HomeMy WebLinkAboutCOMCHECK - 16-00628, 629 - Sawtelle Apts - 18 Plex #1Envelope Compliance Certificate
Project information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Vertical Glazing / Wall Area:
Construction Site:
Rexburg, ID 83440
2012 IECC
146 N 1st W 18 Plex Apt
Rexburg, Idaho
6b
New Construction
9%
Owner/Agent:
Building Area Floor Area
1 -Dormitory: Nonresidential 9026
Additional Efficiency Package
Designer/Contractor:
Design Intelligence LLC
Rexburg, ID 83440
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Envelope Assemblies
Assembly
Gross Area
Cavity
Cont.
Proposed
Budget U -
or
R -Value
R -Value
U -Factor
Factor(a)
Perimeter
Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Dormitory]
3042
49.0
0.0
0.021
0.021
Exterior Wall 1: Wood -Framed, 16" o.c., [Bldg. Use 1 - Dormitory]
8534
21.0
0.0
0.062
0.051
Window 1: Vinyl/Fiberglass Frame:Operable, Perf. Specs.:. Product ID
756
--
--
0.290
- 0.430
Window, SHGC 0.70, [Bldg. Use 1 - Dormitory] (b)
Door 1: Insulated Metal, Swinging, [Bldg. Use 1 - Dormitory]
380
--
--
0.290
0.370
Floor 1: Slab-On-Grade:Unhealed, Vertical 2 ft., [Bldg. Use 1 -
336
--
10.0
0.540
0.550
Dormitory] (c)
(a) Budget U -factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation
(c) Slab -On -Grade proposed and budget U -factors shown in table are F -factors.
drre.pA.SSES: C7esidrr. ln.beit�rtttan rorfP
Envelope Compliance Statement
Compliance Statement. The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2012 IECC requirements in COMcheck Version 4.0.3.0 and to comply with the mandatory requirements
listed in the Inspection Checklist.
Name - Title
Date
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: S:\losh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 1 of 8
Comcheck.cck
COMcheck Software Version 4.0.3.0
Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
-Plan Review
,Complies? Comments/Assumptions
& Req:lq:
,.
... ..
C103.2
: Plans and/or specifications provide all
i❑Complies
[PR1]1
!information with which compliance
'❑Does Not
can be determined for the building
'..
❑Not Observable
envelope and document where
exceptions to the standard are❑Not
Applicable
claimed.
C406
Plans, specifications, and/or❑Complies
[PR9]1
(calculations provide all information❑Does
Not
:with which compliance can be
determined
'determined for the additional energy
Observable
efficiency package options.
'..❑Not Applicable
C402.31
:The vertical fenestration area <= 30
':.❑Complies
[PR10]1
'percent of the gross above -grade wall❑Does
Not
area.
❑Not Observable I
'!❑Not
Applicable
0402.3.1
The skylight area <= 3 percent of the❑Complies
[PR11]1
:gross roof area.
-❑Does Not
-]Not Observable
_
•:❑Not Applicable
0402.3.2.
iSkylights in office, storage,❑Complies
2
: automotive service, manufacturing,
❑Does Not
[PR15]1
non -refrigerated warehouse, retail
'..store,
Observable!
and distribution/sorting area❑Not
have a measured haze value > 90❑Not
Applicable j
percent unless designed to exclude
':.direct sunlight.
Additional Comments/Assumptions:
1 ;High Impact (Tier 1) 2`. Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: S:\losh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 2 of 8
Comcheck.cck
section '..
# Footing I Foundation Inspection
Complies?
Comments)Assumptions
'Slab edge insulation R-value,❑Complies
See the Envelope Assemblies table for values.��
r
❑Does Not
P
❑Not Observable:
4 'I;❑Not
Applicable
Gab 2 j Slab edge insulation installed per
I❑Complies
[ S FO4j .,manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
C4Q2_2„6; =, Slab edge insulation depth/length.
:-]Complies
_See the Envelope Assemblies table for values.
[FQ5: €.Slab insulation extending away from❑Does
Not
. building is covered by pavement or
inches
❑Not Observable
-
>= 10 of soil.
❑Not Applicable
C403.2.8. iExterior insulation protected against❑Complies
1 damage, sunlight, moisture, wind,❑Does
Not
[F06]1 landscaping and equipment
[]Not Observable'
maintenance activities.
❑Not Applicable
i
C402.2.8`. Bottom surface of floor structures❑Complies
•See the Envelope Assemblies table for values.
[FO12]3 - incorporating radiant heating
❑Does Not
insulated to >=R-3.5.
❑Not Observable'
❑Not Applicable
Additional Comments/Assumptions:
i 1 ;High Impact (Tier 1) '�?2ii Medium Impact (Tier 2) 3 I Low Impact (Tier 3) I
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: S:�josh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 3 of 8
Comcheck.cck
section-
#
Framing] Rough-In Inspection
Complies?
Comments/Assumptions
4i fieq.ID.
C402.4.1,
:The building envelope contains a
❑Complies
LL��
C402.4.2
continuous air barrier that is sealed in❑Does
Not
[FR16]1
Ian approved manner and either
❑Not Observable:
(constructed or tested in an approved
'..❑Not Applicable
manner. Air barrier penetrations are
'sealed
in an approved manner.
C402 4:3,
Factory-built fenestration and doors
❑Complies
C402.4.4 'are
labeled as meeting air leakage❑Does
Not
[FR18]3 -.,
requirements.
❑Not Observable;
_❑Not
Applicable
C402.4.7 ':.
Vestibules are installed on all building
'..❑Complies
[FR17]3 !entrances.
Doors have self-closing❑Does
Not
-.
devices.
❑Not Observable
❑Not Applicable
C402.3.3, 'Vertical
fenestration U-Factor.
!❑Complies _See
the Envelope Assemblies table For values.
C402.3.4❑Does
Not
[FR811
❑Not Observable -:
❑Not Applicable
C402.3.3 :Vertical
fenestration SHGC value.❑Complies
see the EnvelopeAssemblies table for values.
[FR10]1
❑Does Not
I❑Not Observable
❑Not Applicable
76p"3 i :`•({Fenestration
products rated in
❑Complies
-- ..------- - ---------- ----------- --- _._............
[Fg1.2]1 H.H,
accordance with NFRC.
❑Does Not
-- - ®"❑Not
Observable '..
151,❑Not
Applicable
C303.1.3
Fenestration products are certified as❑Complies
[FR13]1
to performance labels or certificates
-❑Does Not
provided.
I❑Not Observable :.
❑Not Applicable
O..4, ,:TRU-factor
...........................
of opaque doors associated
❑Complies ';See
the Envelope Assemblies table for values.
(Fi€141,=
with the building thermal envelope❑Does
Not
J� ° ]meets
Ali
requirements.
❑Not Observable,
_--
I❑Not Applicable
Additional Comments/Assumptions:
11 !High Impact (Tier 1);2 1 Medium Impact (Tier 2) 3 i Low Impact (Tier 3)
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: S:Vosh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 4 of 8
Comcheck.cck
C402.4.5. Stair and elevator shaft vents have❑Complies
1 .motorized dampers that automatically❑Does Not
[ME3]3 close. -]Not Observable
❑Not Applicable
C402,4.5. Outdoor air and exhaust systems have❑Complies
2: - :motorized dampers that automatically❑Does Not
[ME58]3 •shut when not in use and meet
- :maximum leakage rates. Check .(--]Not Observable:
gravity dampers where allowed. ❑Not Applicable
Additional Comments/Assumptions:
1 :High Impact (Tier 1) ���,!2';' Medium Impact (Tier 2)3 ILow Impact (Tier 3)
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: S:Uosh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 5 of 8
Comcheck.cck
C402.4.1. All sources of air leakage in the iLlComplies
1
building thermal envelope are sealed,❑Does
Not
[IN111
caulked, gasketed, weather stripped
'..
[IN711
or wrapped with moisture vapor -
permeable wrapping material to
---❑Not Applicable '..
r
minimize air leakage.
❑Not Observable '..
C402.4.2.
'Roof R -value. For some ceiling❑Complies
See the Envelope Assemblies table for values.
1
_systems, verification may need to❑Does
Not
[IN211
occur during Framing Inspection.❑Not
Observable::
_❑Not
Applicable '..
0303.2
[IN311
Roof insulation installed per
manufacturer's instructions. Blown or❑Does
poured loose -fill insulation is installed❑Not
only where the roof slope is <=3 in
X12.❑Not
'. UComplies
Not
Observable:
Applicable
C303.2
(Above -grade wall insulation installed❑Complies
'..
[IN711
per manufacturer's instructions.
❑Does Not
r
Insulation intended to meet the roof❑Complies
❑Not Observable '..
insulation requirements cannot be
-
-❑Not Applicable
,4'0Z;2-5J.'-M,'Floor
insulation R -value.
❑Complies See the Envelope Assemblies table for values.
G1N❑Does
Not
❑Not Observable
❑Not Applicable
O2F31 .'(Building
envelope insulation is labeled❑Complies
fIRK-079,!"-`; e
with R -value or insulation certificate
❑Does Not
;providing
HE MRF €R
R -value and other relevant❑
data
Not Observable
........... .:.;
.._.�.
:
.❑Not Applicable
Exterior insulation is protected from
:❑Complies
damage with a protective material.
❑Does Not
Verification for exposed foundation
Observable:
insulation may need to occur during❑Not
Applicable
Foundation Inspection.❑Not
r
Insulation intended to meet the roof❑Complies
insulation requirements cannot be
[]Does Not
installed on top of a suspended
Observable;
ceiling. Mark this requirement❑Not
❑Not Applicable
compliant if insulation is installed
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2:. Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: S:Vosh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 6 of 8
Comcheck.cck
C402.4.6 Weatherseals installed on all loading iLIComplies
[FI37]1
.dock cargo doors.❑Does
Not
j❑Not Observable'.
❑Not Applicable
C402.4.8
'..Recessed luminaires in thermal
❑Complies
[FI26]3
envelope to limit infiltration and be IC
❑Does Not
.rated and labeled. Seal between
❑Not Observable'.
interior finish and luminaire housing.
❑Not Applicable
C406
Efficient HVAC performance, efficient
.❑Complies
[FI34]1
.lighting system, or on-site supply of❑Does
Not
_renewable energy consistent with
.❑Not Observable
.what is shown the approved plans.
i❑Not Applicable j
Additional Comments/Assumptions:
1 ;High Impact (Tier 1) `,2Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: S:�osh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 7 of 8
Comcheck.cck
Project Title: 146 N 1st W 18 Plex Apt Report date: 09/01/16
Data filename: 5:\Josh\Year 2016\2016-120 146 N 1st West Apts\18 Plex\090116 146 N 1st W 18 Plex Apt Page 8 of 8
Comcheck.cck