HomeMy WebLinkAboutPRODUCT INFO - 17-00212 - 525 S Center St - Austin Building - Fire AlarmAUSTIN BUILDING HVAC UPGRADE
BYU-IDAHO
FIRE ALARM SYSTEM
INDEX
OF
DRAWINGS
PAGE
SHEET #
DESCRIPTI❑N
1
FA -C-01
PROJECT COVER SHEET / INDEX OF DRAWINGS NELSON FIRE SYSTEMS
2
FA -R-01
FIRE ALARM BUILDING RISER DIAGRAM / MATRIX NELSON FIRE SYSTEMS
3
FA -1-01
LEVEL 2- ADDRESSABLE / RELAY CIRCUITS NELSON FIRE SYSTEMS
DEVICE SCHEDULE
SYMBOL
DESCRIPTI❑N
PART NUMBER
MOUNTING
REQUIREMENT
9
DUCT DETECTOR w/SAMPLING TUBE
DNR w/DST-S
SUPPLIED
BY
NFS, FOLLOW MANUFACTURERS INSTRUCTI❑NS.
®
CONTROL MODULE
ADM-2SF
4 SQ, 2-1/8"
DEEP BOX MINIMUM
HORN/STROBE- WALL
EXISTING
EXISTING
TO
REMAIN
El
RELAY
PR -3
4 SQ. 2-1/8"
DEEP BOX MINIMUM
®
FIRE ALARM CONTROL UNIT
EXISTING
EXISTING
TO
REMAIN
®
TRANSPONDER
EXISTING
EXISTING
TO
REMAIN
O
a
'-uma a arca LL z
wino 2aa3wma
aaaa$aF>ow
r a i r o a
w=�
o�yfn�o3 � o z
a z o a z o
waww zusiwh3
mKal-LLNFLLNO
Z y
W
azNFaua uiz
z 3 o
w p LLLLO o ~
Z�~ } Z m a f
a a
oE=eEiiz-ooa a z
I N u rc~ o p z w
o m LL z' z N p v
zza Naz- r
Lu
Q
r cc
CL L
0w
u Lu Q 0 H Q
Zoi
W — (n
0 U =
Z H Q
J_o00mQ
D co X W
En L[) Ofo'
Z LL0 L-
H
N
D
Q
NIPS
NELSON FIRE SYSTEMS
801-468-8300
DRAWN BY: KLM
DESIGNED BY: XXXX
APPROVED BY: ZM
DATE: 4/14/2017
SCALE: (ANSI B) 1/16"=1'
PROJECT NO: XXXX
REV NO: XXXX
DRAWING NAME:
AUSTIN HVAC UPGRADE C.DWG
FIRE ALARM SYSTEM
COVER SHEET
PAGE
FA -C-01
FIRE ALARM INPUT/OUTPUT MATRIX
SYSTEM OUTPUTS
DESCRIPTI❑N
FACU
DUCT DETECTOR
FIRE
AUX.IG
I
HORN/STROBE
ANNUNCIATION
NOTIFICATION
SAFETY CONTROL
SNALS
REPORTING
Q
a��
_
0r
roa
a o
oz�
moo=
w a
¢ U, a
a o
p z o
z- -
oz o
o -
- � o
o
o z
SYSTEM INPUTS
~
a r z
z -
u o
a N 1
a r z
z -
u o
a a 'o
a , 11
LEVEL 2- DUCT DETECTORS
• • •
•
• lel •
LOSS OF POWER ANY PANEL OR NAC
•
•
LOW BATTERY CONDITIONS
•
•
OPEN CIRCUIT CONDITIONS
101 1
•
a
GROUND FAULTS
•-±�TFFFF
•
ADDRESSABLE CIF
1 PAIR #14'S TWI
LEVEL 2
T2l'L-'ZFbNLF 11- 1-11 O O O O
TO NLLIN o K CE OP NE NR3NAL LINE CHT LOOPNEXT OEV�CE
" SIGMA E CHT LOOP
FROM PREVIOUS DEVICE
ELo oNEI
IULTII VOL 0 VACNEU°
0 o
INT
ADM-2SF CCINTRCIL MCIDULE W/ PR -3 DNR 2 -WIRE DUCT SMOKE ➢ETECTCIR
DEVICE LEGEND
SYMBOL
DESCRIPTI❑N
DD
DUCT DETECTOR
❑R
RELAY
HS
HORN/STROBE
RATRANSP❑NDER
PANEL
Eg
I FIRE ALARM CONTROL UNIT
TO FAN TO FAN TO FAN TO FAN TO FAN TO FAN TO FAN TO FAN TO FAN
SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN
D❑ NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUIT
LEVEL 2
X
cQ
L
X: w
LJJ
Z
J Q
D
(L m Of
D Z WQ
Q m N Q
D LuQ
<
Q LL
J
Q
Lu
of
LL
NFS
NELSON FIRE SYSTEMS
801-468-8300
DRAWN BY: KLM
DESIGNED BY: XXXX
APPROVED BY: zM
DATE: 4/14/2017
SCALE: (ANSI B) 1/16"=1'
PROJECT N0: XXXX
REV NO: XXXX
DRAWING NAME:
BYU-1 AUSTIN RISER.DWG
FIRE ALARM SYSTEM
RISER DIAGRAM
PAGE:
FA -R-01
GENERAL NOTES;
I. INSTALLATION SHALL COMPLY WITH NEC, NEPA 72 AND ALL OTHER APPLICABLE
CODES AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. CLASS "A"
WIRING IS REQUIRED.
2. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY
DIFFER FROM THESE PLAN. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING
CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA
SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS
LONG AS NO 110V OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY.
3. POWER -LIMITED AND NONPOWER -LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED
IN CABINET. ALL POWER -LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25"
AWAY FROM ANY NONPOWER -LIMITED CIRCUIT HARING. FURTHERMORE, ALL
POWER -LIMITED AND NONPOWER -LIMITED CIRCUIT WIRING MUST ENTER AND EXIT
THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS.
4. SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL TESTING AND FINAL
INSPECTION ARE COMPLETED. DO NOT INSTALL SMOKE DETECTORS UNTIL BUILDING
IS CLEAN.
5 LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL
DIFFUSERS.
6. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS.
PROVIDE ALL REQUIRED SYNC MODULES. A MULTI -SYNC MODE SLAVE CONNECTION
BETWEEN ALL SYNC MODULES.
7. ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM CONDUIT. 11 OV OR HIGHER
VOLTAGE CABLES ARE NOT ALLOWED IN FIRE ALARM CONDUIT.
8. DO NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUITS.
9. FIRE ALARM CIRCUITS NEED TO BE FREE OF GROUNDS, FAULTS, AND SHORTS PRIOR
TO CONNECTION TO FIRE ALARM EQUIPMENT.
ID.A SMOKE DETECTOR MUST BE IN EVERY ROOM WITH A FIRE ALARM CONTROL UNIT,
POWER SUPPLY, OR ANNUNCIATOR.
11 -DEDICATED 120 VAC CIRCUITS WALL BE MARKED AS "FIRE ALARM CIRCUIT" AND BE
ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS FOR THESE CIRCUITS WILL BE RED
IN COLOR AND THEIR LOCATION WILL BE NOTED AT EACH CONTROL UNIT.
0' I 10' I 20' 25'
SCALE
SYSTEM NOTES:
<T> TO FACU
TO EXISTING TRANSPONDER IN ROOM 122
03 RELAY FOR FAN SHUTDOWN
® EXISTING HORN/STROBE TO REMAIN
A,C
0
0
0
4
0
0
0
DEVICE LEGEND
WIRE
SCHEDULE
NOTE
DESCRIPTION
WIRES
A
ADDRESSABLE CIRCUIT
i PAIR #14'S TWISTED
B
RELAY CIRCUIT
2 #14'S
C
24 VDC AUX POWER
2 #14'S
D
120 VAC POWER
3 #12'S
E
HORN/STROBE CIRCUIT
2 #14'S
F
REMOTE ANNUNCIAT❑R
3 PAIR #16'S TWISTED
A,C
0
0
0
4
0
0
0
DEVICE LEGEND
SYMBOL
DESCRIPTI❑N
DD
DUCT DETECTOR
Hs
HORN/STROBE
AC
FIRE ALARM CONTROL UNIT
RA
TRANSPONDER PANEL
KEY PLAN
7/,/
reCET.
f Vr� V
CEAiICdTIOY
H
t
IN
Y
w vizz r
J F O O
Z
r Na3os z
W awm�Noazo
N a t ILL W r W N N
Q VI r J j w� w 0
z W o r rr wo l z -. -
oQ w
oo>x-�zo www�raw�z
wx Jo
N
w�jZra`na�r
a ww ro Nyz�Z0
aoo
N W Z? Z Z Z U
Z. WaQQoo
_r rJ ��Zzm.
Z< - Z
M'E z o O W� w z a
.. U I U d Q r a 3 U o d
r fn U W N V Z W W> N W
o w rc
00 x x w
zzavai rrJurrorra
W
Q H
WIL Of
p
H W
U N o ~
Of O N
= O N I_ Q (n
p JZ 0
U i j W —
� W U
=a
o m Q
W
m O m of
Z_ N X LL
Lo W
N
Lo
Q
NFS
NELSON FIRE SYSTEMS
801-468-8300
DRAWN BY: KLM
DESIGNED BY: XXXX
APPROVED BY: XXXX
DATE: 4/14/2017
SCALE: (ANSI B) 1/16" = (-
PROJECT NO: XXXX
REVISION N0: XXXX
DRAWING NAME:
HVAC UPGRADE LEVEL 2. DWG
NELSON FIRE SYSTEMS
LEVEL 2
ADDRESSABLE
PAGE:
FA -1-01