LOAD SHORT FORM - 16-00308 - 2293 W 900 S - Summerfield - SFR
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 1 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Load Short Form April 6, 2016Date:Entire House By: Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Kartchner HomesFor: Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960603BN Cond GSX130301B AHRI ref 7365096 Coil CAPF3030D6D AHRI ref 7365264 Efficiency 96.1 AFUE Efficiency 11.5 EER, 13.5 SEER Heating input Btuh60000 Sensible cooling Btuh19600 Heating output Btuh52000 Latent cooling Btuh8400 Temperature rise °F63 Total cooling Btuh28000 Actual air flow cfm900 Actual air flow cfm900 Air flow factor cfm/Btuh0.026 Air flow factor cfm/Btuh0.087 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room2 33 1314 169 34 15 Room9 110 1694 212 44 18 Room10 154 1252 207 33 18 Room11 190 3391 587 88 51 Room12 135 1698 410 44 36 Room13 453 3800 2068 99 180 Room15 162 1301 738 34 64 Room16 248 3155 1344 82 117 Room17 42 320 57 8 5 Room1 1068 16718 4576 434 397 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 2 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N Entire House d 2593 34644 10368 900 900 Other equip loads 6865 1265 Equip. @ 0.94 RSM 10935 Latent cooling 0 TOTALS 2593 41509 10935 900 900 2016-Apr-13 14:39:37 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 1 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Building Analysis April 6, 2016Date:Entire House By: Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Kartchner HomesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 29.6123064.9Walls 19.2797922.8Glazing 1.247911.4Doors 5.522691.5Ceilings 12.853173.63.6Floors 15.262932.2Infiltration 00Ducts 00Piping 00Humidification 16.56865Ventilation0Adjustments 100.041509Total Cooling Walls Glazing Other Ceilings Infiltration Ventilation % of loadBtuhBtuh/ft²Component 10.211820.5Walls 62.2723620.7Glazing 1.01172.8Doors 10.812540.8Ceilings 000Floors 5.05800.2Infiltration 00Ducts 10.91265Ventilation 00Internal gains 00Blower 0Adjustments 100.011633Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 64 Btuh/ft²-°F Data entries checked. 2016-Apr-13 14:39:37 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 1 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Component Constructions April 6, 2016Date:Entire House By: Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Kartchner HomesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) Semi-tightConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1320.4713774.9421.00.065279n 1610.4716804.9421.00.065340e 1160.4712064.9421.00.065244s 1800.4718724.9421.00.065379w 5890.4761354.9421.00.0651242all 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 2"x6" wood frm, 16" o.c. stud 1320.4713774.9421.00.065279n 1490.4715514.9421.00.065314e 1340.4713984.9421.00.065283s 1770.4718454.9421.00.065374w 5930.4761714.9421.00.0651249all Partitions (none) Windows 61C: 61C; 6.67 ft head ht 3509.9080622.800.30035n 5389.90123922.800.30054n 193632.3136822.800.30060e 192032.3135722.800.30060e 160717.7207022.800.30091s 88517.7114022.800.30050s 723620.7797922.800.300350all Doors metal: Door, mtl pur core type 582.7823911.46.50.15021n 582.7823911.46.50.15021w 1172.7847911.46.50.15042all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 12540.8422691.5250.00.0201493 Floors 2016-Apr-13 14:39:37 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 2 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N 22B-10cpm: Bg floor, heavy dry or light damp soil, on grade depth, r-10 edge ins, carpet flr fnsh 00396627.010.00.355147 00135127.010.00.35550 00531727.010.00.355197all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 1 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Project Summary April 6, 2016Date:Entire House By: Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Kartchner HomesFor: Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89 Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14 Daily range H Relative humidity %50 Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh34644 Structure Btuh10368 Ducts Btuh0 Ducts Btuh0 Central vent (98 cfm)6865 Btuh Central vent (98 cfm)Btuh1265 Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh41509 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh10935 Method Latent Cooling Equipment Load SizingSimplified Construction quality Semi-tight 0Fireplaces Structure Btuh-806 Ducts Btuh0 CoolingHeating Central vent (98 cfm)Btuh-1758 25932593Area (ft²)Equipment latent load Btuh0 2443724437Volume (ft³) Air changes/hour 0.110.22 Equipment total load Btuh10935 Equiv. AVF (cfm)4590 Req. total capacity at 0.70 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN; JANITROL; AMANA DISTI... Model GMSS960603BN Cond GSX130301B AHRI ref 7365096 Coil CAPF3030D6D AHRI ref 7365264 Efficiency 96.1 AFUE Efficiency 11.5 EER, 13.5 SEER Heating input Btuh60000 Sensible cooling Btuh19600 Heating output Btuh52000 Latent cooling Btuh8400 Temperature rise °F63 Total cooling Btuh28000 Actual air flow cfm900 Actual air flow cfm900 Air flow factor cfm/Btuh0.026 Air flow factor cfm/Btuh0.087 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2016-Apr-13 14:39:37 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 1 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:AED Assessment April 6, 2016Date:Entire House By: Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Kartchner HomesFor: Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 27.7%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37Right-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 1...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Right-J® W or ksheet April 6, 2016Date:Entire House By:Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Entire House Room2 2 Exposed wall 304.0 ft 11.5 ft 3 Room height 9.4 dft 10.0 heat/coolft 4 Room dimensions ft6.5x5.0 5 Room area 2593.0 f t²32.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 335 279 1377 132 50 40 196 19 .GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 35 0 806 350 10 0 236 102 .DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 21 21 239 58 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 333 279 1377 132 0 0 0 0 1 1 GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 54 0 1239 538 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 400 340 1680 161 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 60 0 1368 1936 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 374 314 1551 149 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 60 0 1357 1920 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 335 244 1206 116 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 91 0 2070 1607 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 333 283 1398 134 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 50 0 1140 885 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 400 379 1872 180 65 65 321 31 DD metalmetal 0.1500.150 ww 11.4011.40 2.782.78 21 21 239 58 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 374 374 1845 177 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1493 1493 2269 1254 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 1100 147 3966 0 33 12 310 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 393 50 1351 0 0 0 0 0 6 c) AED excursion 0 -6 Envelope loss/gain 28350 9788 1063 146 12 a)Infiltration 6293 580 251 23 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)34644 10368 1314 169 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 34644 10368 1314 169 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 34644 10368 1314 169 Air required (cfm)Air required (cfm)900 900 34 15 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37Right-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 2...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Right-J® W or ksheet April 6, 2016Date:Entire House By:Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room9 Room10 2 Exposed wall 21.0 ft 14.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft10.0x11.0 ft14.0x11.0 5 Room area 110.0 f t²154.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 1 1 GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 99 99 489 47 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 90 90 445 43 126 126 622 60 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 110 110 167 92 154 154 234 129 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 35 7 180 0 49 4 120 0 6 c) AED excursion -8 -8 Envelope loss/gain 1281 174 977 181 12 a)Infiltration 413 38 275 25 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1694 212 1252 207 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1694 212 1252 207 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1694 212 1252 207 Air required (cfm)Air required (cfm)44 18 33 18 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37Right-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 3...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Right-J® W or ksheet April 6, 2016Date:Entire House By:Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room11 Room12 2 Exposed wall 28.5 ft 12.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft190.0x1.0 ft13.5x10.0 5 Room area 190.0 f t²135.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 108 79 389 37 90 65 321 31 1 1 GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 29 0 669 290 25 0 570 247 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 14 14 67 6 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 149 149 734 70 9 9 44 4 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 190 190 289 160 135 135 205 113 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 186 28 752 0 98 9 245 0 6 c) AED excursion -22 -15 Envelope loss/gain 2832 536 1453 387 12 a)Infiltration 560 52 246 23 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3391 587 1698 410 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3391 587 1698 410 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3391 587 1698 410 Air required (cfm)Air required (cfm)88 51 44 36 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37Right-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 4...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Right-J® W or ksheet April 6, 2016Date:Entire House By:Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room13 Room15 2 Exposed wall 36.0 ft 9.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft453.0x1.0 ft17.0x9.5 5 Room area 453.0 f t²161.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 135 135 667 64 0 0 0 0 1 1 GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 189 147 726 70 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 42 0 958 1355 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 86 61 299 29 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 0 0 0 0 25 0 570 442 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 453 453 689 381 162 162 245 136 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 25 2 54 0 0 0 0 0 6 c) AED excursion 133 114 Envelope loss/gain 3093 2003 1114 721 12 a)Infiltration 707 65 187 17 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3800 2068 1301 738 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3800 2068 1301 738 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3800 2068 1301 738 Air required (cfm)Air required (cfm)99 180 34 64 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37Right-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 5...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Right-J® W or ksheet April 6, 2016Date:Entire House By:Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room16 Room17 2 Exposed wall 31.5 ft 4.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft15.0x16.5 ft4.0x10.5 5 Room area 247.5 f t²42.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD metalmetal 0.1500.150 nn 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 nn 4.944.94 0.470.47 0 0 0 0 0 0 0 0 1 1 GG 61C61C 0.3000.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.944.94 0.470.47 135 118 580 56 36 36 178 17 GG 61C61C 0.3000.300 ee 22.8022.80 32.2732.27 18 0 399 565 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.944.94 0.470.47 149 124 610 59 0 0 0 0 GG 61C61C 0.3000.300 ss 22.8022.80 17.7017.70 25 0 570 442 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 ww 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 248 248 376 208 42 42 64 35 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 FF 22B-10cpm22B-10cpm 0.3550.355 --26.9826.98 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -43 -2 Envelope loss/gain 2536 1287 242 50 12 a)Infiltration 619 57 79 7 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3155 1344 320 57 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3155 1344 320 57 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3155 1344 320 57 Air required (cfm)Air required (cfm)82 117 8 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-13 14:39:37Right-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 6...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Right-J® W or ksheet April 6, 2016Date:Entire House By:Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room1 2 Exposed wall 135.5 ft 3 Room height 10.0 heat/coolft 4 Room dimensions ft1067.5x1.0 5 Room area 1067.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 4.94 0.47 285 239 1181 113 .G 61C 0.300 n 22.80 9.90 25 0 570 247 .D metal 0.150 n 11.40 2.78 21 21 239 58 .W 12F-0sw 0.065 n 4.94 0.47 0 0 0 0 1 1 G 61C 0.300 n 22.80 9.90 0 0 0 0 W 12F-0sw 0.065 e 4.94 0.47 400 340 1680 161 G 61C 0.300 e 22.80 32.27 60 0 1368 1936 W 12F-0sw 0.065 e 4.94 0.47 0 0 0 0 G 61C 0.300 e 22.80 32.27 0 0 0 0 W 12F-0sw 0.065 s 4.94 0.47 335 244 1206 116 G 61C 0.300 s 22.80 17.70 91 0 2070 1607 W 12F-0sw 0.065 s 4.94 0.47 0 0 0 0 G 61C 0.300 s 22.80 17.70 0 0 0 0 W 12F-0sw 0.065 w 4.94 0.47 335 314 1551 149 D metal 0.150 w 11.40 2.78 21 21 239 58 W 12F-0sw 0.065 w 4.94 0.47 0 0 0 0 C 16B-50ad 0.020 -1.52 0.84 0 0 0 0 F 22B-10cpm 0.355 -26.98 0.00 1068 136 3656 0 F 22B-10cpm 0.355 -26.98 0.00 0 0 0 0 6 c) AED excursion -143 Envelope loss/gain 13761 4304 12 a)Infiltration 2958 272 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)16718 4576 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 16718 4576 15 Duct loads -0%0%0 0 Total room load 16718 4576 Air required (cfm)434 397 Job #: SF11B3 Performed for: Kartchner Homes Modern Plumbing P.O. Box 627 Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 highcountryph@yahoo.com Scale: 1 : 63 Page 1 Right-Suite® Uni ver s al 2015 15.0.18 RSU20477 2016-Apr-13 14:40:01 ...chner\Newport 2 Story\SF11B3.... N Main Floor Room1 Room2 87 cfm 34 cfm 468 cfm 87 cfm 87 cfm 87 cfm 87 cfm 6 " 6 " 14x3.25 6 " 14x3.25 6 " 14x3.25 6 " 6 " 6 " 6 " 6 " 6 " 6 " 24 x 8 6 " 14x12.00 20 x 8 7 " 5 x 8 6 " 14x3.25 6 " 14x3.25 Job #: SF11B3 Performed for: Kartchner Homes Modern Plumbing P.O. Box 627 Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 highcountryph@yahoo.com Scale: 1 : 63 Page 2 Right-S uite® Uni ver s al 2015 15.0.18 RSU20477 2016-Apr-13 14:40:01 ...chner\Newport 2 Story\SF11B3.... N Upstairs Room9 Room10 Room11 Room12 Room13 Room15 Room16 Room17 33 cfm 88 cfm 44 cfm 90 cfm 64 cfm 117 cfm 8 cfm 44 cfm 117 cfm 64 cfm 44 cfm 90 cfm 165 cfm 185 cfm 2016-Apr-13 14:39:38 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 1 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N SF11B3Job:Duct System Summary April 6, 2016Date:Entire House By: Modern Plumbing P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Kartchner HomesFor: CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.40in H2O0.40 Available static pressure in H2O0.30in H2O0.30 Supply / return available pressure 0.145 / 0.155 in H2O in H2O0.145 / 0.155 Lowest friction rate in/100ft0.069in/100ft0.069 Actual air flow cfm900cfm900 Total effective length (TEL)ft438 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk 95.018.5ShMt0x06.00.12779873344hRoom1 st1150.046.0ShMt0x06.00.07479873344hRoom1-A st1140.044.5ShMt0x06.00.07879873344hRoom1-B st1175.036.0ShMt0x06.00.06979873344hRoom1-C st1175.017.5ShMt0x06.00.07579873344hRoom1-D st2140.05.0ShMt0x06.00.10018331252hRoom10 st2130.017.0ShMt0x06.00.09851883391hRoom11 st1175.023.5ShMt0x06.00.07336441698hRoom12 st1175.025.0ShMt0x06.00.07290491034cRoom13 st1130.044.5ShMt0x06.00.08390491034cRoom13-A st1175.017.5ShMt0x06.00.0756434738cRoom15 st1165.035.5ShMt0x07.00.072117821344cRoom16 st1160.028.0ShMt0x06.00.07758320hRoom17 st1175.030.5ShMt0x06.00.07015341314hRoom2 st1175.017.5ShMt0x06.00.07518441694hRoom9 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 693 752 0.069 676 13.4 20x8 ShtMetl st2 Peak AVF 121 69 0.098 434 6.3 5x8 ShtMetl 2016-Apr-13 14:39:38 Rig ht-Su ite® U niv er sal 20 15 15 .0.18 RSU2 0477 Page 2 ...htsoftware\Kartchner\Newport 2 Story\SF11B3.rup Calc = MJ8 House faces: N Return Branch Detail Table Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb2 0x 1650 87 85.5 0.182 521 6.2 3.25x14 10x9 SJSp rt1 rb1 0x 4680 412 218.5 0.071 402 11.1 12.00x14 10x34 SJSp rt1 rb3 0x 820 117 226.5 0.069 369 6.7 3.25x14 10x9 SJSp rt1 rb4 0x 340 64 119.0 0.131 203 4.7 3.25x14 10x9 SJSp rt1 rb5 0x 440 36 128.5 0.121 140 4.1 3.25x14 10x9 SJSp rt1 rb6 0x 1070 185 100.0 0.155 584 6.7 3.25x14 10x9 SJSp rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 900 900 0.069 675 14.3 24x8 ShtMetl