Loading...
HomeMy WebLinkAboutREVIEW RESPONSE BUILDING - 16-00579 - Gorilla Performance New BuildingReview Date: 09/14/2016 35 North Id East Rexburg, ID 83440 Reviewed By: Quinton Owens Gorilla Performance New Building Permit Number: 16-00579 Building Review amandosgrexburg.org Phone: 208.359.3020 www.rexburg.org Fox:208.359.3022 C IT Y OF REXBURG Ameriml Family Cnmmun't' Current Building Review Status: REVISIONS DESCRIPTION C Use classification is shown on plans as per Not Identified (no code summary). REVISIONS IBC Section 302 Plans titled "Storage" (default as S-1). Building height and area meets the REVISIONS requirements of IBC Section 500 & Table Sprinkler system not noted, and area 503 exceeds allowed area in table 503 for V -B construction. "Storage" building Mixed use occupancies meet the COMPLETED requirements of IBC Section 508 and Table 508.4 Incidental use meets the requirements of COMPLETED Table 508.2.5 Fire resistance rating of building elements 0 hour rating for V -B (no construction type REVISIONS meet the req. of IBC Sect 703, 704 identified on plans). Exceeds allowed area. Automatic sprinklers are provided or Not Identified. NFPA 13 required for area REVISIONS exempted as per IBC Section 903.2 increase to Table 503. Occupant load is identified on plans as per 22 occupants based on section 1004 COMPLETED IBC Section 1004 Toilets, Bathing Fac., Sinks, Kit. and Drink. No details of accessible restrooms (must COMPLETED Fount. meet IBC Sec. 1109 meet all All 17.1 requirements). Structural Docs Identify snow, wind, seismic Design criteria is not identified. REVISIONS and other loads per IBC Chp. 16 Structural Docs or plans identify Occupancy Design criteria is not identified. REVISIONS Category as perIBC Table 1604.5 Site Grading meets the requirements of IBC Final grade required to slope away from COMPLETED Section 1804.3 building. Concrete Documentation provided as per No concrete specifications other than slab REVISIONS IBC Section 1901.4 (1500 psi). Slab concrete shall be 2500 psi min. per 1904.2. Concrete Reinforcement Identified on plans Shown but no stamped drawings. REVISIONS and designed by a licensed Engineer "Floor Slab ... with #4 bar on center each way" (what center?) Wood Fram. design. by lice. Eng. and No stamped drawings. REVISIONS meets. re s. IBC Chp. 23 or Conv. Li -Frame Glass and Glazing meets the requirements Window to Office (104) shall be tempered If COMPLETED of IBC Chapter 24 less than 24" from door as shown on plans. Spray booths meet the requirements of IBC Clarification needed: Is the "Booth" area for REVISIONS Section 416 painting. Review Date: 08/31/2016 35 North I a East Rexburg, ID 83440 Reviewed By: Joel Gray Gorilla Performance New Building Permit Number: 16-00579 Public Works Review - Site Plan amandasC�rexburg.org Phone: 208.359.3020 www,rexburg.org Fax: 208.359.3022 0 c rY o REXBURG America} family Community Current Public Works Review - Site Plan Status: REVISIONS DESCRIPTION 1 Plans are approved for a fooling/foundation NO ONLY permit? Street All approaches to be concrete per City REVISIONS Engineering Standards and Chapter 5 Section 1.5.a.v of the Development Code. Driveways to be ADA Compliant (no more than 2% cross slope). Street No loading/unloading area noted on plans REVISIONS per Chapter 5 Section 1.4 and Chapter 3 Sectlon20.130of the Development Code. Street No backing into right of way per Chapter 5 REVISIONS Section 1.5.a.viii of the Development Code. Street Trash enclosure must be 20 feet from right REVISIONS of way per Chapter 3 Section 20.150 of the Development Code. Water No meter location specified. REVISIONS Sewer Service Only. N/A Storm How will snow storage be accessed? REVISIONS Storm Retention area Is too small. REVISIONS Storm Driveway runoff to be retained on site. REVISIONS Lighting No site lighting Indicated on plans. Building N/A mounted lights to light parking area are not allowed. GORILLA PERFORMANCE NEW BUILDING CITY OF REXBURG PLAN REVIEW September 15, 2016 Buildina Review 1. No identified code summary. Response: See attached Drawing G1.2. 2. Building area exceeds that allowed. Sprinkler system not noted. Response: See area increase calculations allowing for 13,230 sq. ft. 3. Fire resistance rating meet IBC requirements. Response: See Code Review. Drawing G1.2 attached. 4. Automatic sprinklers required for area are not identified. Response: Automatic sprinklers not required. 5. Need design criteria for snow, wind, seismic and other loads. Response: See Sheet C1.2 6. Design criteria for occupancy not shown. Response: See Sheet C1.2 7. No concrete specifications other than slab. Response: See Sheet S1.1 8. No stamped floor slab drawings. Slab to have #4 bar on center which way? Response: Rebar to be #3 bar 24" oc each way. See Sheet S1.1. 9. No stamped drawings for wood framing. Response: See submitted truss engineered drawings. 10. Clarification for booth area needed. Response: Booth is a detail booth. Site Plan 1. All approaches to be concrete per City Engineering Standards. Response: See attached Drawing S01.1 2. No loading or unloading area noted on plans. Response: See attached Drawing S01.1 3. No backing into Right of Way allowed. Response: See attached Drawing S01.1 4. Trash enclosure must be 20 feet from right of way. Response: See attached Drawing S01.1 5. No meter location specified. See Note 6 on Drawing S01.2 6. How will snow storage be handled? See Sheet S01.1 7. Storm retention area is too small. Response: Pending John Millar's feedback. 8. Driveway runoff to be retained on site. See Sheet S01.3 for valley gutter.