3-D Fire Protection has been contracted to install a CPVC Fire Sprinkler system for this project.
In compliance with the CPVC pipe manufacturer’s recommendations, we are hereby notifying all parties that
may be working around, or come in contact with the CPVC material on this project, of the precautions that must
be followed to ensure a defect free fire sprinkler system.
3-D Fire Protection will provide an installation that is in 100% compliance with these guidelines but cannot be
responsible for the willful or negligent actions of other parties. Should any party violate these requirements, said
party shall be financially responsible for any corrective actions required to repair the system as determined by
the CPVC manufacturer, local jurisdiction, General Contractor or Owner. Delta Fire Systems hereby expressly
disclaims any liability or responsibility for any damage caused by any violation of those requirements and
guidelines.
These guidelines are:
• DO NOT stack, support, hang equipment, or hang flexible wire/cable, especially communications cable,
or other material on the fire sprinkler system.
• DO NOT expose CVPC products to incompatible substances, such as cutting oils, non‐water‐based paints,
packing oils, traditional pipe thread paste and dope, fungicides, termiticides, insecticides, detergents,
bulking caulking, adhesive tape, solder flux, flexible wire/cable (with special consideration for
communications cabling), and non‐approved spray foam insulation materials.
• DO NOT expose CPVC products to edible oils, solvents, or glycol‐based anti‐freeze fluids.
• DO NOT expose CPVC products to open flame, solder, and soldering flux.
• DO NOT drop, distort, or impact CPVC products or allow objects to be dropped on them.
• DO NOT handle CPVC products with gloves contaminated with oils (hydrocarbons) or other incompatible
materials.
• DO NOT inject system with Microbiologically Controlled Corrosion (“M.I.C.”) inhibitors unless they are
listed in combination with this system.
Failure to follow this notice may cause cracks or fractures to develop in CPVC products resulting in the system
potentially not working properly in the event of a fire and/or property damage due to leaks or flooding. The
presence of any visible cracks may require partial of full system replacement.
For additional information contact 3-D Fire Protection.