 2.51 1.59 0.04 0.00 1.00 RRH AWS B From Leg 4.00 0.0000 60.00 No Ice 2.51 1.59 0.04 0.00 1.00 RRH AWS C From Leg 4.00 0.0000 60.00 No Ice 2.51 1.59 0.04 0.00 1.00 8110.10 A From Leg 4.00 0.0000 60.00 No Ice 0.20 0.25 0.00 0.00 2.00 8110.10 B From Leg 4.00 0.0000 60.00 No Ice 0.20 0.25 0.00 0.00 2.00 8110.10 C From Leg 4.00 0.0000 60.00 No Ice 0.20 0.25 0.00 0.00 2.00 LGPI8601 A From Leg 4.00 0.0000 60.00 No Ice 0.70 0.28 0.01 0.00 3.00 LGPI8601 B From Leg 4.00 0.0000 60.00 No Ice 0.70 0.28 0.01 0.00 3.00 LGP18601 C From Leg 4.00 0.0000 60.00 No Ice 0.70 0.28 0.01 0.00 3.00 tnx ower Job Page Offsets: Rexburg_WT - BU #: 857594 5 of 8 GPD Project Data 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, GH Client Designed by Phone: (330) 572-2100 Crown Castle ESchnaus FAX: (330) 572-2101 Leg 0.201 Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight Load or Type Harz Adjustment in Front Side ° Tl Leg 0.201 Lateral 0.0226 0.0053 T2 40-20 0.104 26 0.0181 0.0028 Vert 20-0 0.031 26 0.0104 0.0009 Wind ft ft ft= ft2 x ft h DC6-48-60-18-8F Surge Suppression Unit A From Leg 4.00 0.0000 60.00 No Ice 1.47 1.47 0.02 0.00 3.00 (3) RRH2x60-1900A-4R (G -code) A From Leg 4.00 0.0000 60.00 No Ice 1.87 1.27 0.05 0.00 3.00 Maximum Tower Deflections - Service Wind Section Elevation Harz. Gov. Tilt Twist No. Radius of Deflection Load Twist Load ft in Comb. Comb. in oft ° Tl 60-40 0.201 26 0.0226 0.0053 T2 40-20 0.104 26 0.0181 0.0028 T3 20-0 0.031 26 0.0104 0.0009 Section Critical Deflections and Radius of Curvature - Service Wind Harz. Gov. Tilt Twist No. Radius of Elevation Appurtenance Gov. Deflection Tilt Twist Load ft Curvature ft Comb. in oft Tl 63.00 6 Lightning Rod 26 0.201 0.0226 0.0053 854957 60.00 Platform Mount [LP 712-1] 26 0.201 0.0226 0.0053 854957 2 0.0628 0.0098 T3 20-0 0.108 2 0.0361 Maximum Tower Deflections - Design Wind Section Elevation Harz. Gov. Tilt Twist No. Deflection Load ft in Comb. oo Tl 60-40 0.697 2 0.0772 0.0187 T2 40-20 0.362 2 0.0628 0.0098 T3 20-0 0.108 2 0.0361 0.0032 Critical Deflections and Radius of Curvature- Design Wind Elevation Appurtenance Gov. Deflection Tilt Twist Radius of Load Curvature WxTower Job Page 6 Rexburg_WT - BU #: 857594 6 of 8 Project Date GPD 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, OH Client Designed by Phone: (330) 572-2100 Crown Castle ESchnaus FAX: (330) 572-2101 Load Ratio Bolt Design Data Section Elevation Component Bolt Bolt Size Number Maximum Allowable Ratio Allowable Criteria No. 3.66 Type Grade -1.54 Of Load per Load Load Ratio ft K=1.00 ft ft in Bolts Bolt K Allowable 60-40 23/4 20.03 4.01 69.9 5.9396 -15.72 186.96 K K=1.00 Tl 60 Leg A325N 0.8750 4 3.05 40.59 3 1 Bolt Tension 80.1 7.0686 -29.87 198.96 0.150' V/ 0.075 K=1.00 Diagonal A325N 0.6250 1 1.53 6.83 ✓ 1 Member Block -43.85 198.96 0.220' 0.224 Shear V/ Top Girt A325N 0.6250 1 0.51 6.83 1 Member Block 0.074 1✓ Shear T2 40 Leg A325N 1.2500 6 4.03 82.83 1 Bolt Tension 0.049 Diagonal A325N 0.6250 1 1.83 6.83 1 Member Block 0.268 Shear T3 20 Diagonal A325N 0.7500 1 2.02 11.96 1 Member Block 0.169 Y Shen Compression Checks Leg Design Data (Compression) Section Elevation Size L L. Kl/r A P„ �P„ Ratio No. 7.39 3.66 111.7 0.7148 -1.54 12.01 0.128 P„ ft K=1.00 ft ft in' K K�P� 9.41 Tl 60-40 23/4 20.03 4.01 69.9 5.9396 -15.72 186.96 0.084' K=1.00 V/ K=1.00 L2 1/2x2 1/2x1/4 10.98 5.48 V/ 72 40-20 3 20.03 5.01 80.1 7.0686 -29.87 198.96 0.150' V/ K=1.00 V/ T3 20-0 3 20.03 5.01 80.1 7.0686 -43.85 198.96 0.220' K=1.00 V/ P. / OP„ controls Diagonal Design Data (Compression) Section Elevation Site L L„ Kl/r A P. Ratio No. P, ft ft ft in' K Kp� Tl 60-40 L2x2x3/16 7.39 3.66 111.7 0.7148 -1.54 12.01 0.128 K=1.00 V/ T2 40-20 L2x2x3/16 9.41 4.69 142.9 0.7148 -1.86 7.91 0.235' K=1.00 V/ T3 20-0 L2 1/2x2 1/2x1/4 10.98 5.48 133.8 1.1900 -2.06 15.01 0.137' K=1.00 V/ P„ / QP„ controls ower Job Page .L Rexburg --WT - BU #: 857594 7 of 8 GPD Project Date 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, OR Client Designed by Phone: (330) 572-2100 Crown Castle ESchnaus FAX: (330) 572-2101 L2x2x3/16 4.58 4.35 132.7 0.7148 Top Girt Design Data (Compression) Section Elevation Size L L. KI1r A P„ $P„ Ratio No. K 'P� TI 60-40 23/4 P„ ft ft ft in' K K �pn Tl 60-40 L2x2x3/16 4.58 4.35 132.7 0.7148 -0.55 9.17 0.060 K=1.00 72 40-20 3 V P„ / �P„ Controls Tension Checks Leg Design Data (Tension) Section Elevation Size L L. KI1r A P„ gyp„ Ratio No. P.. ft Size L f2 ft $P„ int K K 'P� TI 60-40 23/4 20.03 4.01 69.9 5.9396 12.21 267.28 0.046 TI 60-40 L2x2x3/16 4.58 4.35 84.6 0.4307 0.51 18.73 - 0.027 V 72 40-20 3 20.03 5.01 80.1 7.0686 24.20 318.09 0.076' V T3 20-0 3 20.03 5.01 80.1 7.0686 35.56 318.09 0.112' W, P„ l �P„ Controls Diagonal Design Data Tension Section Elevation Size L L. Kilt A P. OP„ Ratio No. P, ft 72 40-20 L2x2x3/16 T3 20-0 L2 l/2x21/2xl/4 P„ l �Pn controls ft ft in' K K 1��J{iittttttttt�EtF�lxlijlj] 9.41 4.69 91.2 0.4307 10.98 5.48 85.5 0.7284 V 1.83 18.73 0.098' V 2.02 31.69 0.064' 6/ Top Girt Design Data Tension Section Elevation Size L L„ KI1r A R, $P„ Ratio No. P„ ft ft ft int K KP TI 60-40 L2x2x3/16 4.58 4.35 84.6 0.4307 0.51 18.73 - 0.027 t/ P„ / �P„ Controls L owed" Job Page Section Capacity Rexburg—WT - BU #: 857594 8 of 8 GPD Project Date 520 South Main Street, Ste 2531 2015777.857594.01 14:35:55 09/03/15 Akron, OR Client Designed by Phone: (330)572-2100 Crown Castle ESchnaus FAX: (330) 572-2101 Section Capacity Table Pass Section Elevation Component Size Critical P OPaam, % No. .t Type Element K K Capacity Fail Tl 60-40 Leg 23/4 3 -15.72 186.96 8.4 Pass T2 40-20 Leg 3 39 -29.87 198.96 15.0 Pass T3 20-0 Leg 3 66 -43.85 198.96 22.0 Pass TI 60-40 Diagonal L2x2x3/16 9 -1.54 12.01 12.8 Pass 22.4 (b) T2 40-20 Diagonal L2x2x3/16 42 -1.86 7.91 23.5 Pass 26.8 (b) T3 20-0 Diagonal L21/2x21/2xl/4 69 -2.06 15.01 13.7 Pass 16.9 (b) TI 60-40 Top Girt L2x2x3/16 4 -0.55 9.17 6.0 Pass 7.4 (b) Summary BLO LC5 Leg (13) 22.0 Pass Diagonal 26.8 Pass (T2) Top Gin 7.4 Pass (T1) Bolt Checks 26.8 Pass Rating= 26.8 Pass 60 It Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594.01, Application 307869, Revision 1 CCI BU No 857594 Page 8 APPENDIX B BASE LEVEL DRAWING tnxTower Report - version 6.1.4.1 @ J ii55 a 9�$� W O ��e �� � � m � � � � W Q 60 ft Self Support Tower Structural Analysis September 03, 2015 Project Number 2015777.857594.01, Application 307869, Revision 1 CCI BU No 857594 Page 9 APPENDIX C ADDITIONAL CALCULATIONS tnxTower Report - version 6.1.4.1 Anchor Rod Check for Self Supporting Towers TIA-222-G, Section 4.9.9 Site Data BU#:857594 Site Name: REXBURG WT App #:1307869 Rev1 Anchor Rod Data Qty: < 4 Dlam: ' 1.5 in Rod Material: A36 Strength (Fu): 58 ksi Yield (Fy): 36 ksi Rod Circle: I in e: in * # of Rods 1 11 or 2 Mu= Pu x e: ft-ki s Only enter rod circle, offset (e) and number of anchor rods at the extreme fiber to consider if eccentric load due to leg reinforcement exist. A ° A a6 SECTION A -A SECTION a -a Detail Type (a) Detail Type (b) rt=o•^va n • o-�o o ° Cmpeb l-JOf0u1 CPIG.OV LTJ SECTION C -C SECTION D -D Detail Type (c) Detail Type (d) WO I OM) Figure 4.4 of TIA-222-G Rev. 6.1 111/ U CASTLE Reactions Eta Factor, q 1 0.5 Detail Type Down load Pu:1 46 Ikips Shear, VuA 5 Ikips er m Mu = 0.65*Ie,*Vu ft -kips Anchor Rod Results: Max Rod (Cu+ Vu/ftj14.0 Kips Design Axial, O*Fu*Anel: 65.4 Kips Anchor Rod Stress Ratio: 21.4% If Applicable; Anchor Rod Results with Bendina Considered: When the clear distance from the top of concrete to the bottom of level nut excceeds 1.0 times the diameter of the anchor rod, the following interaction equation shall also be satisfied (see Figure 4-4 of Rev. G): (VJ0Rm)2 + i(PJORnt) + (Mu/$Rna < =1 QRm=¢*0.45*Fub*Ab= kips 0Rnt=0*Fu*Anet= kips ORnm=¢*Fy*Z= ft -kips Maximum Acceptable Ratio: <' 105 % Governing Stress Ratio: 21.4% Pass SST Anchor Rod Check For Rev G -Rev 6.1 091912.xis Moment Capacity of Drilled Concrete Shaft (Caisson) for TIA Rev F or G Note: Shaft assumed to have ties, not spiral, transverse reinforcing Site Data BU#: 857594 Site Name: REXBURG WT App #: 307869 Rev. 1 Loads Alread Factored or For P (DL) Max Pu = ((p=0.65) Pn. Pn per ClA318 10-2 <---- Disregard <----Disregard 1:3 Pier Diameter = 3:0 ft Concrete Area = 1017.9 int Reinforcement: Clear Cover to Tie -F-3-0-0 " lin Horiz. Tie Bar Size= - 4' Vert. Cage Diameter = 2.35 ft Vert. Cage Diameter = 28.25 in Vertical Bar Size =0 Bar Diameter = 0.75 in Bar Area = 0.44 int Number of Bars =0 As Total= 3.52 int A ACI 10.5 , ACI 21.10.4, and IBC 1810. Min As for Flexural. Tension Controlled. Shafts: (3) * (S q rt(f'c)/Fy: 0.0027 200 / Fy: 0.0033 Minimum Rho Check: Actual Req'd Min. Rho:j 0.330/1 Flexural Provided Rho:j 0.35% OK Ref. Shaft Max Axial Capacities, m Max(Pn or Tn): Max Pu = ((p=0.65) Pn. Pn per ClA318 10-2 -kips (* Note) kips 14` "ft 1454.86 [kips at Mu=($=o.65)Mn= 373.75 ft -kips 0:003 ACI 318 Code Max Tu, =0.9 Tn =1 190.08 Ikips at Mu=(�=(0.90)Mn= 0.00 ft -kips Maximum Shaft Superimposed Forces TIA Revision: Max. Factored Shaft Mu: Max. Factored Shaft Pu: Max Axial Force Type: G -kips (* Note) kips 14` "ft 37, . : Tension Note: Max Shaft SuperimposedMoment Toes not necessarily equal to the shaft top reaction moment Load Factor Shaft Factored Loads 1.00 Mu: 1.00 Pu: 14 ft -kips kips 37 Material Pro erties Concrete Comp. strength, f'c = 3000 psi Reinforcement yield strength, Fy =1 60- - :ksi Reinforcing Modulus of Elasticity, E _ 29000 ' ksi Reinforcement yield strain = 0.00207 Limitingcompressive strain = 0:003 ACI 318 Code Select Analysis ACI Code= 2008 Seismic Properties Seismic Design Category =0 Seismic Risk = Low Solve <-- Press Upon Completing All Input Run Results: Governing Orientation Case: 2 Mu Case 1 E Mu T I � Case 2 Dist. From Edge to Neutral Axis: Extreme Steel Strain, et: et > 0.0050, Reduction Factor,(p: 4.16 in 0.0194 Tension Controlled 0.900 Output Note: Negative Pu=Tension For Axial Compression, W Pn = Pu: -37.00 kips Drilled Shaft Moment Capacity, (pMn: 194.53 ft -kips Drilled Shaft Superimposed Mu: 14.00 ft -kips (Mu/(pMn, Drilled Shaft Flexure CSR: 7.2% Drilled -Shaft -Moment -Capacity, DSMC, Version 1.1 - Effective 04/01/ 2010 Analysis Date: 9/3/2015 AxMat Foundation Analysis Rexburg_WT - BU #: 857594 GPD GROUP 2015777.857594.01 Moment,M j'381k-ft "+;12ik Code >"± TIA°'2C3T',x Y Qxmax 1.68 ksf 1.2D+1.6W Bearing On �, .,-r` '-Ftoc�i Qymax 1.68 ksf 1.21)+1.6W Foundation Type s�5,$ Pfd `�-,. Qmax @ 45° 2.09 ksf 1.2D+1.6W Pier Type '' iFl#ond r"ell Gross 18.00 ksf Reinforcing Known fi .3„�'lot r: Controlling Capacity 11.6% Pass Moment,M j'381k-ft "+;12ik Y k Pier Diameter, 0 Pad Length, L Pad Width,W Pad Thickness, t Depth, D Rebar Fy Concrete Fc' Clear Cover Reinforced Top & Bottom? Pad Reinforcing Size Pad Quantity Per Layer Pier Rebar Size Pier Quantity of Rebar Soil Unit Weight Angle of Friction, 0 Bearing Type Ultimate Bearing Water Table Depth Frost Depth GPD Mat Foundation Analysis - V1.02 ft ksi ksi in pcf ksf FS(ot)x 4.28 21.0 0.9D+1.6W FS(ot) 4.28 a1.0 0.9D+1.6W Controlling Capacity 23.4% Pass LxW HG X,