HomeMy WebLinkAboutPLANS - 17-00212 - 525 S Center St - Austin Building - Fire Alarm FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 Austin Building HVAC Upgrade BYU-Idaho Fire Alarm System Submittal April 21, 2017 AUSTIN BUILDING HVAC UPGRADE BYU-IDAHO FIRE ALARM SYSTEM SUBMITTAL Equipment Manufacturer: Gamewell-FCI Authorized Distributor: Nelson Fire Systems 1481 South Major Street Salt Lake City, UT 84115 801-468-8300 Data Sheet Part No. Description Gamewell-FCI E3 Series Emergency Evacuation System (Existing) Gamewell-FCI AOM-2SF Addressable Control Module Gamewell-FCI DNR w/DST-5 Duct Detector Housing w/Sampling Tube Gamewell-FCI PR-3 Relay Gamewell-FCI HPFF8 NAC Power Supply (Existing) GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0637 Rev. O page 1 of 2 E3 Series® Control Panel SIGNALING Class 1 Class 2 High Rise S1869 Approved City of Denver City of Chicago ApprovedApproved 7165-1703:0125 3025415 APPROVED FM FDNY: COA-#6077 MEA Reference Certificate of Compliance VMA-45894-02C (Revision 1) Description The E3 Series® Expandable Emergency Evacuation Sys- tem by Gamewell-FCI is in the forefront of the latest gener- ation of fire alarm control panels. Employing the new high- speed Velociti® sensors, the E3 Series provides previously unattainable polling speed and response together with the flexibility demanded by today’s emergency evacuation sys- tems. In addition to their high-speed polling rate, the Veloc- iti Series of sensors feature bi-polar LEDs that flash green for normal polling, and light red steadily to indicate an alarm. The E3 Series is equipped with an 80-character LCD-E3 alphanumeric LCD display that allows 40 characters to be user-defined for custom installations. Up to six keyboard LCD displays may also be remotely located. In addition, you can install five of the familiar LCD-7100/RAN-7100 remote displays. The displays show instant system status information and can be connected in any desired area of an installation. A high-speed 32-bit processor easily tackles a wide array of applications from small office buildings to multi-complex, high-rise installations. The 64 node networking is made possible by 625K baud/ ARCNET communications using twisted-pair copper cable, fiber-optic cable, or a combination of both. In addition, the Addressable Node Expander (ANX) board expands the network to 122 nodes. The basic E3 Series is equipped with an ILI-MB-E3/ILI95- MB-E3 Intelligent Loop Interface-Main Board, ILI-S-E3/ ILI95-S-E3 Intelligent Loop Interface Expansion Board, ANX, and ASM-16 Addressable Switch Module that fea- tures 16 software programmable switches, each accompa- nied by red, green and yellow LEDs that can be programmed to indicate operation of the switches. Addi- tional ASM-16 modules may be added to expand the oper- ation to a plateau previously unimagined. The Intelligent Loop Interface - Expansion Board (ILI-S-E3/ ILI95-S-E3 provides the E3 Series control panel with two additional signaling line circuits. The layout is similar to the ILI-MB-E3/ILI95-MB-E3 with the exception that a number of components are omitted. It occupies one node on the Broadband network. E3 Series® and Velociti® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. Features • IBC Seismic Certified. • Listed under UL ® Standard 864, 9th Edition. • UL Listed for smoke control (dedicated and non-dedi- cated) when properly configured. • FM/UL Listed for Pre-action/Deluge use. • Styles 4, 6, or 7* signaling line circuits. • Two to 244 SLCs each supporting 159 sensors and 159 modules. • 625K baud ARCNET communications using wire, fiber, or mixed configurations for installation flexibility. • High-speed 32 bit processor and 4100 event history log. • Advanced Boolean logic-based programming such as AND, OR, NOT, time delay and calendar functions configurable via computer programming. • Supports up to (16), ASM-16 addressable switch or ANU-48 LED driver modules per ILI-MB-E3/ILI95-MB-E3. • Two Class A, Style Z or Class B, Style Y, notification appliance circuits rated at 2.0 amps. per circuit. • Integral city connection. • Flexible 115,200 baud high speed RS-232 interface. • 40 character user-defined text per device. • Supports up to five LCD-7100/RAN-7100 displays and six LCD-E3 keyboard displays per ILI-MB-E3/ILI95-MB- E3. *Style 7 wiring requires the use of System Sensor M500X Isolator Modules. Expandable Emergency Evacuation System E3 Series GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0637 Rev. O page 2 of 2 www.gamewell-fci.com Description (Continued) Each ILI-MB-E3/ILI95-MB-E3 can support as many as six- teen ANU-48 LED Driver modules supporting hundreds of LEDs on a 3rd party graphic annunciator for remote annun- ciation. The ANU-48 modules may be installed in any Listed remote annunciator. It can be remotely located via an RS-485 serial interface. An array of cabinets allows for neat, compact, attractive installations. Installation The E3 Series expandable emergency evacuation system offers four cabinet size options. A typical cabinet includes a backbox, an inner door, and an outer door. The E3 Series cabinet assembly is a compact 19 3/8” (49 cm) wide wall- mounted enclosure. Cabinet A includes the following four options: • Cabinet A1 inner door mounted to the backbox. The backbox houses one NGA module. • Cabinet A2 inner door mounted to the backbox. The backbox houses one LCD-E3 module. • Two or three-bay inner door mounted to the backbox. The backbox typically houses one LCD-E3, or one NGA, and one or two ASM-16 modules. Cabinet B contains a space for the ILI-MB-E3/ILI95-MB-E3, PM-9/PM-9G modules and batteries set inside the back- box. Additional module options mounted on the backbox include the DACT-E3, and RPT-E3 or ILI-S-E3/ILI95-S-E3/ ANX. The 2-bay inner door houses one LCD-E3 module and one ASM-16 module. Both Cabinets C and D include the following: • Pre-assembled outer door that gives visibility to the fire fighter’s phone handset and a microphone voice messaging system. • Two inner door panel selections that may contain optional modules to meet the facility operation requirements. In the Cabinet B, C and D backboxes, the ANX appears in the same place as the ILI-MB-E3/ILI95-MB-E3 and PM-9/ PM-9G. For information on the installation instructions for any of the E3 Series cabinets, refer to the E3 Series® Expandable Emergency Evacuation Installation/Operating Manual Part Number: 9000-0574. Features (Continued) Velociti ® Intelligent Sensor Features: • Poll 318 devices in less than two seconds. • Activate up to 159 outputs in less than five seconds. • LED’s blink associated device address during Walk Test. • Fully digital, hi-precision protocol. • Up to 9 levels of sensitivity adjustment. • Pre-Alarm adjustable between 15 levels for both Alert and Action. • Day/night automatic sensing adjustment. • Sensitivity windows: - Ion .05 to 2% obscuration. - Photo 1 to 3% obscuration. - Laser .02 to 2% obscuration. - MCS Acclimate2F .5 to 4%, also self-adjustable options 1 to 2%, 2 to 3%, and 3 to 4%. - HARSH 1 to 3% obscuration. • Drift compensation. • Each Loop Card has its own integral processor providing maximum survivability on loss of any other component. SLC provides full response on loss of any other system processor. • Optional programmable switches can be configured to enable, disable or group any combination of output devices. • Integrated point or Grouped Cross Zoning allows for numerous devices installed at any location to cooperate and determine alarm condition. • Automatic detector sensitivity testing. • DIRTY and VERY DIRTY detector maintenance alerts. Specifications Operating Voltage:24 VDC Operating Temperature: Not to exceed the range of 32° to 120° F (0 to 49° C) Relative Humidity:Not to exceed 93% non-con- densing at 90° F (32° C) Ordering Information Part Number Description ILI-MB-E3 Intelligent Loop Interface-Main Board ILI95-MB-E3 Intelligent Loop Interface-Main Board ILI-S-E3 Intelligent Loop Interface-Expansion Board ILI95-S-E3 Intelligent Loop Interface-Expansion Board ANX-SR Addressable Node Expander-Single Ring ANX-MR-FO Addressable Node Expander-Multi-Ring Fiber Optic ANX-MR-UTP Addressable Node Expander-Multi-Ring Twisted-pair LCD-E3 LCD-E3, LCD Keypad Display RPT-E3-FO RPT-E3-UTP Network Repeater (fiber and twisted-pair) Network Repeater (twisted-pair only) DACT-E3 Digital Alarm Communicator Transmitter ANU-48 ANU-48 LED Driver Module ASM-16 Addressable Switch Module NGA LCD Network Graphic Annunciator PM-9 Power Supply Module PM-9G Power Supply Module LCD-7100 Remote LCD Display RAN-7100 Remote LCD Display For additional information on the cabinets, refer to the E3 Series Cabinets data sheet (Part Number: 9020-0649). Seismic Battery Bracket Kits For information on the types of Seismic Battery Bracket Kits that are available, the Seismic Battery Bracket Kit Part Numbers and the installation instructions, refer to the following documents: • Seismic Battery Bracket Installation Guide, P/N: 53839 • E3 Series Cabinets Data Sheet, P/N: 9020-0649 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2013 Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0627 Rev. F page 1 of 1 Velociti® Series AOM-2SF Addressable Output Relay Supervised Control Module SIGNALING S1949 3023594 APPROVED FM 227-03-E Vol.IV MEA Approved 7300-1703:0102 Description Velociti® is a registered trademark of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. The Gamewell-FCI Velociti® Series addressable output supervised control module (AOM-2SF) allows an Gamewell-FCI analog addressable fire alarm control to switch an external power supply, such as a DC supply or audio amplifier (up to 80 VRMS) to notification appliances. The AOM-2SF notification appliance circuit can be wired either Class A (Style Z) or Class B (Style Y). It also super- vises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN or SHORT CIR- CUIT. The module contains a panel controlled LED. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm control panels. These devices oper- ate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is a response speed up to five times greater than the earlier designs. The AOM-2SF module is designed for installation in the signaling line circuit of any Gamewell-FCI analog address- able control panel. The signaling line circuits of Gamewell- FCI analog addressable control panels are designed to accommodate up to 159 modules per circuit. The AOM- 2SF is designed to mount in a 4” (10.16 cm) square junction box 2 1/8” (5.5 cm) deep. Relay Contact Ratings Current Rating Maximum Voltage Load Description Application 3A 30 VDC Resistive Non-Coded 2A 30 VDC Resistive Coded 0.9A 110 VDC Resistive Non-Coded 0.5A 125 VAC Resistive Non-Coded 0.5A 30 VDC Inductive (L/R=5ms) Coded 1A 30 VDC Inductive (L/R=2ms) Coded 0.5A 125 VAC Inductive (PF=.35) Non-Coded 0.7A 75 VAC Inductive Non-Coded Features • Listed under UL Standard UL2572 for Mass Notification. • Compact Size allows easy installation. • Class A, Style Z, or Class B, Style Y notification appliance circuit. • Will accommodate audio amplifiers up to 80 VRMS. • FM Listed as suitable for a releasing device service. • Bicolor LEDS flash green whenever the module is addressed, and lights steady red on alarm*. *Note: Only the red LED is operative in panels that do not operate in Velociti ® mode. Specifications Supervisory Current:.000375 amps Alarm Current:.0065 amps Operating Temperature:32° to 120° F (0° to 49° C) Relative Humidity:10 to 93% relative humidity (non-condensing) Dimensions:4 1/2” H x 4” W x 1 1/4” D (11.4 H x 10.2 W x 3.2 D cm) Ordering Information Part Number Description AOM-2SF Addressable output supervised control module AOM-2SF GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60475 Rev. E page 1 of 4 InnovairFlex™ Series DNR/DNRW Duct Smoke Housing Intelligent Non-Relay Photoelectric Duct Smoke Housing FM 3029700 APPROVED SIGNALING S911 MSFM 2202 2207 7272-1703:0121 S911 Description The InnovairFlex™ Series, DNR intelligent, non-relay pho- toelectric duct smoke detector, and the DNRW watertight, non-relay photoelectric duct smoke detector feature a piv- oting housing that fits both square and rectangular foot- prints. These detectors are capable of mounting to a round or rectangular duct. The DNR/DNRW detectors can be used with the E3 Series® and 7100 Series Systems. Note: The InnovairFlex™ Series, DNR requires the Veloc- iti® Series, ASD-PL2FR Sensor and AOM-2RF, if relays are required for the fan control. The DNRW duct smoke detector, with its NEMA 4 rating, is Listed as a watertight enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water. These features allow operators to use the detector in the most extreme environments. The units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of -4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). An improved cover design isolates the sensor head from the low-flow feature for simple maintenance. A cover tam- per feature was added to indicate a trouble signal for a removed or improperly installed sensor cover. The InnovairFlex housing provides a 3/4-inch conduit knockout and ample space to facilitate easy wiring and mounting of the relay module. The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories. WARNING:Duct smoke detectors have specific limitations. DUCT SMOKE DETECTORS ARE: NOT a substitute for an open area smoke detector, NOT a substitute for early warning detection, and NOT a replacement for a building’s regular fire detection system. Refer to NFPA 72 and 90A for additional duct smoke detector 2911 application information. E3 Series® and Velociti® are registered trademarks and InnovairFlex™ is a trademark of Honeywell International, Inc. UL® is a registered trademark of Underwriters Laboratories Inc. Features • Photoelectric, integrated low-flow technology • Air velocity rating from 100 ft/min to 4,000ft/min (0.5m/s to 20.32m/sec) • Versatile mounting options: square or rectangular configuration • Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 95% non-condensing) • Patented sampling tube installs from front or back of the detector with no tools required • New Cover tamper signal • Increased wiring space with a newly added 3/4-inch conduit knockout • Available space within housing to accommodate the mounting of the relay module • Easily accessible code wheels on sensor head (sold separately) • Clear cover for convenient visual inspection •UL® 268A Listed • Remote testing capability • Requires SLC line power only • NEMA Type 4 UL Listed for non-hazardous indoor and outdoor applications (DNRW only) • UV Resistant, UL ® Listed housing and cover material (DNRW only) InnovairFlex-DNR/DNRW GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60475 Rev. E page 2 of 4 www.gamewell-fci.com Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor InnovairFlex™ DNR Intelligent Non-Relay Photoelectric Duct Smoke Detector and DNRW Watertight NEMA4 Duct Smoke Detector. The detector housing shall be UL Listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4,000 ft/min (0.5 m/sec to 20.32 m/ sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring. Physical Specifications Size: Rectangular Dimensions:14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.6 cm) Depth Square Dimensions:7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight:1.6 lb (0.73 kg) Environmental Rating:NEMA4 (DNRW only) Operating Temperature Range:–4° to 158°F (–20° to 70°C) Storage Temperature Range:–22° to 158°F (–30° to 70°C) Operating Humidity Range:0% to 95% relative humidity non-condensing Air Duct Velocity:100 to 4000 ft/min (0.5 to 20.32 m/sec) DCOIL - (if included)17.5 - 26.4 VDC .95mA max. Electrical Ratings For information on the electrical specifications, refer to the InnovairFlex DNR Duct Smoke Detector Installation Instructions, P/N I56-3051-001R. Accessory Current Loads at 24 VDC Device Standby Trouble RA100Z 0 mA 12 mA Max. RTS151/RTS151KEY 0 mA 12 mA Max. Installing the InnovairFlex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab. (Figure 3 illustrates the front locking tab). Figure 1 Figure 2 Figure 3 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60475 Rev. E page 3 of 4 Wiring for Intelligent Non-Relay Duct Smoke Detector Figure 4 System Wiring Diagram for DNR Figure 5 DNR to RA100Z Figure 6 DNR to RTS151/RTS151 Key Important Notes: • The use of either RTS151 or RTS151KEY requires the installation of an accessory coil, DCOIL, sold separately. For additional information, refer to the DNR or DNRW Duct Smoke Detector Installation Instructions, P/N I56-3051-001R and the Duct Application Smoke Detectors Application Guide. • The RTS151/RTS151KEY test coil circuit requires an external 24 VDC power supply which must be UL Listed. RA100Z RT151/RTS151KEY TEST COIL + TEST COIL - COMM + OUT (CONV ONLY) + COMM – RA/RTS – RA + RTS + RTS451/RTS451KEY RTS151/RTS151KEY RTS + RA + RA/RTS - COMM - OUT (CONV ONLY) + COMM + TEST COIL - TEST COIL + DNR TO RTS451/RTS451KEY/RTS151/ RTS151KEY WITH “R” REMOTE TEST CAPABLE DETECTOR HEAD OPTION: JUMPER 1 2 3 4 5 EXTERNAL (-) POWER (+) SUPPLY REMOTE TEST STATION LED OPTION 1 PER UNIT TEST COIL OPTION 1 PER UNIT 95mA CURRENT DRAW GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60475 Rev. E page 4 of 4 www.gamewell-fci.com Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accesso- ries are UL Listed. Figure 7 RTS151 UL S2522 Figure 8 RTS151KEY UL S2522 Figure 9 RA100Z UL S2522 Figure 10 ASD-PL2FR Ordering Information Part Number Description DNR Intelligent non-relay photoelectric low-flow duct smoke detector DNRW Watertight intelligent non-relay photoelectric low-flow duct smoke detector ASD-PL2FR Intelligent photoelectric smoke sensor with remote test capability in duct applications Accessories Part Number Description DCOIL Remove test coil required with RTS151/RTS151151KEY DST1 Metal sampling tube duct width up to 1 ft (0.3m) DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) DST3 Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m) DST5 Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m) DST10 Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) DH400OE-1 Weatherproof enclosure ETX Metal exhaust tube duct width 1ft (0.3m) M02-04-00 Test magnet P48-21-00 End cap for metal sampling tubes RA100Z/RA100ZA Remote annunciator alarm LED RTS151 Remote test station RTS151KEY Remote test station with key lock Agency Listings Multi-Voltage Conventional Relays System Sensor’s multi-voltage conventional relays are used for high-current switching applications such as fan and damper assembly control, door control, air handling unit controls, and other types of system interfacing. Features Multi-voltage operation Activation LEDs Easy and flexible installation Reliable and robust design Multipurpose field installations Multi-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T/20T and R-14T/24T Removable front cover on steel enclosure for R-10E/R-20E and R- 14/R-24E, which mount inside the enclosure LED viewing hole on top of the steel enclosure’s cover Extra pair of wires for redundant power input on PR-3 Terminal strip field wiring connections, mounting track, and hardware • • • • • • • • • • The R-10T, R-20T, R-14T, and the R-24T models are multi- voltage relays with terminal strip field wiring connections, mounting track, and hardware. The R-10T is a single FORM–C (SPDT) relay with a red activation LED, and the R-14T is a four-gang 1 FORM–C (SPDT) relay with four red activation LEDs. The R-20T is a single 2 FORM–C (DPDT) relay with a red activation LED, and the R-24T is a four-gang 2 FORM–C (DPDT) relay with four red activation LEDs. The R-10E/R-20E and R-14E/R-24E are similar to the T-series track mount relays, but they are mounted into a steel enclosure. The enclosure has a removable front cover that provides easy access and an LED viewing hole on the top of the cover. PR-1/PR-2/PR-3 are epoxy encapsulated multi-voltage relays. They are single-pole double-throw relays that use a red LED as a visible indication of relay coil energization. PR–3 is identical to PR–2, except it has an extra pair of wires for redundant power input. Model EOLR-1 is an epoxy encapsulated, single-pole single-throw, normally open relay that can be used as an end of line device in fire alarm systems, e.g. to supervise power supplies. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2007 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0372-005 • 3/07 • #1782 Specifications: R-10T/R-14T/R-20T/R-24T Operating Voltage 18 – 35 VDC, 18 – 35 VAC, 115 VAC, 230 VAC Operating Current 20 mA DC max. @ 24 VDC, 24 VAC, 115 VAC, 230 VAC (R-10T/R-14T) 40 mA DC max. @ 24 VDC, 24 VAC, 115 VAC, 230 VAC (R-20T/R-24T) Operating Temperature –40°F to 158°F (–40°C to 70°C) Humidity Range 10% – 93% non-condensing Dimensions R-10T/R-20T: 2.5˝L × 3.35˝W × 1.2˝H R-14T/R-24T: 10˝L × 3.35˝W × 1.2˝H Contact Ratings 24 VDC: 7 A with L/R = 5 mS 120 VAC: 10 A 120 VAC: 1/6 HP 230 VAC: 7 A Specifications: R-10E/R-14E/ R-20E/R-24E Operating Voltage 18 – 35 VDC, 18 – 35 VAC, 115 VAC, 230 VAC Operating Current 20 mA DC max. @ 24 VDC, 24 VAC, 115 VAC, 230 VAC (R-10E/R-14E) 40 mA DC max. @ 24 VDC, 24 VAC, 115 VAC, 230 VAC (R-20E/R-24E) Operating Temperature –40°F to 158°F (–40°C to 70°C) Humidity Range 10% – 93% non-condensing Dimensions R-10E/R-20E: 5.1˝L × 3.75˝W × 2.5˝H R-14E/R-24E: 11˝L × 5.3˝W × 2.5˝H Contact Ratings 24 VDC: 7 A with L/R = 5 mS 120 VAC: 10 A 120 VAC: 1/6 HP 230 VAC: 7 A Multi-Voltage Conventional Relay Specifications PR–1 E0LR–1 PR–3 PR–2 R–10T R–14T R-10E & R-20E Enclosure R-14E & R-24E Enclosure Specifications: PR-1 Operating Voltage 18 – 35 VDC, 18 – 35 VAC, 120 VAC Operating Current 15 mA DC max. @ 24 VDC, 24 VAC, 120 VAC Operating Temperature –40°F to 158°F (–40°C to 70°C) Humidity Range 10 – 93% RH Wire Length 8˝ minimum Dimensions 0.87˝H × 2.01˝W × 1.42˝D Contact Ratings 24 VDC: 7 A with L/R = 5 mS 120 VAC: 7 A max. (0.35 PF) 250 VAC: 10 A resistive 30 VDC: 10 A resistive Specifications: PR-2/PR-3 Operating Voltage 10 to 40 VDC Operating Current 30 mA DC max. Operating Temperature –40°F to 158°F (–40°C to 70°C) Humidity Range 10 – 93% RH Wire Length 8˝ minimum Dimensions 0.91˝H × 1.65˝W × 1.22˝D Contact Ratings 120 VAC: 10 A max. (resistive load) 120 VAC: 7 A max. (0.35 PF) 250 VAC: 10 A max. (resistive load) 30 VDC: 10 A max. (resistive load) Specifications: EOLR-1 Operating Voltage 9 to 40 VDC Operating Current 20 mA DC max. Operating Temperature –22°F to 140°F (–30°C to 60°C) Humidity Range 10 – 93% RH Wire Length 8˝ minimum Contact Ratings 120 VAC: 0.5 A max. (resistive load) 30 VDC: 3 A max. (resistive load) GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2010 by Honeywell International Inc. All rights reserved.www.gamewell-fci.com 9021-60521 Rev. B page 1 of 2 HPFF8 NAC Expander/Power SupplyDescription The Gamewell-FCI, HPFF8 is a Notification Appliance Cir- cuit (NAC) expansion panel designed to extend the power capabilities of existing NACs and provide power for the auxiliary devices. The HPFF8 connects to any 12 or 24V Fire Alarm Control Panel (FACP) or stand alone. The HPFF8 is available in 8.0 amps. It provides regulated and filtered 24VDC power to each of the four NACs and an auxiliary output. The NAC outputs are rated at 3.0 amps each (the total output cannot exceed 8.0 amps). The auxil- iary output is rated at 2.0 amps. This output is continuously supplied, even in alarm, and therefore must be taken into account for power supply loading and battery size calcula- tions. The NAC outputs may be configured as any of the follow- ing: • Four Class B (Style Y) • Two Class A (Style Z) • Two Class B and one Class A • Four Class A with the optional HPP31076 Class A adapter installed These power supplies contain an internal Battery charger capable of charging up to 26.0 amp-hour (AH) batteries. The HPFF8 is mounted in lockable wall cabinet units that can accommodate up to two (2), 18AH batteries. A multi- pack option allows for up to four chassis mount units installed in a single lockable SBB-D4 enclosure. These chassis mount units have a "CM" suffix, HPFF8CM and can accommodate two 12AH batteries. Power supplies are available in either 120VAC/60 Hz or 240VAC/50 Hz. One of the most challenging aspects of a retrofit applica- tion is locating the existing End-of-Line (EOL) resistor. In these applications that have EOL values, other than the 3.9k normally used with the HPFF8, a single resistor matching the existing EOL can be used as a reference for all the outputs. This feature speeds the installation and the system checkout, because the actual EOL does not need to be located and changed in the circuit. The reference resistor must be within the range of 1.9k to 25k. Features • Four (4) supervised notification application circuits (NACs) capable of supplying +24VDC at 3.0 amp maximum each • NAC output circuits may be configured as any of the following: - Four Class B (Style Y) - Two Class B & one Class A - Two Class A (Style Z) - Four Class A with the optional HPP31076 Class A adapter installed • Four field-programmable operational modes • 2.0 amp auxiliary continuously supplied output • Two (2) fully supervised input/output control circuits • Temporal coding and sync protocols compatible with the following notification appliance brands: - System Sensor - Faraday - Gamewell - Amseco - Cooper-Wheelock - Gentex • Supervised AC input, battery voltage, auxiliary output, charger, and earth ground faults • Trouble indication for supervision of the following: - NAC circuits - Auxiliary output - AC input - Charger - Battery voltage - Open contacts in the initiat- ing device signal inputs (for FACP trouble notification) - Earth ground faults by individual status LED's • Separate Trouble and AC Fail Form-C relay Contacts HPFF8 An ISO 9001-2000 Company 7315-1637:0102 SIGNALING S24562 FM APPROVED GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60521 Rev. B page 2 of 2 www.gamewell-fci.com Features (Continued) • The Trouble Form-C relay contacts selectable for imme- diate or a 2 hour delay with AC failure • 26 AH battery charger capability; the wall cabinet supports two 12V 18AH batteries, while the multi-pack equipment cabinets supports two 12V 12AH batteries. • NAC Overload protection and indication • Up to four chassis mount units (HPFF8CM) can be installed in the SBB-D4 backbox • Wall mount units can be configured to internally house the following: - one AOM-2SF single control module - one AOM-2R single relay module Specifications Primary Input Power:120VAC/60Hz, 3.6A or 220VAC/50Hz, 1.5A Secondary Power:24 volt operation: two (2), 7-24 AH batteries Battery Charging Capacity:Up to 26 AH batteries mounted Battery Space: HPFF8 Cabinet:Up to two 18AH batteries SBB-D4 Cabinet:Up to two 12AH batteries per supply Total Output Power:8.0A max Standby Current: 0.030 A Auxiliary Power Output:0.15A under all conditions 2.0A if load is removed dur- ing operation (external relay or AC Fail Relay is required) Specifications (Continued) NAC Output Ratings:24VDC fully regulated, 3.0A max per circuit (8.0A total) End-of-Line Resistor Range: 2K to 25k ohm, ½ watt Common Trouble Relay/AC Fail Relay:2.0A at 28VDC or 120VAC Input Control Circuit:16-30VDC @ 5mA min. Temperature Rating:32°F to 120°F (0°C to 49°C Relative Humidity:10% to 93% non-condensing Cabinet Dimensions: HPFF8 Cabinet:16.65” W x 19.0” H x 5.2” D (42.29 W x 48.26 H 13.23 D cm) SBB-D4 Cabinet:24” W x 45.9” H x 5.15” D (60.96 W x 116.52 H x 13.1D cm) Ordering Information Part Number Description HPFF8 8A fire rated power supply operating at 120VAC/60 Hz. Unit includes red enclosure with HPP lock and key HPFF8CM 8A fire rated power supply - chassis mounted operating at 120VAC/60 Hz. Unit includes mounting hardware for installation in the SBB-D4 enclosure HPFF8E 8A fire rated power supply operating at 240VAC/50 Hz HPFF8CME 8A fire rated power supply chassis mounted operating at 240VAC/50 Hz HPP31076 Class A (Style Z) NAC module FCI-VDR-D4 Vented door, PK-625 lock and key for SBB-D4 backbox, black SBB-D4 Backbox, accepts up to 4 chassis, black 0.006 A 0.267 A Qty Draw Standby Qty Draw Alarm 0 x 0.08100 1 x 0.15000 0.15000 0 x 0.08100 0 x 0.15000 Intel. Loop Interface Main Board - Apollo (ILI95-MB-E3)0 x 0.05000 0 x 0.09100 Intel. Loop Interface Supplement Board - Apollo (ILI95-S-E3)0 x 0.05000 0 x 0.09100 E3 Panel, 1 SLC 0 x 0.05600 0 x 0.07600 E3 Panel, 1 SLC with DACT 0 x 0.07500 0 x 0.09500 0 x 0.06500 0 x 0.08500 0 x 0.08500 0 x 0.10500 120V Power Supply Sub-Assembly (PM-9)0 x 0.05000 0 x 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.05000 0 x 0.02400 0 x 0.02800 0 x 0.01300 0 x 0.01300 0 x 0.01800 0 x 0.01800 0 x 0.05000 0 x 0.07500 0 x 0.20000 0 x 0.20000 0 x 0.01100 0 x 0.01100 0 x 0.01100 0 x 0.01100 0 x 0.06500 0 x 0.06500 Intelligent Network Inferface Module (INI-7100)0 x 0.04000 0 x 0.04000 0 x 0.02000 0 x 0.02000 0 x 0.03500 0 x 0.20000 0 x 0.00100 0 x 0.00100 0 x 0.00100 0 x 0.00100 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.02000 0 x 0.00200 0 x 0.00650 0 x 0.15000 0 x 0.15000 0 x 0.05000 0 x 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.05000 0 x 0.08600 0 x 2.20600 Amplifier Sub-assembly, 50 watt 70V (AM-50-70)0 x 0.04900 0 x 2.30000 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.02000 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00030 0 x 0.00650 0 x 0.00030 0 x 0.00650 9 x 0.00030 0.00270 9 x 0.00650 0.05850 0 x 0.00038 0 x 0.00500 9 x 0.00038 0.00338 9 x 0.00650 0.05850 0 x 0.00030 0 x 0.00700 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 1 1 Intel. Loop Interface Supplement Board (ILI-S-E3) Total Standby Load:0.006 A 0.267 ATotal Alarm Load: E3 Panel, 2 SLC with DACT 2. E3 Optional Modules Remote LED Driver Module (ANU-48) Addressable Node Expander (ANX) Digital Communicator (DACT-E3) Remote LED Driver Module (LDM-7100) Optional Remote Serial Annunicator (LCD-7100) Alarm CurrentStandby Current System Current Draw - Tie to Existing FACP E3 Series Control Panel with Broadband Total AlarmTotal Standby Intel. Loop Interface, Main Board (ILI-MB-E3) Addressable Switch Sub-assembly (ASM-16) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Signal (AOM-2SF) 1. System Device E3 Panel, 2 SLC Amplifier Sub-assembly, 50 watt 25V (AM-50) 5. INI-VGX Voice Gateway LCD Display & Switch Control (LCD-E3) ARCNET Repeater (RPT-E3) Printer Transient Module (PTRM) Firefighter's Telephone (Handset) 3. 7100 Optional Modules Intel. Network Command Voice Gateway (INI-VGE) Addressable Switch Sub-assembly (ASM-16) Voice Paging Microphone (Microphone) Network LCD Annunicator (NGA) Auxiliary Switch Sub-Assembly (ASM-16) 4. INI-VGC Command Center Intel. Network Command Center (INI-VGC) 6. INI-VGE Command Center Voice Gateway DNR Firefighter's Telephone (Handset) Addressable Output Module-Signal (AOM-2SF) Intel. Network Voice Gateway (INI-VGX) 120V Power Supply Sub-Assembly (PM-9) Class A Option Module (CAOM) Municipal Circuit Option Module (MCOM) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) Voice Paging Microphone (Microphone) MS-7AF CO1224T 8. Notification Appliances Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) ASD-PL2F/ASD-IL2F 7. Smoke Detectors/Modules ATD-RL2F/ATD-HL2F Device AMM-4F AOM-2RF Protected Premises:Date:4/21/2017 Address: City:State:UT Zip:83440 Prepared By:Phone:801-468-8300 Address:Email: City:State:Utah Zip:84115 Secondary Load Requirements 0.20 Amp Hours Total (AH) 0.15 0.02 0.17 x 1.20 0.20 AH 31.00 Amp Hours Battery Distribution Chart Spare Battery Capacity 30.80 Amp Hours Secondary Standby Load 0.17 Amp Hours Secondary Alarm Load 0.03 Amp Hours 0.267 A x x Select batteries from the list below. Total Secondary Load System Power Requirements E3 Fire Alarm Control Panel with Broadband Battery Selection Secondary Standby Load 0.006 A Secondary Alarm Load 1481 S Major Street office@nelsonfire.com Salt Lake City 24 hours Required Standby Time Austin Building HVAC Upgrade BYU-Idaho 525 South Center Street Rexburg Nelson Fire Systems Current Draw Time (hours) Total Secondary Load from the calculation table below. Shows amp-hour distribution of your selections. Derating factor Secondary Load Requirements 31 AH Battery (12 volt) Required Alarm Time (hours) 0.084 hours Spare Battery Capacity 99% Secondary Standby Load 1% Secondary Alarm Load 0%Spare Battery Capacity Secondary Standby Load Secondary Alarm Load